Password: place a Number Input component, t he Address is Lw9502, Word Length is 2 ,Data Type is Password. Confirm password: place a Number Input component, the Address is Lw9510, Word Length is 2 ,Data Type is Password.
Logoff Time: place a Number Input component, the Address is Lw9508, Word Length is 2 ,Data Type is Unsigned Int : Set the user permission : Place four Bit State Switch , their Address is LW9506.0, LW9506.1, LW9506.2, LW9506.3. Switch Type is Toggle.
Add: Place a Bit State Switch component, t he Address is LB9167., Switch Type is On,. This component is user to add user permission. The simulation effect is as the following picture:
Click the Add user. , it will pop up a dialog box like that: Input user name that need to add, set the password and confirm the password, then set the permission of the user. After the above setting , click Add, so the user is added.
2 Delete the user permission: The Delete window contains User, Password, Confirm password, Delete. Settings of User, Password, Confirm password in Delete window are the same as the User setting window. Delete: Place a Bit State Switch component, t he Address is LB9168., Switch Type is On,. This component is used to delete user permission. Note Delete user permission is only effective to the users that added via HMI. The users set in the conf iguration project can not be delete d The following picture is the ef fect of offline simulation: Click the Delete, pop up a dialog box named Delete user
Input the user name ,password and confirm the password, then click the Delete, then the user is deleted. 12 Clear/export the compiling message
In the Message Window, you can clear or export the compiling message. Click the right left mouse button in the Mess age window, it will pop up two options: Clear Messages: Clear up all the compiling messages in the Message window. Export Messages: Export the compiling message to the folder where the current project loaded. The file name is log.txt 13 Event Information can trigger the Buzzer. In the Event Information, add a new function named Use Buzzer and Buzzing Time can be set. The unit is seconds.. Improvement of components 1 Meter Meter add the function of Using Scale to di splay, the upper and lower limit in Alarm can be labeled by color block, and Variable Lower / Upper Limit in Meter Component Extended Attribute (1) Meter
Basic Attribute ◆ Dial Style: Choose the dial style of Meter Hand Style: Choose the hand style of Meter Hand Color: Chose the hand color of Meter Point Length: Change the point length of Meter. T he utmost length is the radius of the Meter’s actual cycle
◆Scale attribute Use Scale : Select to display the scale of Meter Scale Color : Chose the scale color of Meter The Number of Main Scale : Change the number of main scale. The range is from 0 to 50 The Length of Main Scale :Change the length of main scale. The utmost length is the radius of the Meter’s actual cycle The Number of Minor Scale : Change the number if minor scale The Length of Minor Scale; Change the length of minor scale. The utmost length is the radius of the Meter’s actual cycle Show Scale Frame: Select to show scale frame Scale tag Use Scale Tag: Select to display the scale tag Tag Font: Click the Tag Font to se t the font of Scale Tag Integer: Integer of scale tag.(Can not be set , but it can be adjusted by the Maximum of the Meter automatically) Decimal : Change the decimal of scale tag. (Ranges from 0 to 8) Attribute of Dial Axis ◆ Use Dial Axis: Select to change the size and color of the Dial Axis. Axis Width: Change the size of the dial axis. The utmost width is the radius of the
Meter’s actual cycle Axis Color: Change the color of dial axis. 2 Meter Component Extended Attribute Maximum and Minimum: ◆ Minimum: Set the scale’s minimum of Meter Maximum: Set the scale’s Maximum of Meter ◆Variable Min/Max Variable Min/Max: If checked ,means that the scale’s minimum and maximum will use variable in Addr.Type : Address type of the variable register, it is a word register Address: The first address of variable register Word Length : Word length of variable register, the default is 2. Suppose the variable register Address of Minimum and Maximum used is Lw1, That is to say LW1 is the variable that Minimum used, LW2 is the variable that Maximum used. ◆Alarm Alarm: If checked, it means the Meter uses color block to label Upper/Lower Limit alarm. Upper Limit Color: Set block color of upper limit area of the Meter. Lowe Limit Color: Set block color of lower limit area of the Meter Normal Color: Set block color of normal lower limit area of the Meter. Fan Thickness: Set the thickness of ring like color bl ock, the utmost is the radius of the Meter’s actual cycle and it must be le ss or equal to the Fan External Radius. Fan External Radius: Set radius of the ring like color block. The utmost is the radius of the Meter’s actual cycle and it must be bigger or equal to the Fan Thickness.