Home
>
American Water Heater
>
Gas Heater
>
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual
Have a look at the manual American Water Heater High Efficiency Commercial Gas HCG Series AHCG3 119T 300 THRU AHCG3 119T 500 Series 200 201 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 32 American Water Heater manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
41 8. Route the control wires inside the junction box on the top of the water heater; see Figure 3 on page 8 to locate the junction box. Use an available knock-out to route the wires inside the junction box. 9. Install field supplied control wiring and conduit as required by national and local codes between the water heater’s junction box and the external supervisory control. Connect the wiring from the external control to the control wires inside the junction box using wire nuts and electrical tape. 10. Connect the control wiring to a set of dry contacts on the external control. Follow the control manufacturer’s instructions for making connections. 11. Restore power to the water heater. 12. From the water heaters UIM “Heater Information Screen” select “Use External Enable” and change to “Yes”. See Figure 3 on page 8 to locate the UIM. NOTE: Whenever the external control opens the set of dry contacts used, water heating operation will be disabled. Whenever the external control closes the set of dry contacts used, water heating operation will be enabled. A diagonal line and circle appears over the thermometer icon on the UIM when water heating operation is disabled. See the Status Icons descriptions in Table 16 on page 45. NOTE: Ensure the water heater is protected from freezing temperatures when water heating operation is disabled. Damage to the water heater caused by freezing temperatures is not covered under the limited warranty. WATER LINE CONNECTIONS The water piping installation must conform to these instructions and to all local and national code authority having jurisdiction. Good practice requires that all heavy piping be supported. Read and observe all requirements in the following sections before installation of the water piping begins: 1. Mixing Valves on page 14. 2. Dishwashing Machines on page 14. 3. Temperature-Pressure Relief Valve on page 15. 4. Closed Systems and Thermal Expansion on page 14. 5. For multiple water heater installations see Water Piping Diagrams beginning on page 68. WATER PIPING DIAGRAMS This manual provides detailed water piping diagrams for typical methods of application for the water heaters, see Water Piping Diagrams beginning on page 68. The water heater may be installed by itself, or with a separate storage tank. When used with a separate storage tank, the circulation may be either by gravity or by means of a circulating pump. When a circulating pump is used, it is important to note that the flow rate should be slow so that there will be a minimum of turbulence inside the water heater storage tank. Adjust flow by throttling a full port ball valve installed in the circulating line on the outlet side of the pump. Never throttle flow on the suction side of a pump. See the Water Piping Diagrams beginning on page 68. NOTE: In addition to the factory installed Temperature-Pressure Relief Valve (T&P valve) on the water heater, each remote storage tank that may be installed and piped to a water heating appliance must also have its own properly sized, rated and approved Temperature-Pressure Relief Valve installed. Call the toll free technical support phone number listed on the back cover of this manual for further assistance in sizing a T&P valve for remote storage tanks. NOTE: If electrical connections are made directly to the terminal block remove the jumper wires before making connection. 5. Connect the ground wire from the power supply to the green jumper wire or the ground terminal location inside of the junction box located on top of the water heater. If the green jumper wire is used, make the connection inside of the junction box with a properly sized wire nut and wrap electrical tape around the wire nut and wire end. See junction box Figure 49 and wiring diagram Figure 58 on page 66. 6. Replace the junction box cover when connections are complete. NOTE: Do not apply power to the water heater before installation is complete and the water heater is filled with water. Heater Wiring(Factory Installed) MOVGround Ground Terminal Jumper Wire L1 Neutral Figure 49 ENABLE/DISABLE CIRCUIT ( For Building Management Systems) The water heaters covered in this manual are equipped with an enable/disable circuit for use with field supplied external supervisory controls such as time clocks or Building Management Systems. The enable/disable circuit may be used to disable heating operation during periods when the building is unoccupied or there is no demand for hotwater. To use the enable/disable circuit it must first be activated by selecting the “Use External Enable” from the UIM. Field supplied wiring is then installed between the water heater’s CCB and a set of “dry contacts” (no voltage or load) on the field supplied external control. NOTE: The water heater’s enable/disable circuit is a switching circuit only: Do not apply external voltage or connect any load (IE: relay coil) to this circuit. This will damage the CCB circuit board and is not covered under the limited warranty. CONNECTING AN EXTERNAL SUPERVISORY CONTROL The enable/disable circuit is accessed from the CCB’s J17 plug inside the CCB enclosure; see Figure 3 on page 8 to locate the CCB enclosure and Figure 57 on page 65 for the CCB layout. Install field wiring to the enable/disable circuit: 1. Turn off power at the water heater’s enable/disable switch and the breaker that supplies power to the water heater. 2. Locate the CCB enclosure. 3. Carefully remove the Temperature Probe connectors and CCB enclosure cover. 4. Locate pins 1 and 2 on the CCB J17 plug. See Figure 57 on page 65. 5. Connect the two field supplied control wires to pins 1 and 2 on the CCB J17 plug. 6. Thread the control wires out of the CCB enclosure with the other wiring and carefully replace the CCB enclosure cover. Ensure all wiring is routed through the intended area provided for strain relief. Ensure no wiring is being pinched. 7. Reinstall the CCB enclosure cover.
