Home > Carrier > Air Conditioner > Carrier Em1 Manual

Carrier Em1 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Carrier Em1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 29 Carrier manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							T--311
    2-13
    Figure 2-27 Punching out Louver HolesFigure 2-28 End Cap With Louver
    Figure 2-29 EM-9 Ducted Evaporator - Location - Completed Assembly
    Figure 2-30 School Style Ducting-Passenger SideFigure 2-31 School Style Ducting-Drivers Side 
    						
    							T--311
    2-14
    Figure 2-32 Side Mounted Hose Routing
    (Using 45°
    °° °Angles)
    Figure 2-33 Side Mounted Hose Routing (Straight) 
    						
    							T--311
    2-15 2.5 EM-17 EVAPORATOR
    The EM-17 is available in single and dual loop
    applications. Due to the weight and size of the
    evaporator assembly it is recommended that this type
    evaporator and accompanying condenser and electrical
    controls be installed only by OEM’s (Original Equipment
    Manufacturers).
    Reinforced mounting channels must be welded to thebus roof bows in order to support the evaporator
    assembly. Examples of this application have been given
    below (See Figure 2-34).
    Before attempting to install this type system, it is
    strongly advised that you contact Carrier Transport Air
    Conditioning Technical Service Hot Line for assistance
    (1-800-450-2211).
    Figure 2-34 EM-17 INSTALLED
    2.6 IW-1, IW-2, IW-7 & IW-14 EVAPORATORS
    The IW (In-Wall) evaporator assemblies are designed to
    be installed in the rear wall of a bus while it was being
    assembled at an OEM’s location. There are also OEM
    applications where the IW has been installed in the front
    of a bus.
    This type evaporator is not recommended for after
    market applications.2.7 EM-20, EM-21 & EM-22 EVAPORATORS
    EM-20, EM-21 and EM-22 are floor mounted
    heating/cooling units normally used on ambulances
    and/or armored trucks. For installation instructions and
    or information on these type systems contact Carrier
    Transport Air Conditioning Technical Service Hot Line
    (800) 450-2211. 
    						
    							T--311
    3-1
    SECTION 3
    CONDENSERS
    3.1 INTRODUCTION
    3.1.1 Description
    Condensers are normally located in the bus skirt or on
    the bus roof. Their primary function is to reject heat from
    the refrigerant to the exterior of the vehicle.
    3.1.2 Location
    Assure that the condenser will mount properly in the
    location of choice. Always try to fit skirt mounted
    condensers between the front and back wheels and
    always as close to the bus skirt as possible. This
    assures adequate air flow and avoids recirculating heat
    from under the bus.
    3.1.3 Cap Plugs
    Carrier Transport Air Conditioning condensers are
    leak-checked and shipped with a charge of inert gas to
    keep the coil dry. Do not remove any of the caps/plugs
    from the condensers until you are ready to hook up the
    refrigerant lines.
    3.1.4 Protection
    When a skirt condenser must be mounted close to a
    vehicle wheel, CarrierTransport Air Conditioning
    recommends that the condenser be protected from
    wheel-sling, (mud, water road salts,etc.) by a splash
    guard. Failure to properly locate and protect the
    condenser may cause a variety of problems, from
    corrosion to inefficient cooling, pressure increases, and
    compressor failure.
    3.1.5 Obstructions
    To function efficiently the air inlet and outlet of the skirt
    condenser must be free of any obstruction, including the
    bus chassis rail and the bus skirt. Failure to have free air
    flow will restrict the rate of heat rejection causing apressure rise in the system. Excessive pressure may
    cause cooling inefficiencies and possible compressor
    failure. The bus skirt must always be cut out when
    installing a skirt mounted condenser.
    3.1.6 Skirt Supports
    Whenever a bus skirt support must be removed in order
    to mount the condenser, the skirt must be resupported
    by the condenser assembly or by attaching an alternate
    skirt support. All skirt mounted condenser screens must
    be flat against the vehicle skirt.
    3.1.7 Mounting (Skirt)
    All Carrier Transport Air Conditioning condensers are
    supplied with the proper mounting hardware. Never
    substitute mounting hardware. Always insure that the
    skirt mounted condensers are mounted on a flat surface
    and are level. Carrier highly recommends that “OEM’s
    (original equipment manufacturers) provide condenser
    mounting brackets in order that the bus floor does not
    have to be drilled through when mounting/installing the
    skirt condenser.
    3.1.8 Mounting (Rooftop)
    When mounting a roof top condenser, alterations must
    be made to the bus roof. The installation instructions
    include sealing instructions which must be followed.
    Failure to follow these instructions will allow water to
    enter the passenger compartment.
    3.1.9 Voltage
    Carrier Transport Air Conditioning condensers are
    designed to operate efficiently at 12.5 and 25 Volts
    respectively. Condensers operating at less than the
    required voltage will cause the fans to run slower and
    may cause pressure buildup and possible compressor
    failure. 
    						
