Home
>
American Water Heater
>
Gas Heater
>
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
Have a look at the manual American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
21 • Centrotherm InnoFlue vent system AL29-4C Stainless Steel - See page 29 • HeatFab Saf-T Vent • Duravent FasNSeal NOTE: The use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in non-metallic venting systems is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited. CATEGORY IV APPLIANCE Category IV appliances operate with a positive vent (exhaust) static pressure and with vent gas temperatures low enough to produce condensate in the vent piping. POWER VENT CONFIGURATION Power Vent configurations derive all combustion air from the room where they are installed and discharge all flue gases to the outdoor atmosphere through a sealed vent (exhaust) pipe. Power vent configurations have one vent pipe connected to the water heater which can be terminated in a vertical or horizontal arrangement. See Figure 36 and Figure 37 on page 34. DIRECT VENT CONFIGURATION Direct Vent configurations derive all combustion air directly from the outdoor atmosphere through a sealed intake air pipe and discharge all flue gases to the outdoor atmosphere through a sealed vent (exhaust) pipe. Direct Vent configurations have two pipes connected to the water heater, one vent pipe and one intake air pipe. Direct Vent configurations can be terminated in one of seven different arrangements. See Figure 38 on page 34 through Figure 44 on page 35. GENERAL VENTING INSTRUCTIONS These instructions must be followed on all installations. 1. DO NOT install the water heater in a Power Vent configuration unless there is adequate supply of fresh air, see Air Requirements on page 17. If the installation space does not provide an adequate supply of fresh air the water heater must be installed in a Direct Vent configuration. 2. If the water heater is to be installed in a beauty shop, barber shop, cleaning establishment, a laundry with dry cleaning equipment or any space with contaminated air it is imperative that the water heater(s) be installed in a Direct Vent configuration so that all air for combustion is derived from the outdoor atmosphere. 3. The vent and intake air piping must terminate outdoors. 4. The minimum clearance from combustible materials for the vent (exhaust) and intake air piping shall be 0 inches. Vent piping passing through a combustible wall or ceiling must be a continuous run (no joints). 5. The water heater must be protected from freezing downdrafts during shutdown periods. 6. The vent (exhaust) pipe must not be combined or connected to any other appliance’s vent system or chimney. 7. The intake air pipe must not be combined or connected to any other appliance’s intake air piping. 8. Locate the water heater where the vent (exhaust) and intake air piping will remain within the maximum equivalent lengths allowed. See Venting Requirements on page 22. 9. Do not install the vent or intake air piping in a manner that will allow water to be trapped in the piping. 10. Vent pipes must be pitched a minimum of a 1/4 inch per foot back to the water heater (to allow drainage of condensate). 11. Do not anchor the vent or intake air pipe directly to framed walls, floors or ceilings unless rubber isolation pipe hangers are used to prevent vibration noise from being transmitted. 12. Use only approved vent/intake air pipe sizes and materials. See Venting Requirements on page 22. VENTING INSTALLATION Breathing carbon monoxide can cause brain damage or death. Always read and understand the instruction manual . Install vent system in accordance with codes. Do not operate water heater if exposed to flooding or water damage Special consideration must be taken with installations above 10,000 feet (3,048 m) refer to high altitude section of this manual. Breathing Hazard - Carbon Monoxide Ga s Do not operate if soot buildup.Do not obstruct water heater air intake with insulating jacket or blanket. Do not place chemical vapor emitting products near water heater. Gas and carbon monoxide detectors are available.Never operate the heater unless it is vented to th e outdoors and has adequate air supply to avoid risks of improper operation, fire, explosion or asphyxiation . Analyze the entire vent system to make sure that condensate will not become trapped in a section of vent pipe and therefore reduce the open cross sectional area of the vent. Never operate water heater unless it is vented to the outdoors. Instructions in this section of the manual must be followed to avoid choked combustion or recirculation of flue gases. Such conditions cause sooting of the combustion chamber, burners and flue tubes and creates a risk of asphyxiation. GENERAL VENTING INFORMATION The water heaters covered in this manual are operationally equivalent to Category IV appliances and may be installed in either a Power Vent or Direct Vent configuration. APPROVED MATERIALS Approved vent and intake air pipe materials that may be used in the United States: PVC pipe materials: • DWV ASTM-D2665 or CSA B181.2 • Schedule 40, 80, 120 ASTM-D1785 