42 This water heater is provided with a properly rated/sized and certified combination temperature - pressure (T&P) relief valve by the manufacturer. See Temperature-Pressure Relief Valve on page 15 for information on replacement and other requirements. Water Damage Hazard Temperature-Pressure Relief V alve discharge pipe must terminate at adequate drain. CAUTION Install a discharge pipe between the T&P valve discharge opening and a suitable floor drain. Do not connect discharge piping directly to the drain unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in adequate quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage. T&P Valve Discharge Pipe Requirements: • Shall not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions. • Shall not be plugged or blocked. • Shall not be exposed to freezing temperatures. • Shall be of material listed for hot water distribution. • Shall be installed so as to allow complete drainage of both the Temperature-Pressure Relief Valve and the discharge pipe. • Must terminate a maximum of six inches above a floor drain or external to the building. In cold climates, it is recommended that the discharge pipe be terminated at an adequate drain inside the building. • Shall not have any valve or other obstruction between the relief valve and the drain. THERMOMETERS (NOT SUPPLIED) Thermometers are installed in the water piping system as a means of detecting the temperature of the hot water supply at critical points in the system. Field supplied thermometers should be obtained and installed. See Water Piping Diagrams on page 68. WATER (POTABLE) HEATING AND SPACE HEATING 1. All water piping components connected to the water heater that are for space heating applications shall be suitable for use with potable water. 2. Toxic chemicals, such as those used for boiler treatment, must NEVER be introduced into this system. 3. The water heaters covered in this manual may never be connected to any existing heating system or component(s) previously used with non-potable water heating appliance. 4. When the system requires water for space heating that exceed safe temperatures at domestic water fixtures a mixing valve must be installed, see Mixing Valves on page 14. 5. These water heaters cannot be used in space heating applications only. T&P VALVE DISCHARGE PIPE Explosion Hazard Temperature-Pressure Relief Valve must comply with ANSI Z21.22- CSA 4.4 and ASME code. Properly sized temperature- pressure relief valve must be installed in opening provided. Can result in overheating and excessive tank pressure . Can cause serious injury or death.
43 TABLE 15 Water Temperature °F (°C) Time for 1st Degree Burn (Less Severe Burns) Time for Permanent Burns 2nd & 3rd Degree (Most Severe Burns) 110 (43) (normal shower temp.) 116 (47) (pain threshold) 116 (47) 35 minutes 45 minutes 122 (50) 1 minute 5 minutes 131 (55) 5 seconds 25 seconds 140 (60) 2 seconds 5 seconds 149 (65) 1 second 2 seconds 154 (68) instantaneous 1 second (U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)The water heaters covered in this manual are equipped with an electronic control system to regulate the water temperature inside the storage tank. The control system senses temperature from two factory installed temperature probes, one installed in the top of the storage tank and one installed near the bottom, See Figure 3 on page 8 and Figure 4 on page 9 for location. The “Operating Set Point” is adjusted to regulate water temperature inside the storage tank. This is an adjustable user setting in the control system’s “Temperatures Menu.” This and all control system menus are accessed through the UIM (user interface module) located on the front of the water heater, see Figure 52. The Operating Set Point is adjustable from 90°F (42°C) to 180°F (82°C). The factory setting is 120°F (49°C). See Operating Set Point And Differential Adjustment on page 47 for instructions on how to adjust the Operating Set Point and other user settings. Set the Operating Set Point at the lowest setting which produces an acceptable hot water supply. This will always provide the most energy efficient operation. MODULATION The water heaters covered by this manual are capable of modulating their firing rate. The CCB monitors the water temperature in the tank and regulates the firing rate to achieve the target temperature setpoint. The firing rate is dictated by the hot water draw, proximity to the tank temperature setpoint, and various other temperature limitations. Periodically, when the heater is in modulation mode, the CCB will increase the blower speed for a short period of time to clear out any condensation that has accumulated in the heat exchanger then decreases the blower speed back to the modulating firing rate required to maintain