    							T--311
    3-2 3.2 CONDENSERS
    Condensers are normally located on the outside of the
    vehicle. Their primary function is to reject heat absorbed
    by the refrigerant from the passenger compartment to
    the outside air. Condensers are normally located on thevehicle skirt or on the roof. If space in the vehicle skirt is
    a problem, the CM-2 and CM-3 can be stacked on each
    other with a kit available from Carrier Transport Air
    Conditioning (Refer to paragraph 3.7) Carrier Transport
    Air Conditioning condenser assemblies are listed in
    Table 1-5.
    Ta b l e 3 -1CONDENSERS (Used With GEN 4 And GEN 5 Series)
    Component
    Ty p eCFM
    (Approx)AmpsWeightBTU Heat
    Rejection
    CM-2SKT [email protected]
    16@25V66 Lbs.57,000
    CM-3SKT [email protected]
    24@25V76 Lbs.76,000
    CM-4SKT OR RF [email protected] Lbs.43,000
    CM-5SKT MT600041@24V202 Lbs.162,000
    CM-7RF [email protected]
    12@25V87 Lbs.76,000
    CM-11RF [email protected] Lbs.57,000
    KR-4RF [email protected]
    22@25V187 Lbs.130,000
    CM-14SKT [email protected]
    30@25V95 Lbs.85,000
    CM-2 STKD (2 ea)SKT [email protected] Lbs.114,000
    CM-3 STKD (2 ea)SKT [email protected] Lbs.152,000
    Legend:
    CM - Condenser Module
    KR - Rooftop (4 Fan)
    RF - Roof Mounted
    SKT - Skirt Mounted
    STKD - Stacked
    3.3 CM-2, CM-3, CM-4, CM-5, & CM-14 SKIRT-
    MOUNTED CONDENSER ASSEMBLIES
    The Carrier Transport Air Conditioning Condensers
    listed in paragraph 3.3 are designed so they can easily
    be installed in the skirt of a bus, while other condenser
    assemblies are mounted on the bus roof.
    Check the location selected under the bus for any
    obstacles that might interfere with the proper installation
    of the condenser assembly.
    Using the dimensions listed in Table 2-1, determine that
    the condenser assembly will fit safely and securely in
    the desired location.
    Table 3-2 SKIRT MOUNTED CONDENSERS
    Condenser
    A(width)B(height)C(depth)
    CM-235.75 inch10.312 inch15.75 inch
    CM-348.0 inch10.312 inch15.75 inch
    CM-439.0 inch8.38 inch14.50 inch
    CM-587.5 inch15.25 inch15.281 inch
    CM-1461.0 Inch10.37 Inch15.75 Inch
    To install the skirt mounted condenser assemblies
    utilize the following installation procedures:
    a. Unpack the condenser and check for obvious dam-
    age.
    b. Make a condenser mounting template from card-
    board or other thin material.c. Lay condenser upside down on the template material.
    d. Align the front of the condenser with the straight edge
    of the template material.
    e. Mark all of the oblong mounting holes located in the
    front and rear of the condenser assembly.
    f. Mark outer edges of the condenser assembly on to
    the template material.
    g. Remove condenser from template material and cut-
    out template and oblong mounting holes.
    h. Mark center of template.
    i. Using the condenser template under the vehicle, find
    the optimum location between the front and rear
    wheels of the vehicle and mark the mounting holes.
    Note
    The condenser assembly should contact as
    many of the floor supports (stringers) as pos-
    sible, while hitting the least amount of skirt sup-
    ports.
    Note
    Always attempt to use at least one of the ve-
    hicles floor supports (stringers) to mount the
    condenser assembly.
    j. Drill pilot holes up through the bus (vehicle) floor.
    Caution
    Make sure there is nothing installed where
    you are going to drill through the bus floor.
    k. Using the pilot holes, drill 7/16 inch holes through the
    bus floor or stringers. See Figure 3-1. 
    						
