Carrier Em1 Manual
Have a look at the manual Carrier Em1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
T--311 2-13 Figure 2-27 Punching out Louver HolesFigure 2-28 End Cap With Louver Figure 2-29 EM-9 Ducted Evaporator - Location - Completed Assembly Figure 2-30 School Style Ducting-Passenger SideFigure 2-31 School Style Ducting-Drivers Side
T--311 2-14 Figure 2-32 Side Mounted Hose Routing (Using 45° °° °Angles) Figure 2-33 Side Mounted Hose Routing (Straight)
T--311 2-15 2.5 EM-17 EVAPORATOR The EM-17 is available in single and dual loop applications. Due to the weight and size of the evaporator assembly it is recommended that this type evaporator and accompanying condenser and electrical controls be installed only by OEM’s (Original Equipment Manufacturers). Reinforced mounting channels must be welded to thebus roof bows in order to support the evaporator assembly. Examples of this application have been given below (See Figure 2-34). Before attempting to install this type system, it is strongly advised that you contact Carrier Transport Air Conditioning Technical Service Hot Line for assistance (1-800-450-2211). Figure 2-34 EM-17 INSTALLED 2.6 IW-1, IW-2, IW-7 & IW-14 EVAPORATORS The IW (In-Wall) evaporator assemblies are designed to be installed in the rear wall of a bus while it was being assembled at an OEM’s location. There are also OEM applications where the IW has been installed in the front of a bus. This type evaporator is not recommended for after market applications.2.7 EM-20, EM-21 & EM-22 EVAPORATORS EM-20, EM-21 and EM-22 are floor mounted heating/cooling units normally used on ambulances and/or armored trucks. For installation instructions and or information on these type systems contact Carrier Transport Air Conditioning Technical Service Hot Line (800) 450-2211.
T--311 3-1 SECTION 3 CONDENSERS 3.1 INTRODUCTION 3.1.1 Description Condensers are normally located in the bus skirt or on the bus roof. Their primary function is to reject heat from the refrigerant to the exterior of the vehicle. 3.1.2 Location Assure that the condenser will mount properly in the location of choice. Always try to fit skirt mounted condensers between the front and back wheels and always as close to the bus skirt as possible. This assures adequate air flow and avoids recirculating heat from under the bus. 3.1.3 Cap Plugs Carrier Transport Air Conditioning condensers are leak-checked and shipped with a charge of inert gas to keep the coil dry. Do not remove any of the caps/plugs from the condensers until you are ready to hook up the refrigerant lines. 3.1.4 Protection When a skirt condenser must be mounted close to a vehicle wheel, CarrierTransport Air Conditioning recommends that the condenser be protected from wheel-sling, (mud, water road salts,etc.) by a splash guard. Failure to properly locate and protect the condenser may cause a variety of problems, from corrosion to inefficient cooling, pressure increases, and compressor failure. 3.1.5 Obstructions To function efficiently the air inlet and outlet of the skirt condenser must be free of any obstruction, including the bus chassis rail and the bus skirt. Failure to have free air flow will restrict the rate of heat rejection causing apressure rise in the system. Excessive pressure may cause cooling inefficiencies and possible compressor failure. The bus skirt must always be cut out when installing a skirt mounted condenser. 3.1.6 Skirt Supports Whenever a bus skirt support must be removed in order to mount the condenser, the skirt must be resupported by the condenser assembly or by attaching an alternate skirt support. All skirt mounted condenser screens must be flat against the vehicle skirt. 3.1.7 Mounting (Skirt) All Carrier Transport Air Conditioning condensers are supplied with the proper mounting hardware. Never substitute mounting hardware. Always insure that the skirt mounted condensers are mounted on a flat surface and are level. Carrier highly recommends that “OEM’s (original equipment manufacturers) provide condenser mounting brackets in order that the bus floor does not have to be drilled through when mounting/installing the skirt condenser. 3.1.8 Mounting (Rooftop) When mounting a roof top condenser, alterations must be made to the bus roof. The installation instructions include sealing instructions which must be followed. Failure to follow these instructions will allow water to enter the passenger compartment. 3.1.9 Voltage Carrier Transport Air Conditioning condensers are designed to operate efficiently at 12.5 and 25 Volts respectively. Condensers operating at less than the required voltage will cause the fans to run slower and may cause pressure buildup and possible compressor failure.