the desired tank temperature setpoint. This ramping up and down of the blower speed is considered normal operation of the water heater. HIGH TEMPERATURE APPLICATIONS Higher operating temperatures cause more wear on all water heaters and will decrease the life span of the water heater. Consider installing a small booster water heater for high temperature applications, such as commercial dishwashers, to raise the outlet temperature from the larger primary water heater to the desired point of use temperature. Contact your local distributor or call the technical support phone number listed on the back cover of this manual for further technical assistance. Tank Temperature 103°F Operating Set Point 120°F Status: Heating MENU HELP UP DN GASOFF ON MANUF ACTURER / MODEL INFORMATION Figure 50 HIGH TEMPERATURE LIMIT CONTROL (ECO) This water heater is equipped with an ECO (energy cut off) non adjustable high temperature limit switch. The ECO is a normally closed switch that opens (activates) on a rise in temperature. The ECO is located inside the Upper Temperature Probe (two red wires), see Figure 3 on page 8 for location. The ECO switch contacts will open when the water temperature reaches approximately 202°F (94°C) and close at approximately 140°F (49°C). If the ECO activates (contacts open) due to abnormally high water temperatures in the storage tank the control system will immediately de-energize the 24 VAC Gas Valve and end the current heating cycle. The control system will "lock out" disabling further heating operation. The control system will display the "Energy Cut Out (ECO)" Fault message on the LCD screen. It is important that a Qualified Service Agent be contacted to determine the reason for the ECO activation before resetting the ECO. Once the reason has been determined and corrected the ECO can be reset as follows: Should the ECO activate, the water temperature must drop below 140°F (49°C) before the control system can be reset. Once the water temperature has cooled below this point the power supply to the water heater must be turned off and on again to reset the control system. THERMOSTAT CONTROL Water temperature over 125°F (52°C) can cause severe burns instantly resulting in severe injury or death. Children, the elderly and the physically or mentally disabled are at highest risk for scald injury . Feel water before bathing or showering. Te mperature limiting devices such as mixing valves must be installed when required by codes and to ensure safe temperatures at fixtures. Hot water temperatures required for automatic dishwasher and laundry use can cause scald burns resulting in serious personal injury and/or death. Table 15 shows the approximate time-to- burn relationship for normal adult skin. The temperature at which injury occurs varies with the person’s age and duration of exposure. The slower response time of children, the elderly or disabled persons increases the hazards to them. If anyone using hot water provided by the water heater being installed fits into one of these groups or if there is a local code or state law requiring a certain water temperature at the point of use, then special precautions must be taken. In addition to using the lowest possible temperature setting that satisfies the demand of the application a mixing valve can be installed at the water heater (see Figure 8 on page 14) or at the hot water taps to further reduce system water temperature. Never allow small children to use a hot water tap or draw their own bath water. Never leave a child or disabled person unattended in a bathtub or shower. The water heater should be located in an area where the general public does not have access to set temperatures. Setting the Operating Set Point at 120°F (49°C) will reduce the risk of scalds. Some States require settings at specific lower temperatures. TEMPERATURE REGULATION
44 CONTROL SYSTEM OPERATION Tank Temperature 103°F Operating Set Point 120°F Status: Heating MENU HELP GASOFF ON MANUF ACTURER / MODEL INFORMATIONLCD Screen Information Display Status Icons 3 Operational buttons: enter/exit menus, select menu items, activate adjustment modes, confirm/cancel changes. Up & Down buttons: navigate menus, adjust user settings Title Bar Enable/Disable Switch Operational buttons are multi functional. Their current function is defined by the text that appears directly above each button on the LCD screen. UIM (user interface module) Desktop Screen Shown UP DN Figure 52 OVERVIEW The water heaters covered in this manual are equipped with an electronic control system that regulates water temperature inside the storage tank. Heating cycles and ignition are managed by the control system. The ECO (energy cut out), flame sensor, pressure switches and temperature probes are monitored by the