or CSA B137.3 • SDR Series ASTM-D2241 or CSA B137.3 CPVC pipe materials: • CPVC 41 ASTM-D2846 or CSA B137.6 • Schedule 40, 80 ASTM-F441 or CSA B137.6 • SDR Series ASTM-F442 Polypropylene - See page 28 • M & G Duravent Polypro vent system • Centrotherm InnoFlue vent system AL29-4C Stainless Steel - See page 29 • HeatFab Saf-T Vent • Duravent FasNSeal Approved vent pipe materials that must be used in Canada: • ULC S636 PVC / CPVC • ULC S636 Polypropylene - See Page 27. • AL29-4C Stainless Steel - See Page 28. Intake air pipe materials that may be used in Canada: PVC pipe materials: • DWV ASTM-D2665 or CSA B181.2 • Schedule 40, 80, 120 ASTM-D1785 or CSA B137.3 • SDR Series ASTM-D2241 or CSA B137.3 CPVC pipe materials: • CPVC 41 ASTM-D2846 or CSA B137.6 • Schedule 40, 80 ASTM-F441 or CSA B137.6 • SDR Series ASTM-F442 Polypropylene - See page 28 • M & G Duravent Polypro vent system
22 Six Inch Pipe The water heaters covered in this manual are certified to a maximum length of 6 inch pipe for the exhaust venting arrangement of 120 equivalent feet (36.5 m). The certified maximum length of 6 inch pipe for intake air piping is also 120 equivalent feet (36.5 m). IE: On Direct Vent installations both pipes can be up to 120 equivalent feet (36.5 m). INTAKE AIR AND VENT PIPE CLEARANCES The minimum clearance from combustible materials for the vent (exhaust) and intake air piping shall be 0 inches. Vent or intake air piping passing through a combustible wall or ceiling must be a continuous run (no joints). MINIMUM EQUIVALENT LENGTHS Four Inch Pipe The water heaters covered in this manual are certified to a minimum length of 4 inch pipe for the vent (exhaust) of 15 equivalent feet (4.6 m). There is no minimum equivalent feet requirement for the intake air pipe. Six Inch Pipe The water heaters covered in this manual are certified to a minimum length of 6 inch pipe for the vent (exhaust) of 70 equivalent feet (21.3 m). There is no minimum equivalent feet requirement for the intake air pipe. MAXIMUM NUMBER OF ELBOWS The vent pipe may have a maximum of six 90° elbows installed. The intake air pipe may have a maximum of six 90° elbows installed. IE: in a Direct Vent configuration each pipe can have up to six (6) 90° elbows installed. Two (2) 45° elbows equal one (1) 90° elbow. Each 90° elbow is equivalent to 5 feet (1.5 m) of linear pipe, 45° elbows are equivalent to 2.5 feet (0.75 m) of linear pipe. Note: Refer to Table 10 and Table 11 for equivalent linear pipe length of AL29-4C ® 45° and 90° elbows. FACTORY SUPPLIED FITTINGS The water heater ships with two (2) factory supplied 4 inch terminations (PVC 45° elbows with debris screen). Factory supplied vent and intake air terminations or concentric and low profile terminations must be used. Factory supplied terminations and installed fittings (exhaust elbow and intake air connection) add zero equivalent feet to the vent and intake air piping. NOTE: 3 inch vent and/or intake pipe as well as 3 inch terminations previously used on older (A)HCG3 119T 300/400 models must be replaced with 4 inch or 6 inch pipe and 4 inch or 6 inch terminations depending on installed length. TABLE 7-PVC/CPVC and Polypropylene Number of 90° Elbows Installed 4 Inch Pipe 6 Inch Pipe Maximum Feet (Meters) Maximum Feet (Meters) One (1) 65 feet (19.8 meters) 115 feet (35.0 meters) Two (2) 60 feet (18.2 meters) 110 feet (33.5 meters) Three (3) 55 feet (16.8 meters) 105 feet (32.0 meters) Four (4) 50 feet (15.2 meters) 100 feet (30.5 meters) Five (5) 45 feet (13.7 meters) 95 feet (29.0 meters) Six (6) 40 feet (12.2 meters) 90 feet (27.4 meters) 6 INCH EXTENDED VENT TERMINATIONS When 6 inch intake air or vent pipe is installed using standard terminations, factory supplied 6 inch terminations must be used. Contact your local distributor or call the parts department (phone number listed on the back cover of this manual) to order 6 inch termination(s). See Optional Direct Vent Terminations on page 12. 13. Use only factory supplied vent and intake air, concentric or low profile terminations. See Venting Requirements on page 22. 14. Do not locate the vent (exhaust) or intake air terminations where they would be objectionable due to noise at the termination(s). This includes locations close to or across from windows and doors. 15. Direct venting into dead air spaces such as alleys, atriums, and inside corners can cause recirculation of flue gases. Recirculation of flue gases will cause sooting, premature failure of the heat exchanger and icing of the combustion air intake during severe cold weather. To prevent the recirculation of flue gases, maintain as much distance as possible between the intake air and vent terminations. 16. Do not locate the vent termination over a public area where condensate or vapor can cause a nuisance or ice hazard. 17. Ensure the screens in the factory supplied terminations are securely installed to prevent blockage in the vent system. 18. Stress levels in pipe/fittings can be significantly increased by improper installation. If rigid pipe clamps are used to hold the pipe in place, or if the pipe cannot move freely through a wall penetration, the pipe may be stressed, or high thermal stresses may be formed when the pipe heats up and expands. Install accordingly to minimize such stresses. 