    							T--311
    3-3 NOTE
    To safely attach/mount the CM-2 it will require a
    minimum of 4 bolts, while the CM-3 requires 6
    bolts.
    NOTE
    Block spacers or jam-nuts may be required if
    the condenser mounting area is not tight
    against the bus stringers. See Figure 3-3.
    Figure 3-1 3/8 Inch Carriage Bolts Thru Floorl. Mount the condenser using 3/8 inch diameter hard-
    ware. See Figure 3-2.
    m.Install grill/screen on condenser assembly or skirt of
    bus, depending on application.
    n. Connect discharge and liquid lines. Refer to Section
    4, hose routing.
    o. Connect electrical harness to condenser. Refer to
    Section 5, electrical.Figure 3-2 Condenser Mounted With Hardware
    CONDENSER
    SCREENSKIRT
    MOUNTING HARDWARE
    SUPPLIED BY INSTALLERFLOOR MEMBERBUS FLOOR ALTERNATE MOUNTING
    BLOCK SPACER REQUIRED IF NO
    FLOOR MEMBER AT FASTENER LOCATION
    (STRINGER)
    POP RIVER
    3/16 STEEL
    CM-3:(6) 3/8-16 GRADE 5 BOLTS CM-2:(4) 3/8-16 GRADE 5 BOLTS NOTE:MINIMUM MOUNTING HARDWARE REQUIRED
    MOUNTING HARDWARE
    SUPPLIED BY INSTALLER
    Figure 3-3 Installation Drawing (Typical Skirt Mounted) 
    						
    							T--311
    3-4
    Figure 3-4 CM-3 Condenser Mounting (Typical)
    Figure 3-5 CM-2 Condenser Mounted on an Extended Roof Van (Custom)
    Figure 3-6 CM-3 Mounted In Cut-A-Way Chassis 
    						
    							T--311
    3-5 3.4 Cm-5 CONDENSER
    The Carrier Transport Air Conditioning CM-5
    Condenser is designed to be installed in the skirt of the
    bus.
    To install the CM-5 Condenser utilize the installation
    procedures found in paragraph 3.3.Refer to the installation drawing enclosed with the
    condenser or see Figure 3-7.
    Note
    Because of the size and weight of the CM-5
    condenser assembly, ten (10) bolts are re-
    quired to safely install it to the bus floor string-
    ers, Five (5) in the front and (5) in the rear.
    ALTERNATE MOUNTING
    FLOOR
    SKIRT
    POP RIVET, 3/16” STEEL
    OR SELF DRILLING SCREWS
    GRILL (3)
    MOUNTING HARDWARE
    SUPPLIED BY INSTALLER
    MOUNTING HARDWARE
    SUPPLIED BY INSTALLER
    CM-5(10) 3/8-16 GRADE 5 BOLTS NOTE:MINIMUM HARDWARE REQUIRED
    SPACER
    CM-5 CONDENSER
    Figure 3-7 CM-5 Installation Drawing 
    						