control system. The Combustion Blower, spark ignition control, 24 VAC Gas Valve and anode rods are all powered by the control system. The main components of the control system are a UIM (user interface module) and a CCB (central control board). The UIM is located on the top front side of the water heater. The CCB is mounted on top of the water heater inside a protective enclosure. This unit is equipped with an Enable/Disable switch. To operate unit, make sure the switch is set to Enable. See Features And Components on page 7 for location of these and all water heater components. POWER SUPPLY BOARD TRANSFORMER CCBBOARD Figure 51 CONTROL SYSTEM NAVIGATION All operational information and user settings are displayed and accessed from the UIM. The UIM houses the control system's LCD (liquid crystal display) and five snap acting (momentary) user input buttons; an up, down and three (3) multi functional operational buttons below the LCD, see Figure 52. User Input Buttons • The up and down buttons are used to navigate menus and adjust user settings. • The operational buttons are used to enter/exit menus, select menu items, activate adjustment modes and confirm or cancel new user settings. The operational buttons are multifunctional, their current function is defined by the text that appears directly above each button on the LCD screen. THE DESKTOP SCREEN During normal operation the control system will display the "Desktop" screen on the LCD which is the default screen. The control system will return to the Desktop screen when there are no active Fault or Alert conditions or when there has been no user input for several minutes. • Manufacturer and water heater model information is displayed in Title Bar at the top of the Desktop screen. Menu titles are displayed in the Title Bar when navigating the control system menus. • The first temperature shown on the Desktop screen, Tank Temperature, is the temperature of the water inside the water heater's storage tank. • The second temperature shown on the Desktop screen is the Operating Set Point. The Operating Set Point is the temperature at which the control system will maintain the water inside the storage tank. • Beneath the Operating Set Point is the "Status" line. The Status line shows the current operational state of the control system in real time, see Table 17 on page 46 for a description of the various operational states. • The Desktop screen also displays animated "Status Icons" to convey operational information, see Table 16 on page 45 for descriptions of the Status Icons.
45 STATUS ICONS The Status Icons are displayed on the Desktop screen and convey operational and diagnostic information. The icons are described in the table below. See Figure 54 on page 57 and the Sequence Of Operation on page 56. TABLE 16 IconDescription Water temperature in the tank has fallen. Shaded area of the animated thermometer icon will rise and fall in response to water temperature in the storage tank as sensed from the Upper and Lower Temperature Probes. See Figure 3 on page 8 and Figure 4 on page 9 for location of Temperature Probes. Water temperature in the tank has reached the Operating Set Point. The control system enters the Standby mode. The control is unable to initiate a heating cycle. This will happen whenever a Fault condition is detected by the control system or when the Enable/Disable switch on front panel is in disable position or Building Management system Enable/Disable circuit is an open circuit. Display will read "Status: Water Heating Disabled". For more information see Enable/Disable Circuit on page 41. The Combustion Blower is being energized. The Blower Prover pressure switch contacts have closed. The check mark icon is visual confirmation of contact closure. See Figure 3 on page 8 for Blower Prover Switch location. The spark igniter is being energized. See Figure 2 on page 7 for spark igniter location. GAS OFF ONThe 24 VAC Gas Valve is being energized. The control system has sensed flame at the Main Burner from the flame sensor. See the Sequence Of Operation Flow Chart on page 57 and Figure 2 on page 7. The control system has declared a Fault condition and must be inspected/serviced by a Qualified Service Agent. Fault message details can be viewed in the Current Fault menu. Heating operation is disabled (lock out) until the condition that caused the Fault is corrected. Power to the water heater must be cycled off and on at the breaker to reset the control system. NOTE: Cycling power will not reset the control system if the condition that caused the Fault has not been corrected. The control system has declared an Alert condition and must be inspected/serviced by a Qualified Service Agent. The water heater will continue to operate during an Alert condition.