19. Carefully read Venting Requirements on page 22 and then proceed to the Venting Installation Sequence on page 23. VENTING REQUIREMENTS FIELD SUPPLIED FITTINGS Field supplied fittings should be equivalent to the piping material being installed. Field installed/supplied fittings will add equivalent feet to the vent or intake air piping as indicated below. All field supplied/installed fittings and piping must be factored into the equivalent feet calculations. • 90° elbows (short or long radius) are equivalent to 5 linear feet (152 cm) of pipe. • 45° elbows (short or long radius) are equivalent to 2.5 linear feet (76 cm) of pipe. Note: Refer to Table 10 and Table 11 for equivalent linear pipe length of AL29-4C ® 45° and 90° elbows. PRIMER AND CEMENT Tetrahydrofuran (THF) primer should be used to prepare the surfaces of pipe and fittings for solvent welding. If CPVC pipe and fittings are used, then the proper cement must be used for all joints, including joining the pipe to the factory provided terminations (PVC material). PVC Materials should use ASTM D-2564 Grade Cement; CPVC Materials should use ASTM F-493 Grade Cement. PIPE SIZE REQUIREMENTS The water heaters covered in this manual are certified for the use of 4 and 6 inch pipe for the vent (exhaust) and intake air piping. If the installed equivalent length for the intake air or vent piping will be 70 feet (21.3 m) or less, 4 inch pipe must be used. If the installed equivalent length will be more than 70 feet (21.3 m), 6 inch pipe must be used. NOTE: Install the pipe size required for the installed equivalent length of each pipe independently. IE: If the intake air pipe will be 70 equivalent feet or less and the vent pipe will be more than 70 equivalent feet; the intake air pipe must be installed using 4 inch pipe and the vent must be installed using 6 inch pipe. MAXIMUM EQUIVALENT LENGTHS Four Inch Pipe The water heaters covered in this manual are certified to a maximum length of 4 inch pipe for the exhaust venting arrangement of 70 equivalent feet (21.3 m). The certified maximum length of 4 inch pipe for intake air piping is also 70 equivalent feet (21.3 m). IE: On Direct Vent installations both pipes can be up to 70 equivalent feet (21.3 m).
23 9. All vent (exhaust) pipes must be pitched a minimum of a 1/4 inch per foot back to the water heater (to allow drainage of condensate). 10. If installing 4 inch vent pipe connect the vent pipe to the exhaust elbow on the water heater. 11. If installing 6 inch pipe transition to 4 inch pipe as shown in Figure 15. The field installed 4” pipe between the exhaust elbow and the 6” x 4” reducer coupling should be 18 inches (45 cm) or less in length. DIRECT VENT INSTALLATION 1. Read the General Venting Instructions on page 21 and Venting Requirements on page 22 before proceeding. These instructions and requirements must be followed in addition to the instructions below that are specific for Direct Vent configurations. 2. Determine which Direct Vent arrangement will be used for the installation. There are seven (7) Direct Vent arrangement options, see pages 34 and 35. 3. Determine vent and intake air pipe size to be used for the installation; see Venting Requirements on page 22. 4. Plan the layout of the vent and intake air piping backwards from the termination point outdoors to the water heater. Layout the vent and intake air piping to use a minimum of pipe and elbows. 5. Install the terminations first. If standard terminations are being used and the intake air or vent piping will terminate vertically, through a roof, see Vertical Termination Installation on page 24. If standard terminations are being used and the intake air or vent piping will terminate horizontally, through a sidewall, see Sidewall Termination Installation on page 26. If a concentric termination(s) will be used see Concentric Termination Installation on page 29. If a low-profile termination will be used see Low Profile Termination Table 12 on page 33. 6. When installation of the termination(s) is complete Install necessary piping and fittings to route the intake air and vent piping back to the water heater. 7. The intake air and vent piping must be supported properly to avoid bending or failure. The water heater manufacturer recommends that the vent and intake air piping be supported every 5 feet (152 cm) of vertical run and every 3 feet (91 cm) of horizontal run. 8. Do not install the vent or intake air piping in a manner that will allow water to be trapped in the piping. 9. A field supplied condensate Tee fitting and drain hose must be installed in the intake air piping near the water heater in colder climates with heavy snow accumulations and in areas that regularly experience high humidity. The drain hose must be routed to an adequate floor drain separate from any other condensate drains. See Figure 16 on page 24. NOTE: Snow being pulled into the intake air piping and then melting can lead to excessive amounts of water accumulation and damage water heater components. Warm, humid outdoor air can lead to excessive condensation inside the intake air piping and may also damage water heater components. 