Home
>
American Water Heater
>
Gas Heater
>
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
Here you can view all the pages of manual American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual. The American Water Heater manuals for Gas Heater are available online for free. You can easily download all the documents as PDF.
Page 11
11 LOCATING THE WATER HEATER Carefully choose a location for the new water heater. The placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the water heater. Property Damage Hazard All water heaters eventually leak.Do not install without adequate drainage. CAUTION Whether replacing an existing water heater or installing the water heater in a new location observe the following critical points: 1. The water heater must be...
Page 12
12 INSULATION BLANKETS Do not obstruct water heater air intake with insulating blanket. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Breathing Hazard - Carbon Monoxide Ga s Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose...
Page 13
13 If a positive lock-up regulator is required follow these instructions: 1. Positive lock-up gas pressure regulators must be rated at or above the input Btu/hr rating of the water heater they supply. 2. Supply gas regulators shall have inlet and outlet connections not less than the minimum supply gas line size for the water heater they supply. See Table 13, page 39. 3. Positive lock-up gas pressure regulator(s) should be installed no closer than 3 feet (1 meter) and no farther than 8 feet (2.4...
Page 14
14 HOT WATER OUTLET TO TA NK INLET CHECK VA LVE MIXING VA LVE COLD WA TER INLET TEMPERED WA TER OUTLET 12” TO 15” (30-38 cm) CHECK VA LVE Figure 8 The National Sanitation Foundation also recommends circulation of 180°F (82°C) water. The circulation should be just enough to provide 180°F (82°C) water at the point of take-off to the dishwashing machine. Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump....
Page 15
15 Water Damage Hazard Temperature-Pressure Relief V alve discharge pipe must terminate at adequate drain. CAUTION T&P Valve Discharge Pipe Requirements: • Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. • Shall not be plugged or blocked. • Shall not be exposed to freezing temperatures. • Shall be of material listed for hot water distribution. • Shall be installed so as to allow complete drainage of both the...
Page 16
16 CONDENSATE DRAIN The water heaters covered in this manual are condensing appliances and require a building drain to be located in close proximity to allow the condensate to drain safely. Condensate drains from the water heater at the exhaust/ condensate elbow located at the bottom. The field installed condensate drain line must not be elevated above the condensate drain connection on the exhaust/condensate elbow, see Figure 9. If the condensate does not...
Page 17
17 UNUSUALLY TIGHT CONSTRUCTION In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of unusually tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.) additional air must be provided using the methods described in the Confined Space section that follows. CONFINED SPACE A Confined Space is one whose volume IS...
Page 18
18 Alternatively a single permanent opening, commencing within 12 inches (300 mm) of the top of the enclosure, shall be provided. See Figure 11. The water heater shall have clearances of at least 1 inch (25 mm) from the sides and back and 6 inches (l50 mm) from the front of the water heater. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the...
Page 19
19 AIR FROM OTHER INDOOR SPACES Figure 14 The confined space shall be provided with two permanent openings, one commencing within 12 inches (300 mm) of the top and one commencing within 12 inches (300 mm) of the bottom of the enclosure. See Figure 14. Each opening shall communicate directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an Unconfined Space. Each opening shall have a minimum free area...
Page 20
20 COMMONWEALTH OF MASSACHUSETTS For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to...