46 OPERATING STATES The current operational state of the water heater is displayed on the Desktop screen as the "Status." The common operational states are described in the table below. See Figure 54 on page 57 and the Sequence Of Operation on page 56. TABLE 17 StateDescription Standby The water heater is not in an active heating cycle. IE: the Tank Temperature is at or above the Operating Set Point. Input Verification The control system is conducting a diagnostic check at the beginning of a heating cycle. Water heating disabled A Fault condition is detected by the control or when the Enable/Disable switch on front panel is in disable position or the Building Management system Enable/Disable is an open circuit. Pre-Purge The Combustion Blower is energized to flush residual flue gases from the combustion chamber prior to ignition. Spark Igniter Energized The Spark Igniter is energized. Ignition Activation The 24 VAC Gas Valve is energized and opens to allow fuel gas to flow to the Main Burner. Ignition Verification The control system is monitoring the flame sensor for the required minimum flame sensing current. See the Sequence Of Operation on page 56 for minimum flame sensing current (DC micro amps) information. Inter-Purge The Combustion Blower is energized to flush residual fuel gas from the combustion chamber after a failed ignition attempt. Heating Ignition was successful, flame sensing current has been established. The water in the storage tank is being heated. Post-Purge The Combustion Blower is energized to flush residual flue gases from the combustion chamber at the end of a heating cycle. Fault The control system has detected a Fault condition. Heating operation is disabled until the Fault condition is corrected. Power to the water heater must be cycled off and on at the breaker to reset the control system. NOTE: Cycling power will not reset the control system if the condition that caused the Fault has not been corrected. CONTROL SYSTEM MENUS From the Desktop screen pressing the Operational button directly below "Menu" on the LCD will display the "Main Menu" this is where all control system menus are located. The table below describes the control system menus. TABLE 18 Menu Description Temperatures Most commonly accessed menu. Contains the Operating Set Point and Dif ferential user settings. Heater Status This menus displays the current state of all pressure switches and the ECO (open/closed). The on/off status of the Combustion Blower, gas valve, spark igniter, flame sensor and other monitored water heater components are displayed in this menu. Display Settings Temperature units (°F or °C), the LCD appearance (brightness/contrast) and backlight delay user adjustable settings are located in this menu. Heater Information Elapsed time of operation, total heating cycle time, heating cycle count, heating on time along with UIM and CCB software revisions can be viewed in this menu. Current Fault Displays any current Alert or Fault messages. Fault History This control system menu retains a list of the last nine (9) Fault and Alert messages with a time stamp. The newest event will replace the oldest. Faults will clear after 30 days. Fault Occurrence This control system menu retains a running total of how many times each Fault condition has occurred since the water heater was first installed. This screen does not clear and the information can not be reset. Restore Factory Defaults This control system feature allows the user to restore control system user settings to their factory default settings. Display Settings preferences ARE NOT changed when factory defaults are restored. Help Screens Text based operational and user information explaining how to change user settings, navigate the control system menus and icon descriptions.
47 USER SETTINGS & CONTROL SYSTEM MENUS TEMPERATURES MENU Operating Set Point And Differential Adjustment The Operating Set Point is adjustable from 90°F (42°C) to 180°F (82°C). The factory setting is 120°F (49°C). The Differential is adjustable from 2° to 20°. The factory setting is 8°. These user settings are accessed from the Temperatures menu. The following instructions will explain how to adjust these settings and navigate the control system menus. When the water temperature sensed by the control system from the two (upper and lower) Temperature Probes reaches the Operating Set Point the control system will end the heating cycle. A heating cycle will be activated again when the sensed water temperature drops below the Operating Set Point minus the Differential setting. NOTE: Lower Differential settings may cause excessive heating cycles (short-cycling) which can cause premature failure of components such as the Hot Surface Igniter. Set the Differential at the highest setting which produces an acceptable hot water supply. Set the Operating Set Point to the lowest setting which produces an acceptable hot water supply for most efficient use. DESCRIPTION/ACTIONDISPLAY From the Desktop screen, press the Operational Button under MENU. The "Main Menu" screen will be displayed. Ta nk Temperature 120°F Operating Set Point 120°F Status: Standby MENUHELP MANUF ACTURER / MODEL INFORMA TION The