10. All vent (exhaust) pipes must be pitched a minimum of a 1/4 inch per foot back to the water heater (to allow drainage of condensate). 11. If installing 4 inch vent pipe connect the vent pipe to the exhaust elbow on the water heater. 12. If installing 6 inch vent pipe transition to 4 inch pipe at the exhaust elbow on the water heater as shown in Figure 15. The field installed 4” pipe between the exhaust elbow and the 6” x 4” reducer coupling should be 18 inches (45 cm) or less in length. The water heaters covered by this manual may be installed in a Direct Vent configuration using a 6 inch concentric or 6 inch low profile termination. Contact your local distributor or call the parts department phone number listed on the back cover of this manual to order. • 6” Concentric Termination Part # 9008841005 • 6" Low Profile Termination Part # 9008935005 VENTING INSTALLATION SEQUENCE 1. Read the General Venting Instructions on page 21 and Venting Requirements on page 22 before proceeding. These instructions and requirements must be followed on all installations. 2. Determine whether the water heater will be installed in a Power Vent or Direct Vent configuration and which vent system arrangement will be used for the installation. See the various venting arrangements on pages 34 and 35. 3. Proceed to the applicable installation instructions that follow; Power Vent Installation or Direct Vent Installation. POWER VENT INSTALLATION 1. Read the General Venting Instructions on page 21 and Venting Requirements on page 22 before proceeding. These instructions and requirements must be followed in addition to the instructions below that are specific for Power Vent configurations. 2. Determine which Power Vent arrangement will be used for the installation; vertical or horizontal termination. See Figure 36 and Figure 37 on page 34. 3. Determine the vent pipe size for the installation, see Venting Requirements on page 22. 4. Plan the layout of the vent piping backwards from the termination point outdoors to the water heater. Layout the vent piping to use a minimum of pipe and elbows. 5. Install the termination first. If the vent piping will terminate vertically, through a roof, see Vertical Termination Installation on page 24. If the vent piping will terminate horizontally, through a sidewall, see Sidewall Termination Installation on page 26. 4” PIPE FIELD SUPPLIED ALUMINUMEXHAUST/ CONDENSA TE ELBOW VENT CONNECTION FA CT OR Y INST ALLED 6” PIPE FIELD SUPPLIED 6” x 4” REDUCER FIELD SUPPLIED VENT (EXHAUST) CONNECTION Figure 15 6. When installation of the termination is complete install necessary piping and fittings to route the vent piping back to the water heater. 7. The vent pipe must be supported properly to avoid bending or failure. The water heater manufacturer recommends that the vent pipe be supported every 5 feet (152 cm) of vertical run and every 3 feet (91 cm) of horizontal run. 8. Do not install the vent piping in a manner that will allow water to be trapped in the piping.
24 14. If installing 4 inch intake air pipe connect the intake air pipe to the intake air connection on the water heater. 15. If installing 6” intake air pipe transition to 4” pipe at the intake air connection on the water heater as shown in Figure 18. The field installed 4” pipe between the intake air connection and the 6” x 4” reducer coupling should be 18 inches (45 cm) or less in length. 3” PIPE F ACTORY INST ALLED 6” PIPE FIELD SUPPLIED 4” PIPE FIELD SUPPLIED 6” x 4” REDUCER FIELD SUPPLIED 4” x 3” REDUCER FA CT OR Y INST ALLED INT AKE AIR CONNECTION INT AKE AIR CONNECTION INT AKE AIR COMBUSTION BLOWER Figure 18 VERTICAL TERMINATION INSTALLATION 1. Determine the location for the termination(s). 2. If installing only the vent (exhaust) piping in a Power Vent configuration vertically through the roof; ensure that all exterior vertical clearance requirements shown in Figure 19 and Figure 20 on page 25 are being maintained. These clearances and those cited by local and national codes must be maintained. NOTE: On flat roof installations the vent termination must be a minimum of 24 inches (60 cm) above any parapet, vertical wall or structure within 10 feet (3 m) horizontally. See Figure 20 on page 25. 3. If installing both intake air and vent piping in a Direct Vent configuration vertically through the roof; ensure that all exterior vertical clearance requirements shown in Figure 20 and Figure 21 on page 25 are being maintained. These clearances and those cited by local and national codes must be maintained. NOTE: On flat roof installations the intake air and the vent terminations must be a minimum of 24 inches (60 cm) above any parapet, vertical wall or structure within 10 feet (3 m) horizontally. See Figure 20 on page 25. 