T--311 3-2 3.2 CONDENSERS Condensers are normally located on the outside of the vehicle. Their primary function is to reject heat absorbed by the refrigerant from the passenger compartment to the outside air. Condensers are normally located on thevehicle skirt or on the roof. If space in the vehicle skirt is a problem, the CM-2 and CM-3 can be stacked on each other with a kit available from Carrier Transport Air Conditioning (Refer to paragraph 3.7) Carrier Transport Air Conditioning condenser assemblies are listed in Table 1-5. Ta b l e 3 -1CONDENSERS (Used With GEN 4 And GEN 5 Series) Component Ty p eCFM (Approx)AmpsWeightBTU Heat Rejection CM-2SKT [email protected] 16@25V66 Lbs.57,000 CM-3SKT [email protected] 24@25V76 Lbs.76,000 CM-4SKT OR RF [email protected] Lbs.43,000 CM-5SKT MT600041@24V202 Lbs.162,000 CM-7RF [email protected] 12@25V87 Lbs.76,000 CM-11RF [email protected] Lbs.57,000 KR-4RF [email protected] 22@25V187 Lbs.130,000 CM-14SKT [email protected] 30@25V95 Lbs.85,000 CM-2 STKD (2 ea)SKT [email protected] Lbs.114,000 CM-3 STKD (2 ea)SKT [email protected] Lbs.152,000 Legend: CM - Condenser Module KR - Rooftop (4 Fan) RF - Roof Mounted SKT - Skirt Mounted STKD - Stacked 3.3 CM-2, CM-3, CM-4, CM-5, & CM-14 SKIRT- MOUNTED CONDENSER ASSEMBLIES The Carrier Transport Air Conditioning Condensers listed in paragraph 3.3 are designed so they can easily be installed in the skirt of a bus, while other condenser assemblies are mounted on the bus roof. Check the location selected under the bus for any obstacles that might interfere with the proper installation of the condenser assembly. Using the dimensions listed in Table 2-1, determine that the condenser assembly will fit safely and securely in the desired location. Table 3-2 SKIRT MOUNTED CONDENSERS Condenser A(width)B(height)C(depth) CM-235.75 inch10.312 inch15.75 inch CM-348.0 inch10.312 inch15.75 inch CM-439.0 inch8.38 inch14.50 inch CM-587.5 inch15.25 inch15.281 inch CM-1461.0 Inch10.37 Inch15.75 Inch To install the skirt mounted condenser assemblies utilize the following installation procedures: a. Unpack the condenser and check for obvious dam- age. b. Make a condenser mounting template from card- board or other thin material.c. Lay condenser upside down on the template material. d. Align the front of the condenser with the straight edge of the template material. e. Mark all of the oblong mounting holes located in the front and rear of the condenser assembly. f. Mark outer edges of the condenser assembly on to the template material. g. Remove condenser from template material and cut- out template and oblong mounting holes. h. Mark center of template. i. Using the condenser template under the vehicle, find the optimum location between the front and rear wheels of the vehicle and mark the mounting holes. Note The condenser assembly should contact as many of the floor supports (stringers) as pos- sible, while hitting the least amount of skirt sup- ports. Note Always attempt to use at least one of the ve- hicles floor supports (stringers) to mount the condenser assembly. j. Drill pilot holes up through the bus (vehicle) floor. Caution Make sure there is nothing installed where you are going to drill through the bus floor. k. Using the pilot holes, drill 7/16 inch holes through the bus floor or stringers. See Figure 3-1.
T--311 3-3 NOTE To safely attach/mount the CM-2 it will require a minimum of 4 bolts, while the CM-3 requires 6 bolts. NOTE Block spacers or jam-nuts may be required if the condenser mounting area is not tight against the bus stringers. See Figure 3-3. Figure 3-1 3/8 Inch Carriage Bolts Thru Floorl. Mount the condenser using 3/8 inch diameter hard- ware. See Figure 3-2. m.Install grill/screen on condenser assembly or skirt of bus, depending on application. n. Connect discharge and liquid lines. Refer to Section 4, hose routing. o. Connect electrical harness to condenser. Refer to Section 5, electrical.Figure 3-2 Condenser Mounted With Hardware CONDENSER SCREENSKIRT MOUNTING HARDWARE SUPPLIED BY INSTALLERFLOOR MEMBERBUS FLOOR ALTERNATE MOUNTING BLOCK SPACER REQUIRED IF NO FLOOR MEMBER AT FASTENER LOCATION (STRINGER) POP RIVER 3/16 STEEL CM-3:(6) 3/8-16 GRADE 5 BOLTS CM-2:(4) 3/8-16 GRADE 5 BOLTS NOTE:MINIMUM MOUNTING HARDWARE REQUIRED MOUNTING HARDWARE SUPPLIED BY INSTALLER Figure 3-3 Installation Drawing (Typical Skirt Mounted)
T--311 3-4 Figure 3-4 CM-3 Condenser Mounting (Typical) Figure 3-5 CM-2 Condenser Mounted on an Extended Roof Van (Custom) Figure 3-6 CM-3 Mounted In Cut-A-Way Chassis
