    Have a look at the manual Anaheim HMIPLC Release note for Version 16 all20110601 Users Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 523 Anaheim manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							
     
    Only show the event which doesn’t recover: if checked, so Only show the event 
    which doesn’t recover, If a event  recovers, it will not be displayed in the Event Display list. 
    If uncheck  Only show the event which doesn’t recover,  so the events that were 
    triggered and have recovered are still displayed in the Event Display list, unless clear the 
    Event Display list. 
    13 Min Time Interval 
    In each setting components ,add a option of  Min Time Interval(seconds), it is the 
    effective interval of touching a same component. 
    As shown in the picture,  the default is zero second: 
     
     
    14 Add a Video Mode NTSC  
    						
    							
        Add a Video Mode NTSC to HMI that support video interface. Industrial camera 
    that support NTSC mode can use this m ode., and now our HMI support two video mode: 
    PAL and NTSC. 
     
    15 Vector Fonts Edge Blur; 
      Use the  Vector Fonts Edge Blur  can make the words look smooth, beautiful and 
    without toothed shape along  the edge, but the computation  of HMI will increase if check 
    the  Vector Fonts Edge Blur  function, and it will be slow  when HMI refreshing, so if  
    users who don’t    care much about the effect about the vector fonts, and want the HMI to 
    refresh quickly , uncheck this f unction, because the default is to select this function. 
    This function can’t support t he component of Event Informat ion, Event Display, Alarm 
    Display, Alarm list, History Event Display, Oper ation Log, the reason is that: this function 
    can not support the component t hat display word of various color at same time. 
    Settings of Vector Fonts Edge Blur 
    In the page of  HMI Extended Attributes,  select the Vector Fonts Edge Blur   
    						
    							
     
    The following two pictures are the effect contrast between select the Vector Fonts 
    Edge Blur  and unchecked.. 
    1 Uncheck the Vector Fonts Edge Blur  
      
    2 Select the Vector Fonts Edge Blur   
    						
    							
     
    It is very obvious that it is more smooth and beautiful and there is no teethed shape 
    along the edge of word if select the  Vector Fonts Edge Blur 
    16 Invalided component color 
    The use of Invalided component color:  if the enable condition of a component can 
    not be met or be invalid, HMI can set a sign of In valid for it , it means that the component 
    is invalid, and the touch is invalid. If the en able condition of this component is met, the 
    sign will disappear automatically,  so the component can be used. Only control 
    components , like  Switch, Multiple State Setting  etc can use this function , the    display 
    components  , like  Indicator, Multiple State Display  etc can not use this function 
    Example for the usage of  Invalided component color 
    If value of VW0 is 0 , the Bit State Sw itch M0 can be operated or it can not be 
    operated, and display the sign of invalid
     
      1 Set the color of invalid comp onent: double click the HMI, chose the  HMI 
    Extended Attributes  page, select the color of invalid component as red.  
    						
    							
     
    2 Set a Bit State Switch M0, chose the Conditional Enabling in Control Setting  of 
    Bit state Setting Component Attribute , chose the Word control  = =0 in the Register 
    Control , then chose the  Show Elements Invalid Tag .  
    						
    							
     
    3 Set a Number Input component VW0 
    4 Offline Simulation , if VW=0 ,M0 can be operated, if VW0=50 , M0 can not be 
    operated , and show the invalid tag.. 
     
      
    						
    							
     
    17 When security level is 0.there is no password    
    						
    							
     
    18 Customize the printing in PLC Control component   
    There are two types of printing in PLC Control: Screen Hard Copy and Report 
    Printout 
    1 Screen Hard Copy 
    A bit component is used to control the Screen Hard Copy, when the component’s 
    state switch ON , the current screen is printed out.  
    						
    							
     
    As shown in the above picture, use LB0 to control Screen Hard Copy, if LB0 switch 
    is ON, the content in the window wh ere the LB0 is set is printed out. 
    There are two ways to set the output mode of printing content: 
      1 , Use the Custom Print Options   
    						
    							
     
    Explain for the attributes of Custom Print Options: 
    Custom Print Options Detail descriptions 
    MonochromePrint Color Color 
    Only color printer supports the  Print 
    Color  chose 
    MagnificationRange from 0.1 to 5.0 (Reduce the printing distortion, not 
    recommended ) 
    Current PagePrint the content to the first paper in 
    printer Print Page 
    Change Page 
    To Print When the printer receive the print 
    command ,it print a blank paper, then print 
    the content to the second paper    
    						