4. If installing only vent piping in a Power Vent configuration vertically through the roof the following instructions must be followed: The vent termination must be oriented facing downward as shown in Figure 19 and Figure 20 on page 25. The bottom edge of the vent termination must be a minimum of 12 inches (30 cm), 18 inches (45 cm) in Canada, above the average or expected snow level as shown in Figure 19 on page 25. 5. If installing both intake air and vent piping in a Direct Vent configuration vertically through the roof the following instructions must be followed: The intake air and vent pipes must penetrate the same side of the roof as shown in Figure 21 on page 25. The intake air and vent terminations must be oriented facing downward and in the same direction as shown in Figure 21 on page 25. The intake air and vent terminations must have a minimum INT AKE AIR CONDENSA TE TEE INST ALLATION INSTALL TEE FITTING AS CLOSE TO WA TER HEAT ER INTAKE AIR CONNECTION AS POSSIBLE FIELD SUPPLIED 4” x 4 ” x 1/2” TEE WITH HOSE BARB FITTING INST ALLEDFA CT OR Y INST ALLED INT AKE AIR CONNECTION (4” x 3” REDUCER) INT AKE AIR CONNECT FIELD SUPPLIED FLEXIBLE DRAIN HOSE TO BARB FITTING AND FORM A LOOP WATER TRAP IN DRAIN HOSE RUN DRAIN HOSE TO SUIT ABLE FLOOR DRAIN SEP ARATELY FROM OTHER CONDENSA TE DRAINS Figure 16 13. Ensure the Intake Air Screen on the Intake Air Connection is removed before connecting the intake air pipe to the water heater, see Figure 17. Do not obstruct water heater air intake. Gas and carbon monoxide detectors are available. Install water heater in accordance with the instruction manual. Breathing carbon monoxide can cause brain damage or death. Always read and understand instruction manual. Breathing Hazard - Carbon Monoxide Ga s NOTE: Do not leave the screen inside the Intake Air connection in Direct Vent installations. Once the intake air pipe is installed the screen will be hidden from view and may become clogged with debris over time. This will cause improper combustion. INTAKE AIR CONNECTION DET AIL 4” x 3” REDUCER COUPLING - F ACTORY INST ALLED INTAKE AIR SCREEN(remove for Direct V ent) Figure 17
25 INTAKE AIR AND/OR VENT TERMINA TION(S) MUST BE A MINIMUM OF 24 INCES (60 cm) ABOVE ANY PARAPET, VERTICAL WA LL OR STRUCTURE WITHIN 10 FEET (3 m) HORIZONT ALLY. VERTICAL TERMINATION(S) FLA T ROOF CLEARANCEINTAKE AIR AND/OR VENT (EXHAUST) 24 INCHES (60 cm) MINIMUM HEIGHT ABOVE IF LESS THAN 10 FEET (3 m) Figure 20 11. Return to Power Vent Installation on page 23 or Direct Vent Installation on page 23 to complete the installation of the intake air and/or vent piping between the termination(s) and the water heater. VERTICAL TERMINATION - DIRECT VEN TSTANDARD TERMINATIONS 24 INCHES (61 cm) MINIMUM 48 INCHES (122 cm) IN COLDER CLIMA TES FA CT OR Y SUPPLIED ST ANDARD TERMINATIONS POINTED DOWNW ARD FIELD SUPPLIED 90° ELBOW VENT (EXHAUST) TERMINA TION INT AKE AIR TERMINA TION FIELD SUPPLIED PLUMBING ROOF BOOTS OR FLASHINGS MAINTA IN 12” (30 cm) 18” (45 cm) FOR CANADA MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPA TED SNOW LEVEL. Figure 21 separation of 24” (61 cm) measured on center line as shown in Figure 21 on page 25. In colder climates this separation should be increased to at least 48 inches (122 cm). The bottom edge of the intake air and vent terminations must be a minimum of 12 inches (30 cm), 18 inches (45 cm) in Canada, above the average or expected snow level as shown in Figure 19 and Figure 21 on page 25. 6. When the intake air and/or vent piping from multiple water heaters will terminate in the same location the vent terminations can be grouped together in close proximity 0 inches/touching. Intake air terminations can also be grouped together in close proximity 0 inches/touching. The distance between the closest vent and intake air terminations must be a minimum of 24 inches (61 cm) as shown in Figure 21. In colder climates this separation should be increased to at least 48 inches (122 cm). 7. Cut a 5 inch (13 cm) diameter hole for 4 inch pipe or 7 inch (18 cm) diameter hole for 6 inch pipe where the pipe(s) will pass through the roof. NOTE: Beware of concealed wiring and piping when cutting through the roof. 8. Suspend the pipe(s) through center of hole using field supplied metal strapping or equivalent support materials as shown in Figure 19. 9. Slide a roof boot or equivalent flashing over the pipe and secure roof boot or equivalent flashing to roof (see Figure 19) and seal around the flashing. 10. Install the factory supplied intake air and/or vent termination(s) using field supplied pipe and one field supplied 90° elbow as shown in Figure 19. The short section of pipe that connects between the field supplied 90° elbow and the factory supplied termination must not be excessive in length. The exposed portion of this pipe shall be no more than 2 inches (5 cm), see Figure 19. 2” (5 cm) MAXIMUM FACT OR Y SUPPLIED ST ANDARD TERMINATION POINTED DOWN TOWA RDS THE GROUND VERTICAL TERMINATION(S) INST ALLATIONINTAKE AIR AND/OR VENT (EXHAUST) FIELD SUPPLIED 90° ELBOW FIELD SUPPLIED STRAP/SUPPOR T FIELD SUPPLIED PLUMBING ROOF BOOT OR FLASHING MAINTAIN 12” (30 cm) 18” (45 cm) FOR CANADA MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPAT ED SNOW LEVEL. Figure 19