T--311 3-5 3.4 Cm-5 CONDENSER The Carrier Transport Air Conditioning CM-5 Condenser is designed to be installed in the skirt of the bus. To install the CM-5 Condenser utilize the installation procedures found in paragraph 3.3.Refer to the installation drawing enclosed with the condenser or see Figure 3-7. Note Because of the size and weight of the CM-5 condenser assembly, ten (10) bolts are re- quired to safely install it to the bus floor string- ers, Five (5) in the front and (5) in the rear. ALTERNATE MOUNTING FLOOR SKIRT POP RIVET, 3/16” STEEL OR SELF DRILLING SCREWS GRILL (3) MOUNTING HARDWARE SUPPLIED BY INSTALLER MOUNTING HARDWARE SUPPLIED BY INSTALLER CM-5(10) 3/8-16 GRADE 5 BOLTS NOTE:MINIMUM HARDWARE REQUIRED SPACER CM-5 CONDENSER Figure 3-7 CM-5 Installation Drawing
T--311 3-6 3.5 Cm-7, CM-11 ROOFTOP CONDENSER ASSEMBLIES The Carrier Transport Air Conditioning CM-7 & CM-11 condensers are designed to be installed on the roof of the bus. To install a rooftop condensers utilize the following installation procedures: a. Select a location on the bus roof where the mounting channels will span at least two roof bows.Note The ideal location will be close to the evaporator inside the bus as well as spanning two roof bows. b. Remove the rooftop condenser from the shipping box. Locate the two mounting channels, 4 mounting feet and mounting hardware. c. Remove rooftop cover. Install four mounting feet with inclosed hardware. Refer to inclosed installation drawing or see Figure 3-8. Condenser Frame Bus Roof Bow Bus Outer Skin Mounting Channel 1/4 In. Flat Washer 1/4-20 ESNA1/4 In. Spacer Bolt,1/4-20X1In. Condenser Frame Mounting FootMounting Foot 1/4 In. Flat Washer 1/4-20 ESNA1/4 In. Spacer 1/4 In. Spacer Bolt,1/4-20X1In.Bolt, 3/8-16 X 1-1/4 In. (Torque to 20 Ft. Lbs.) 3/8 In. Lock Washer 3/8 In. Flat Washer 3/8 In. Lock Washer TOPVIEW (Angle may have to be adjusted) Figure 3-8 Installing Mounting Feet & Mounting Channels d. Install the two mounting channels to the mounting feet with the enclosed hardware. Note Do not tighten the mounting hardware at this time. You may have to make adjustments to the mounting feet and rails later.e. Carefully place the condenser at the predetermined location on the bus roof. Center the condenser side- to-side on the bus roof. f. Trace around both mounting channels. g. Mark where the feed-thru-plate will be located. This is where the discharge and liquid line will be connected. Refer to the enclosed installation drawing or see Figure 3-9. Liquid line (#8 hose) - to evaporatorOptional configuration of remote mounted filter drier-sightglassFeed-Thru-Plate 1/2 in.O-Ring (4 places) Filter Drier/Sightglass W/Moisture Indicator 1/2 in.O-Ring (2 places)Drill 13/64 Dia. holes. Use 3/16 In. rivets thru outer skin, (8 places). Apply sealant to plate & rivet heads to prevent water leaks. BUS ROOF Figure 3-9 Attaching To Feed-Thru-Plate & Remote Filter Drier
T--311 3-7 h. Remove mounting channels from condenser mount- ing feet. i. Drill 13/64 In. Dia. holes thru the bus roof outer skin and roof bows using the mounting channel holes as a guide. See Figure 3-10.Note It is recommended that a drill stop be used when drilling through the bus roof. j. Apply sealant around all the holes and the mounting channels. Place the channels on the bus roof. Position mounting channel so it spans across a minimum of two roof bows. Drill a 13/64 dia. hole. Use 3/16 in. steel rivets located thru each roof bow a minimum of 8 places Drill a 13/64 Dia. holes. Use 3/16 In. rivets thru outer skin. Minimum of 20 places Figure 3-10 Attaching Mounting Channels To Bus Roof k. Using 3/16 In. Dia. steel rivets, attach the mounting channels to the bus roof. l. Where previously marked carefully cut a 3 X 4 Inch hole thru the bus roof and ceiling. This is where the feed-thru-plate will be attached. m.Place the feed-thru-plate over the cut-out. Modifica- tions may be needed in order for the plate to fit proper- ly. n. Drill 13/64 In.Dia. holes in the bus roof using the holes in the feed-thru-plate as a guide. Use all 8 holes. o. Apply sealant around all the holes and the plate. p. Using 3/16 In. Dia. steel rivets, attach the feed-thru- plate to the bus roof. q. Seal around the feed-thru-plate and the mounting channels. Apply sealant to all the rivet heads to pre- vent water leaks.Note The mounting foot angle may have to be ad- justed in order that it sits flat on the mounting channels. See Figure 3-8. r. Place the condenser back on to the mounting chan- nels. The center of the condenser must be close to the bus roof but not touching it. Adjust the mounting legs up or down for the correct height. Refer to the installation instructions enclosed or see Figure 3-11. Note Remember to lubricate all fittings, O-Rings, and refrigerant hose with mineral oil before attach- ing components. All refrigerant O-Ring fittings must be torqued to 30 ft. lbs. s. Connect the condenser discharge and liquid lines to the feed-thru-plate fittings. t. Securely mount (clamp) the filter drier/sightglass as- sembly to the ceiling at the rear of the evaporator as- sembly. 1In. Drill 0.28 Hole (8 Pls) NOTE: Use Mounting Leg as a Template.50 In. Adjust Leg to Correct Height - Then Install Hardware Figure 3-11 Adjusting Mounting Foot Height