    							T--311
    3-6 3.5 Cm-7, CM-11 ROOFTOP CONDENSER
    ASSEMBLIES
    The Carrier Transport Air Conditioning CM-7 & CM-11
    condensers are designed to be installed on the roof of
    the bus.
    To install a rooftop condensers utilize the following
    installation procedures:
    a. Select a location on the bus roof where the mounting
    channels will span at least two roof bows.Note
    The ideal location will be close to the evaporator
    inside the bus as well as spanning two roof
    bows.
    b. Remove the rooftop condenser from the shipping
    box. Locate the two mounting channels, 4 mounting
    feet and mounting hardware.
    c. Remove rooftop cover. Install four mounting feet with
    inclosed hardware. Refer to inclosed installation
    drawing or see Figure 3-8.
    Condenser Frame
    Bus Roof Bow Bus Outer Skin Mounting Channel 1/4 In. Flat Washer
    1/4-20 ESNA1/4 In. Spacer
    Bolt,1/4-20X1In.
    Condenser Frame Mounting FootMounting Foot 1/4 In. Flat Washer
    1/4-20 ESNA1/4 In. Spacer
    1/4 In. Spacer
    Bolt,1/4-20X1In.Bolt, 3/8-16 X 1-1/4 In.
    (Torque to 20 Ft. Lbs.)
    3/8 In. Lock Washer
    3/8 In. Flat Washer
    3/8 In. Lock Washer
    TOPVIEW
    (Angle may have to be adjusted)
    Figure 3-8 Installing Mounting Feet & Mounting Channels
    d. Install the two mounting channels to the mounting
    feet with the enclosed hardware.
    Note
    Do not tighten the mounting hardware at this
    time. You may have to make adjustments to the
    mounting feet and rails later.e. Carefully place the condenser at the predetermined
    location on the bus roof. Center the condenser side-
    to-side on the bus roof.
    f. Trace around both mounting channels.
    g. Mark where the feed-thru-plate will be located. This is
    where the discharge and liquid line will be connected.
    Refer to the enclosed installation drawing or see
    Figure 3-9.
    Liquid line (#8 hose) - to evaporatorOptional configuration of remote
    mounted filter drier-sightglassFeed-Thru-Plate
    1/2 in.O-Ring
    (4 places)
    Filter Drier/Sightglass
    W/Moisture Indicator
    1/2 in.O-Ring
    (2 places)Drill 13/64 Dia. holes. Use 3/16 In.
    rivets thru outer skin, (8 places).
    Apply sealant to plate & rivet heads
    to prevent water leaks.
    BUS ROOF
    Figure 3-9 Attaching To Feed-Thru-Plate & Remote Filter Drier 
    						
    							T--311
    3-7 h. Remove mounting channels from condenser mount-
    ing feet.
    i. Drill 13/64 In. Dia. holes thru the bus roof outer skin
    and roof bows using the mounting channel holes as a
    guide. See Figure 3-10.Note
    It is recommended that a drill stop be used
    when drilling through the bus roof.
    j. Apply sealant around all the holes and the mounting
    channels. Place the channels on the bus roof.
    Position mounting channel so it
    spans across a minimum of two
    roof bows.
    Drill a 13/64 dia. hole. Use 3/16 in.
    steel rivets located thru each roof bow
    a minimum of 8 places Drill a 13/64 Dia. holes. Use 3/16 In.
    rivets thru outer skin. Minimum of 20
    places
    Figure 3-10 Attaching Mounting Channels To Bus Roof
    k. Using 3/16 In. Dia. steel rivets, attach the mounting
    channels to the bus roof.
    l. Where previously marked carefully cut a 3 X 4 Inch
    hole thru the bus roof and ceiling. This is where the
    feed-thru-plate will be attached.
    m.Place the feed-thru-plate over the cut-out. Modifica-
    tions may be needed in order for the plate to fit proper-
    ly.
    n. Drill 13/64 In.Dia. holes in the bus roof using the holes
    in the feed-thru-plate as a guide. Use all 8 holes.
    o. Apply sealant around all the holes and the plate.
    p. Using 3/16 In. Dia. steel rivets, attach the feed-thru-
    plate to the bus roof.
    q. Seal around the feed-thru-plate and the mounting
    channels. Apply sealant to all the rivet heads to pre-
    vent water leaks.Note
    The mounting foot angle may have to be ad-
    justed in order that it sits flat on the mounting
    channels. See Figure 3-8.
    r. Place the condenser back on to the mounting chan-
    nels. The center of the condenser must be close to
    the bus roof but not touching it. Adjust the mounting
    legs up or down for the correct height. Refer to the
    installation instructions enclosed or see Figure 3-11.
    Note
    Remember to lubricate all fittings, O-Rings, and
    refrigerant hose with mineral oil before attach-
    ing components. All refrigerant O-Ring fittings
    must be torqued to 30 ft. lbs.
    s. Connect the condenser discharge and liquid lines to
    the feed-thru-plate fittings.
    t. Securely mount (clamp) the filter drier/sightglass as-
    sembly to the ceiling at the rear of the evaporator as-
    sembly.
    1In.
    Drill 0.28 Hole (8 Pls)
    NOTE: Use Mounting Leg as a Template.50 In.
    Adjust Leg to Correct Height - Then Install Hardware
    Figure 3-11 Adjusting Mounting Foot Height 
    						
    All Carrier manuals Comments (0)

    Related Manuals for Carrier Em1 Manual