26 SIDEWALL TERMINATION INSTALLATION 1. Determine the location for the termination(s). 2. If installing only vent (exhaust) piping in a Power Vent configuration through a sidewall; ensure that all exterior sidewall clearance requirements for the termination, shown in Figure 45a on page 36, are being maintained. These clearances and those cited by local and national codes must be maintained. 3. If installing both intake air and vent piping in a Direct Vent configuration through a sidewall; ensure that all exterior sidewall clearance requirements for the terminations, shown in Figure 45b on page 37, for the vent and intake air termination are being maintained. These clearances and those cited by local and national codes must be maintained. 4. If installing both an intake air and vent termination in a Direct Vent configuration through a sidewall there must be a minimum of 24 inches (61 cm) separation, measured on vertical center line, between the intake air and vent terminations, see Figure 22. NOTE: In colder climates this separation should be increased to at least 48 inches (122 cm) between the intake air and vent termination or any other appliance vent that discharges moisture-laden air such as clothes dryers. This will reduce possibility of frost over from side winds blowing exhaust vapors to the intake air termination and is recommended for Canadian installations. 5. If installing both intake air and vent terminations in a Direct Vent configuration through a sidewall the intake air and vent terminations must be installed at the same elevation measured on horizontal center line - see Figure 22. VENT (EXHAUST) TERMINA TION INT AKE AIR TERMINA TION INST ALL ON ELEVATION CENTERLINE 24 INCHES (61 cm) MINIMUM 48 INCHES (122 cm) IN COLDER CLIMA TES KEEP INTAKE AND VENT TERMINAT ION SCREENS CLEAR OF DEBRIS SIDEWA LL TERMINA TION - DIRECT VENT STANDARD TERMINATIONS Figure 22 6. When the intake air and/or vent piping from multiple water heaters will terminate at the same location through a sidewall, the vent terminations can be grouped together in close proximity - 0 inches/touching. The intake air terminations can also be grouped together in close proximity - 0 inches/ touching. However, the distance between the closest vent and intake air terminations must be a minimum of 24 inches (61 cm). In colder climates this separation should be increased to at least 48 inches (122 cm). See Figure 22. 7. Cut a 5 inch (13 cm) diameter hole for 4 inch pipe or 7 inch (18 cm) diameter hole for 6 inch pipe where the pipe(s) will pass through the wall. NOTE: Beware of concealed wiring and piping when cutting through the wall. 8. Cut a length(s) of pipe being installed 3.5 inches (8.9 cm) to 9.5 inches (24.1 cm) longer than the wall thickness at the opening. See Figure 23. NOTE: Vent Termination – exhaust gases of this water heater are less than 140°F. In cold climates water vapor in the exhaust gases will condense into a cloud of vapor where the vent exits the building. This vapor can gradually discolor exterior building surfaces. The vent termination should be located where this vapor cloud and potential discoloration are not a concern. Extending the exposed vent piping up to a maximum of 6 inches (15.2 cm) from the wall helps vapor from being trapped along a building’s face. To avoid this problem, the vent can also be terminated vertically through the roof, see Vertical Termination Installation on page 24. 9. Cement the intake air and/or vent termination to the section(s) of pipe cut to length in the above Step. 10. Slide the included metal wall plate(s) over the pipe(s) to stop against the intake air and/or vent termination. Place some silicone caulking (field supplied) on the back of the wall plate(s) to secure it to the wall. 11. Working from outside, slide the pipe and termination(s) assembled in the above steps through the wall. Ensure the termination(s) is pointed down towards the ground. See Figure 23. INTERIOR WA LL EXTERIOR WALL FROM WA TER HEAT ER COUPLING SIDEWA LL TERMINA TION INST ALLATION INTAKE AIR AND/OR VENT (EXHAUST) MET AL PLAT ES INST ALL INSIDE AND/OR OUTSIDE FACT OR Y SUPPLIED ST ANDARD TERMINATION POINTED DOWN TO WA RDS THE GROUND INCREASE EXPOSED VENT PIPING UP TO A MAXIMUM OF 6 INCHES (15.2 cm) FROM WA LL TO HELP PREVENT V APOR FROM DISCOLORING THE WALL SURF ACE IN COLDER CLIMA TES Figure 23 12. Place a bead of silicone caulking (field supplied) around the gap between the installed pipe(s) and the wall. Apply enough to fill the gap between the pipe(s) and wall. 13. Press the wall plate flush against the outside wall. 14. Working from the inside apply enough silicone caulking on the back of the interior wall plate(s) to hold it in place and slide the wall plate over the installed pipe(s). 15. Install a coupling to the end of the pipe(s) inside the building. Before the silicone caulking has time to completely set go outside the building and ensure the termination(s) is still pointing down towards the ground. See Figure 23. 16. Return to Power Vent Installation on page 23 or Direct Vent Installation on page 23 to complete the installation of the intake air and/or vent piping between the termination(s) and the water heater.