Main Menu is where all control system menus are listed, see Table 18 on page 46 for a complete list and description of control system menus. Use the Up and Down Buttons to view all control system menus from the Main Menu. With Temperatures menu selected (highlighted in black) in the Main Menu screen, press the Operational Button under “SELECT” to enter the Temperatures menu. If the Temperatures menu is not selected use the Up and Down Buttons to select this menu item. Temperatures Heater Status Display Settings Heater Information Current Fault SELECT BACK HELP Main Menu With the Operating Set Point selected in the Temperatures menu, press the Operational Button underneath “CHANGE” to activate the adjustment mode for this menu item. If Operating Set Point is not selected use the Up and Down Buttons to select this menu item. NOTE: Higher Temperature settings increase wear and operating costs. Set the Operating Set Point to the lowest setting which produces an acceptable hot water supply. This will always provide the most energy efficient operation and longer life. Operating Set Point 120°F Dif ferential 8°F Ta nk Temperature 120°F Ta nk Probe Of fset 0°F CHANGE BACK HELP Temperatures With the adjustment mode for the Operating Set Point activated the selection bar will change from a black fill to a black outline. Use the Up and Down Buttons to change the current setting. Press the Operational Button under "UPDATE" to save the new setting. Press the Operational Button under "CANCEL" to discard changes and return to the previously saved setting. NOTE: Use this same procedure to change the Differential setting and other adjustable user settings in the control system menus. Operating Set Point 140°F Dif ferential 8°F Ta nk Temperature 120°F Ta nk Probe Of fset 0°F UPDATE CANCEL Temperatures
48 TEMPERATURES MENU (CONT) DESCRIPTION/ACTIONDISPLAY • Differential - Adjustable user setting that changes the tank temperature differential with a range of 2° to 20°F. The factory setting is 8°F. • Tank Temperature - non adjustable - control system sensed temperature (averaged from upper and lower temperature probes). • Tank Probe Offset - adjustable user setting, range -5° to +5° (factory setting 0°). NOTE: These settings should only be used if the hot water supply temperature varies greatly from the Operating Set Point setting. The Tank Probe Offset is used to calibrate control system temperature sensing. This can improve the precision of temperature control in the storage tank and at points of use. This feature can also be used to compensate for building recirculation loops (hot water returning to the storage tank) that may cause the heating cycles to terminate prematurely. Example: If the current sensed temperature from a temperature probe is 120°F (49°C) and the Offset setting for that probe is adjusted to a value other than 0°, the control system would calibrate or “offset” the sensed temperature from the probe and the averaged tank temperature. Heating cycles would be activated and deactivated based on the calibrated (offset) temperature. A -5° setting results in +5° hotter water. These settings are adjusted in the same way described for the Operating Set Point And Differential Adjustment on page 47. Operating Set Point 140°F Dif ferential 8°F Ta nk Temperature 120°F Ta nk Probe Of fset 0°F CHANGE BACK HELP Temperatures HEATER STATUS MENU DESCRIPTION/ACTION DISPLAY Select Heater Status from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains non adjustable operational information. Use the Up & Down Buttons to navigate the menu. • Status - displays the current Operating State, see Table 17 on page 46. • ECO Contact, Low Gas PS , Blocked Inlet PS, Blocked Outlet PS , Blower Prover PS - displays the current state of the switch contacts; open or closed. • Igniter On , Gas Valve On - displays whether or not the control system is currently energizing these water heater components; yes = energized, no = de-energized. • Flame Detected - displays whether or not the control system has detected Main Burner flame during ignition from the flame sensor. NOTE: Menu display is shown with Enable/Disable switch in Enable position. Top of Menu Status Standby ECO Contact Closed Low Gas PS Closed Blocked Inlet PS Closed Blocked Outlet PS Closed Blower Prover PS Open Igniter On No BACK HELP Heater Status Bottom of Menu Gas Valve On No Flame Detected No BACK HELP Heater Status
