Page 51
51 SERVICE CONTACT INFORMATION The control system has a discrete menu that Installing contractors and/or service agents can access to enter contact information for their customers. This contact information will be displayed with all Fault and Alert messages. DESCRIPTION/ACTIONDISPLAY From the Desktop Screen (see Figure 52 on page 44) press and hold down the middle (unmarked) Operational Button for 30 seconds and then release it. This will launch a discrete menu where personalized...
Page 52
52 PRIOR TO START UP Installation and start up of this water heater requires abilities and skills equivalent to that of a licensed tradesman in the field involved, see Qualifications on page 6. Do not place the water heater in operation if any part has been under water. Immediately call a qualified service technician to inspect the water heater and to replace any part of the control system and any gas control which has been under water. Light the...
Page 53
53 LIGHTING & OPERATION LABEL The instruction label below is affixed to the water heater's covered by this manual at the factory and must be followed when lighting and operating the water heater. E L B A M M A L F . 1 . 1 . 3 ! P O T S e v o b a n o i t a m r o f n i y t e f a s e h t d a e R . l e b a l s i h t n o 2 . Set the Enable/Disable switch on the control panel to the Enable position. 4. Set the Enable/Disable switch on the control panel to the Disable position. 8....
Page 54
54 Gas Line Installation on page 39 and Supply Gas Regulator on page 13. Ensure all requirements and installation instructions are maintained. CHECKING THE FIRING RATE If firing rate adjustment is required follow these instructions to determine the actual firing rate of the water heater: NOTE: The heaters covered by this manual are capable of modulating their firing rate. The firing rate should be checked with the heater operating at it's full firing rate. 1. Ensure...
Page 55
55 HIGH ALTITUDE INSTALLATIONS Fire and Explosion Hazard Gas and carbon monoxide detectors ar e available. Overfiring could result in fire or explosion. Under no circumstances should the input exceed the rate shown on the water heater ’s rating label. Breathing Hazard - Carbon Monoxide Ga s Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Under no circumstances should the input exceed the rate shown on the water heater ’s rating label....
Page 56
56 SEQUENCE OF OPERATION Read the Sequence of Operation below before attempting to correct any operational problems. Refer to the Features And Components section beginning on page 7 for the location of various water heater components described below. See the Sequence Of Operation Flow Chart on page 57 also. 1. When the control system is first powered, during boot up, it will display water heater model information during initialization. After a few moments...
Page 57
57 SEQUENCE OF OPERATION FLOW CHART YESNO Water is h eat ed to se t poin t24 VAC Ga s Va lve de -energi zed Inter-Pu rge cycl e24 VAC Ga s Va lve de- energ ized Re trie s up to tw o mo re time sPost-P urge cycl e Cont rol S yst em Loc ks Out “I gni tion Failure” Fa ult Ms g is di sp laye d Wa ter heat er goes in to sta ndby mode If ta nk te mp erat ure drop s bel ow Oper ating Se t Po int mi nus Di fferen tial se tting a heati ng cycle is ac tiva ted Bl ow er Prov er sw itch co...
Page 58
58 requirements (erratic gas supply volume/pressures) - see Supply Gas Regulator on page 13. • Excessive supply gas pressure - see Table 4 on page 10 and Supply Gas Pressure Adjustment on page 54. • Vent (exhaust) gas recirculation at the vent and intake air pipe terminations on Direct Vent installations - see Direct Vent Installation on page 23. • Excessive equivalent lengths of intake air and/or vent (exhaust) piping installed - see Venting Requirements on page 22. • Debris clogging/blocking...
Page 59
59 ALERT CONDITIONS When the control system declares an Alert condition it will display an Alert message on the control system's LCD with a question "?" mark. The water heater will continue to operate during an Alert condition but the water heater must be serviced by a qualified service agent as soon as possible. RESETTING CONTROL SYSTEM LOCK OUTS To reset the control system from a lock out condition; turn the electrical power supply off for approximately 20...
Page 60
60 FAULT AND ALERT MESSAGES Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service agent in your area. POSSIBLE CAUSES - CHECK/REPAIRDISPLAYED FAULT/ALERT MESSAGE • Using a manometer, ensure that gas supply pressure is above minimum requirement listed on heater’s data plate and does not drop more than 1.5” W.C. when unit fires. • Ensure wire connections to gas valve are clean and tight. • Ensure wire connections to flame...