27 Installations must comply with applicable national, state, and local codes. For Canadian installation, Polypropylene vent must be listed as a ULC-S636 approved system. If Polypropylene vent is not required by your local code, you may use either PVC or CPVC pipes for your water heater that allows non-metallic venting material installations. Polypropylene vent systems do not use cement to connect the pipe and elbow sections but use a push together gasket seal method. Do not attempt to connect Polypropylene with sealant cement. All vent connections MUST be secured by the vent manufacturer’s joint connector. The installer must use a specific vent starter adapter at the flue connection. The adapter is supplied by the vent manufacturer to adapt to its vent system. In order to be in full compliance with UL 1738 or ULC-S636 and to meet the requirements of the water heater manufacturer, you must use the metal joint connector rings, available from the Polypropylene vent manufacturer, to stiffen the joints of 4” and 6” diameter pipes.POLYPROPYLENE INSTALLATIONS The water heaters covered by this manual have been approved to be installed with Polypropylene vent material as shown in Table 8 and Table 9. The approved application of single wall, non-flexible, non-concentric Polypropylene vent material is offered by two specific manufacturers (Centrotherm ECO Systems and DuraVent Polypropylene). These listed products must be installed by following the vent manufacturer’s instructions. Refer to Table 7-PVC/CPVC and Polypropylene on Page 22 to determine the maximum pipe length and number of elbows that can be used. Insulation should not be used on Polypropylene venting materials. The use of insulation will cause increased vent wall temperatures, which could result in vent pipe failure. Use only the adapters and vent system listed in Tables below. DO NOT mix vent systems of different types or manufacturers. Failure to comply could result in severe personal injury, death, or substantial property damage. TABLE 8 M & G Duravent PolyPro Vent system part numbers Nominal Pipe Diameter Flue Outlet Adapter Adapter Connector Ring Connector 90 Degree Elbow Vent Material Vent Terminal(s) 4” 4PPS-AD PPS-PAC4PPS-LB4PPS-E90B PPS4PPS-E45B for Exhaust; 4PPS-E45B for Intake (Direct Vent only) 6” 6PPS-06PVCM- 6PPF PPS-PACL 6PPS-LBC 6PPS-E90 PPS6PPS-E45 for Exhaust; 6PPS-E45 for Intake (Direct Vent only) TABLE 9 Centrotherm InnoFlue SW Vent system part numbers Nominal Pipe Diameter Flue Outlet Adapter Adapter Connector Ring Connector 90 Degree Elbow Vent Material Vent Terminal(s) 4” ISAGL 0404 IAFC04IANS04ISEL0487 Polypropylene ISELL0445UV for Exhaust; ISELL0445UV for Intake (Direct Vent only) 6” ISAGL 0606 IAFC06IANS06ISEL0687 Polypropylene ISELL0645UV for Exhaust; ISELL0645UV for Intake (Direct Vent only)
28 AL29-4C® VENT INSTALLATIONS (AL29-4C® is a registered trademark of Allegheny Technologies, Inc.) The water heaters covered by this manual are approved to be installed with AL29-4C® stainless steel vent material using parts from the manufacturers listed in Table 10 and Table 11 below. These listed systems must be installed using the vent manufacturer’s instructions including their listed clearances to combustible and noncombustible materials. Refer to Table 7-PVC/CPVC and Polypropylene on page 22 for the maximum and minimum equivalent linear vent lengths and number of elbows that may be used. However, use Table 10 and Table 11 below to find the appropriate equivalent linear vent lengths for the AL29-4C® elbows. Note: The equivalent lengths of the AL29-4C® elbows are different than those from smooth walled plastic vents. Consult Table 10 and Table 11 for the correct equivalent linear vent lengths. Listed vent systems composed of AL29-4C® must not mix parts from the different manufacturers. The joints of these products are sealed by internal gaskets. Do not use any other type of sealant. When assembling these vent systems, follow the vent manufacturer’s instructions for cleaning and lubricating the joints, if required. Each section must be locked together using the method supplied by the vent manufacturer. The water heaters covered by this manual are approved to be installed using the approved vent terminations shown in this manual. This means that, the installer must use the adapter listed in Table 10 and Table 11 and a short piece of PVC pipe to complete the end of the vent system with an approved termination. In Canada, the PVC pipe length must be listed to ULC636. TABLE 10 HeatFab Saf–T Vent AL29-4C® Vent System Parts Diameter Flue Outlet Adapter *Straight Pipe (3’ Section) 45° ElbowEquivalent Linear Length, 45° Elbow 90° Elbow Equivalent Linear length, 90° Elbow Adapter to PVC 4" 9401 PVC 9307 94115 feet 941410 feet9454CPVC 6" 9601 PVC 960796115 feet 961410 feet9656CPVC *Consult vent manufacturer’s catalog for other available lengths. TABLE 11 Duravent FasNSeal AL29-4C® Vent System Parts Diameter Flue Outlet Adapter *Straight Pipe (3’ Section) 45° ElbowEquivalent Linear Length, 45° Elbow 90° elbowEquivalent Linear Length, 90° Elbow Adapter to PVC 4" 810005545 FSVL3604FSELB4504 5 feetFSELB9004 10 feet810009529 6" 810005225 FSVL3606FSELB4506 5 feetFSELB9006 10 feet81005572 *Consult vent manufacturer’s catalog for other available lengths.