49 DISPLAY SETTINGS DESCRIPTION/ACTIONDISPLAY Select Display Settings from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains adjustable display options for viewing information on the UIM’s LCD screen. Use the Up & Down Buttons to navigate the menu. • Temperature Units - Adjustable user setting that changes temperature units display to Celsius °C or Fahrenheit °F. • Backlight Delay - Adjustable user setting that determines how long the UIM’s LCD backlight remains illuminated after a key has been pressed. Available settings are; Always Off, 10, 30 or 60 seconds and Always On. • Contrast - Adjustable user setting to adjust the UIM’s LCD screen contrast between text and background. NOTE: These settings are adjusted in the same way described for the Operating Set Point And Differential Adjustment on page 47. Te mperature Units °F Backlight Delay 30s Contrast 60% CHANGE BACK HELP Display Settings HEATER INFORMATION DESCRIPTION/ACTION DISPLAY Select Heater Information from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains non adjustable operational information. • Elapsed Time - Total accumulated time the control system (water heater) has been energized. • Burner On Time - Total accumulated time the control system has been in the heating operating state; burner run time. • Total Cycle Count - Total accumulated count of heating cycles. • CCB Version - Software version for central control board. • UIM Version - Software version for user interface module. • Config CRC - Verifies the configuration key matches the CCB programming. • Use External Enable - Enables/Disables the external enable circuit. • External Enable Status - displays whether or not the external enable circuit has been activated. • Ignition Trials - displays the number of ignition trials allowed. NOTE: Historical data is stored in the configuration key. If this 'key' is replaced during servicing the historical data will be lost. The data stored in the new configuration key will no longer reflect the entire history of the water heater. The Elapsed Time, Burner On Time and Cycle Count indicate age, usage and wear. If the Cycle Count per day is high (divide cycle count by days to determine cycles per day) or the cycle duration is short (determine burner on time total minutes, divide burner on time total minutes by cycle count) consider rasing the Differential setting to avoid short cycling and excessive component wear, see Operating Set Point And Differential Adjustment on page 47. This historical data can also be used to assist facilities managers in forecasting planned replacement of equipment to help avoid lengthy and costly hot water supply interruptions. Elapsed Time 10 day 0 hrs 0 mins Burner On Time 5 hrs 22 mins To tal Cycle Count 00000035 CCB V ersion X.XX Config CRC 0 x 605D CHANGE BACK HELP Heater Information UIM Version X.XX Use External Enable No External Enable Status No Ignition Trials 3 BACK HELP Heater Information
50 CURRENT FAULT DESCRIPTION/ACTIONDISPLAY Select Current Fault from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains non adjustable operational information. Use the Up & Down Buttons to navigate the menu. This menu contains the current Fault or Alert error message. The time the Fault or Alert message occurred appears directly below. A brief description of what causes the particular Fault or Alert condition appears below that. Pressing the Operational Button under "ADVANCED" will give more detailed service information and a list of possible causes for the Fault or Alert condition. See Fault And Alert Messages on page 59 for more detailed information and diagnostic procedures. If there is no Fault or Alert condition active this menu will not contain any information, "(none)" will be shown next to Current Fault in the Main menu. CHANGE BACK ADV ANCED Blocked Exhaus tFault occurred 2 mins ago Restriction in exhaust pipe. Check exhaust pipe and termination for blockage. Call a service professional: Your Company Name Here (press [DOWN] for more.... ) FAULT HISTORY DESCRIPTION/ACTION DISPLAY Select Fault History from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains non adjustable operational information. Use the Up & Down Buttons to navigate the menu. This menu contains a list of the last nine (9) Fault and Alert messages with a time stamp. The newest event will replace the oldest. Press the Operational Button under "VIEW" to view details for each Fault or Alert message stored. 1: Blocked Air Intake (A7) 51 mins ago 2: Blocked Exhaust (A8 ) 54 mins ago 3: Low Gas Pressure (A6 ) 57 mins ago 4: Blower Prover Failure (AC ) VIEW BACK HELP Fault History FAULT OCCURRENCE DESCRIPTION/ACTION DISPLAY Select Fault Occurrence from the Main Menu and press the Operational Button under "SELECT" to enter this menu. This menu contains non adjustable operational information. Use the Up & Down Buttons to navigate the menu. This menu contains a running total of how many times each Fault condition has occurred since the water heater was first installed. NOTE: Historical data is stored in the Configuration Key. If this 'key' is replaced during servicing the historical data will be lost. The data stored in the new configuration key will no longer reflect the entire history of the water heater. Ignition Failure 10 ECO 0 Low Gas Pressure 10 Blocked Intake Air 0 Blocked Exhaust 0 Blower Prover 0 Flame Detect Error 3 BACK HELP Fault Occurrence RESTORE FACTORY DEFAULTS DESCRIPTION/ACTION DISPLAY Select Restore Factory Defaults from the Main Menu and press the Operational Button under "SELECT" to enter this menu. To restore the adjustable user settings to their factory default settings press the Operational Button underneath “YES.” The display will show text confirming the factory default settings have been restored. Press the Operational Button underneath “BACK” to exit the Restore Factory Defaults menu. YES NO Restore Factory Default s Are you sure you want to restore the system to factory defaults?