21 • Centrotherm InnoFlue vent system AL29-4C Stainless Steel - See page 29 • HeatFab Saf-T Vent • Duravent FasNSeal NOTE: The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in non-metallic venting systems is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. CATEGORY IV APPLIANCE Category IV appliances operate with a positive vent (exhaust) static pressure and with vent gas...
Page 22
22 Six Inch Pipe The water heaters covered in this manual are certified to a maximum length of 6 inch pipe for the exhaust venting arrangement of 120 equivalent feet (36.5 m). The certified maximum length of 6 inch pipe for intake air piping is also 120 equivalent feet (36.5 m). IE: On Direct Vent installations both pipes can be up to 120 equivalent feet (36.5 m). INTAKE AIR AND VENT PIPE CLEARANCES The minimum clearance from combustible materials for...
Page 23
23 9. All vent (exhaust) pipes must be pitched a minimum of a 1/4 inch per foot back to the water heater (to allow drainage of condensate). 10. If installing 4 inch vent pipe connect the vent pipe to the exhaust elbow on the water heater. 11. If installing 6 inch pipe transition to 4 inch pipe as shown in Figure 15. The field installed 4” pipe between the exhaust elbow and the 6” x 4” reducer coupling should be 18 inches (45 cm) or less in length. DIRECT...
Page 24
24 14. If installing 4 inch intake air pipe connect the intake air pipe to the intake air connection on the water heater. 15. If installing 6” intake air pipe transition to 4” pipe at the intake air connection on the water heater as shown in Figure 18. The field installed 4” pipe between the intake air connection and the 6” x 4” reducer coupling should be 18 inches (45 cm) or less in length. 3” PIPE F ACTORY INST ALLED 6” PIPE FIELD SUPPLIED 4” PIPE FIELD SUPPLIED 6” x 4” REDUCER FIELD...
Page 25
25 INTAKE AIR AND/OR VENT TERMINA TION(S) MUST BE A MINIMUM OF 24 INCES (60 cm) ABOVE ANY PARAPET, VERTICAL WA LL OR STRUCTURE WITHIN 10 FEET (3 m) HORIZONT ALLY. VERTICAL TERMINATION(S) FLA T ROOF CLEARANCEINTAKE AIR AND/OR VENT (EXHAUST) 24 INCHES (60 cm) MINIMUM HEIGHT ABOVE IF LESS THAN 10 FEET (3 m) Figure 20 11. Return to Power Vent Installation on page 23 or Direct Vent Installation on page 23 to complete the installation of the intake air and/or vent piping between the...
Page 26
26 SIDEWALL TERMINATION INSTALLATION 1. Determine the location for the termination(s). 2. If installing only vent (exhaust) piping in a Power Vent configuration through a sidewall; ensure that all exterior sidewall clearance requirements for the termination, shown in Figure 45a on page 36, are being maintained. These clearances and those cited by local and national codes must be maintained. 3. If installing both intake air and vent piping in a Direct Vent...
Page 27
27 Installations must comply with applicable national, state, and local codes. For Canadian installation, Polypropylene vent must be listed as a ULC-S636 approved system. If Polypropylene vent is not required by your local code, you may use either PVC or CPVC pipes for your water heater that allows non-metallic venting material installations. Polypropylene vent systems do not use cement to connect the pipe and elbow sections but use a push together gasket seal method. Do not...
Page 28
28 AL29-4C® VENT INSTALLATIONS (AL29-4C® is a registered trademark of Allegheny Technologies, Inc.) The water heaters covered by this manual are approved to be installed with AL29-4C® stainless steel vent material using parts from the manufacturers listed in Table 10 and Table 11 below. These listed systems must be installed using the vent manufacturer’s instructions including their listed clearances to combustible and noncombustible materials. Refer to Table 7-PVC/CPVC...
Page 29
29 termination caps for all concentric terminations must be at the same height measured from ground. See Multiple Concentric Termination Arrangements on page 31. 9. Determine if the concentric termination will need to be shortened to accommadate required clearances or to ensure all vent caps are at the same height when installing multiple terminations vertically through the roof in the same location. See Figure 25 for the minimum lengths allowed for the 6...
Page 30
30 6 INCH CONCENTRIC TERMINATION INSTALLATION 6 INCH CONCENTRIC TERMINATION KITFIELD ASSEMBL Y REQUIRED VENT PIPE INT AKE AIR CONNECTION VENT CONNECTION - 4 INCH PVC INTAKE AIR PIPE Y FITTING ASSEMBLY VENT CAP VENT PIPE ASSEMBL Y VENT PIPE IS 4 INCH SDR-26 PIPE SUPPLIED LENGTH 46.50” (1 18 cm) MINIMUM ALLOWABLE LENGTH 16.38” (41.6 cm) INT AKE AIR PIPE IS 6 INCH SDR-26 PIPE SUPPLIED LENGTH 25.38” (64.5 cm ) MINIMUM ALLOWABLE LENGTH 12” (30 cm )VENT CAP INT AKE AIR PIPE 6” x 6” x 6” Y FITTIN...