29 termination caps for all concentric terminations must be at the same height measured from ground. See Multiple Concentric Termination Arrangements on page 31. 9. Determine if the concentric termination will need to be shortened to accommadate required clearances or to ensure all vent caps are at the same height when installing multiple terminations vertically through the roof in the same location. See Figure 25 for the minimum lengths allowed for the 6 inch concentric termination. Note: When shortening the length of the termination carefully measure and cut the larger (intake air) pipe first. Cut the same amount of pipe off of the smaller (vent) pipe. Note: Lengthening of the Concentric Vent Termination is not permitted. CONCENTRIC TERMINATION(S) MUST BE A MINIMUM OF 10 FEET (3 m) AWAY FROM ANY PA RAPET, VER TICAL WA LL OR STRUCTURE. 6 INCH CONCENTRIC TERMINA TION FLA T ROOF CLEARANCE Figure 24 CONCENTRIC TERMINATION INSTALLATION 1. Concentric terminations must be ordered separately. (A) HCG3 119T300/400/500 models must use the 6 inch concentric termination for both 4" & 6" vent diameters; Part Number: 9008841005. Contact your local distributor or call the parts department phone number on the back cover of this manual to order concentric terminations. 2. Determine the location for the termination. NOTE: Roof termination is preferred since it is less susceptible to damage, has reduced chances to intake contaminants and vent vapors are less visible. 3. When installing a concentric termination vertically through the roof; ensure that all exterior vertical clearance requirements for the concentric termination, shown in Figure 24 on page 29 and Figure 26 on page 30, are being maintained. These clearances and those cited by local and national codes must be maintained. 4. When installing a concentric termination vertically through a flat roof, the termination's vent cap must be a minimum of 10 feet (3 m) away from any parapet, vertical wall or structure as shown in Figure 24. NOTE: If this required distance to a parapet, vertical wall or structure cannot be maintained, standard terminations must be used. See Vertical Termination Installation on page 24. 5. When installing a concentric termination through a sidewall; ensure that all exterior sidewall clearance requirements for the termination, shown in Figure 45b on page 37, are being maintained. These clearances and those cited by local and national codes must be maintained. 6. When installing multiple concentric terminations vertically through a roof or horizontally through a sidewall ensure the required clearances between terminations and groupings of multiple terminations are maintained. See pages 31 and 32 for more information. 7. Cut a 7 inch (18 cm) diameter hole for 6 inch concentric terminations where they will pass through the wall or roof. NOTE: Beware of concealed wiring and piping when cutting through the wall or roof. 8. When installing multiple concentric terminations vertically through the roof in the same location the
30 6 INCH CONCENTRIC TERMINATION INSTALLATION 6 INCH CONCENTRIC TERMINATION KITFIELD ASSEMBL Y REQUIRED VENT PIPE INT AKE AIR CONNECTION VENT CONNECTION - 4 INCH PVC INTAKE AIR PIPE Y FITTING ASSEMBLY VENT CAP VENT PIPE ASSEMBL Y VENT PIPE IS 4 INCH SDR-26 PIPE SUPPLIED LENGTH 46.50” (1 18 cm) MINIMUM ALLOWABLE LENGTH 16.38” (41.6 cm) INT AKE AIR PIPE IS 6 INCH SDR-26 PIPE SUPPLIED LENGTH 25.38” (64.5 cm ) MINIMUM ALLOWABLE LENGTH 12” (30 cm )VENT CAP INT AKE AIR PIPE 6” x 6” x 6” Y FITTIN G 6” x 4” BUSHING (FACTO RY INST ALLED) Figure 25 Assemble and install the 6 inch concentric termination. Refer to Figure 25, Figure 26 and Figure 27 for these instructions: 1. Cement the Y fitting to the larger diameter intake air pipe. 2. Slide the intake air pipe and Y fitting assembly from inside the building through the hole cut for the termination in the roof or sidewall. Ensure no foreign materials such as insulation accumulate inside the assembly. 3. Secure the intake air Y fitting assembly using field supplied metal strapping or equivalent support materials. 4. On installations installed through the roof slide a field supplied plumbing boot or roof flashing over the intake air Y fitting assembly and secure it to the roof. 5. Seal around the plumbing boot or roof flashing. 6. Cement the vent cap onto the vent pipe. Alternately a field- supplied stainless steel screw may be used to secure the 2 components together when field disassembly is desired for cleaning. A pilot hole must be drilled for the screw to prevent damage/cracking of the vent cap and/or vent pipe. 7. Install the vent cap/vent pipe assembly into the intake air Y fitting assembly, Ensure small diameter vent pipe is cemented and bottomed in the Y fitting. 8. Connect the intake air and vent piping from the water heater to the 6 inch concentric termination using field supplied 6” x 4” reducer couplings as needed. 9. Return to Direct Vent Installation on page 23 to complete the installation of the intake air and vent piping between the concentric termination and the water heater. NOTE: SECURING STRAP MUST BE FIELD INST ALLED TO PREVENT MOVEMENT OF TERMINA TION KIT MAINT AIN 12” (30 cm) 18” (45 cm) FOR CANADA MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPAT ED SNOW LEVEL. MAXIMUM OF 24” (60 cm) ABOVE ROOF . ROOF FLASHING (field supplied) STRAP (field supplied) VENT PIPE INT AKE AIR PIPE COMBUSTION AIR VENT 6 INCH CONCENTRIC TERMINATION VER TICAL INSTALLATION Figure 26 NOTE: SECURING STRAP MUST BE FIELD INST ALLED TO PREVENT MOVEMENT OF TERMINA TION KIT IN SIDEW ALL. STRAP (field supplied) VENT PIPE INT AKE AIR PIPE COMBUSTION AIR VENT 1 INCH MAXIMUM 6 INCH CONCENTRIC TERMINATION SIDEW ALL INST ALLATION Figure 27