Aimco Brakes Monitor UTM1500 Fastening Counter Manual
Here you can view all the pages of manual Aimco Brakes Monitor UTM1500 Fastening Counter Manual. The Aimco Brakes manuals for Monitors are available online for free. You can easily download all the documents as PDF.
Page 21
21 LS1+TIMER ・Fastening operation will start at the time of LS1 input, and the line control timer will also start. When the preset fastening number is attained, COUNT OK will result, and then LS1 input will be accepted only after COUNT OK terminal output (output duration time can be set by using COUNT OK output timer). ・If the line control timer has become time-out before completing the preset fastening number, COUNT NOK will result. In this case, fastening operation will finish when COUNT OK...
Page 22
22 W.SELECT ・Fastening operation will start upon WORK SELECT 1~4 input. ・When the preset fastening number is attained, Work No. specific COUNT OK will be output (output duration time can be set by using COUNT OK output timer). ・When the preset fastening number is not attained at the time of WORK switching input OFF condition, COUNT NOK will result. ・ In addition, when WORK SELECT input is turned OFF before attaining the preset fastening number, COUNT NOK will result....
Page 23
23 W. SEL. TIMING (WORK No. switching timing) Initial Setting : NO (without timing) ・This setting is common among WORK No. 1~4. Particulars NO (without timing) ・WORK No. switching will take effect immediately after WORK SELECT input condition has been changed. YES (with timing) ・The following timings will be interposed at the time of WORK No. switching. ①At the time of Front Panel RESET key input ②At the time of RESET terminal input ③At the time when COUNT OK lamp is turned off....
Page 24
24 KEY BZ VOL. (Buzzer Sound at Key Operation) Initial Value : 5 Setting Range : 0~5 ・This buzzer sounds to give operators power-on and/or key-in signals. 0: no sound 1: low-volume~5: high-volume ・This setting is common among WORK No. 1~4. ・Be sure to set to Level 5 when you use the low-tone buzzer. DISPLAY (LCD Display Selection) Select any of the following LCD display options to view under Operation Mode: Selections: Standard (initial setting) or Fas. time Standard ・Items on...
Page 25
25 AUTOMATIC SET UP (automatic setting) This Automatic Set Up function performs automatic pressure setting by utilizing the pressure variation obtained through Tool free running and practical fastening operation. (1)Tool Selection ①Select Tool you will use and press key. (2)Measurement of Pressure at Free Running ①Run your Tool for 2~3 seconds under no-load, and then release the lever. (Run your Tool with the socket and bit removed from Tool end.) ②The buzzer sounds...
Page 26
26 TIMER ①INITIAL. E [msec] (initial error detection timer) Initial Value : 0 Setting Range : 0~9999 (0 setting when you do not use this function) Functions ・Timer will start at the time when the pressure attained the preset fastening start pressure, and error will be detected when the preset shut-off pressure is attained before time-out. ・This is on-a-WORK No. basis setting. ②CYCLE. E. [msec] (cycle error detection timer) Initial Value : 0 Setting Range :...
Page 27
27 ⑤ON [msec] (ON Timer) Initial Value : 0 Setting Range : 0~9999 ・This is on-a-WORK No. basis setting. ⑥OFF [msec] (OFF Timer) Initial Value : 0 Setting Range : 0~9999 ・This is on-a-WORK No. basis setting. ⑦OK [msec] (Fastening OK Output Timer) Initial Value : 1000 Setting Range : 0~9999(Output will be held up to the next fastening start point in the case of 0 setting.) Functions ・This is fastening OK terminal’s output time ・Output will be turned OFF even before time-out...
Page 28
28 TERMINAL ALLOCATION(Terminal Block Input/Output Alternatives) (1) Choice among terminal block input alternatives ・Choose input signal alternatives for use in Input Terminal Block IN1~6. ・This setting is common among WORK No. 1~4. Initial Setting IN1:LS1 IN2:RESET IN3:NOK RESET IN4:QL IN5:WORK SELECT A IN6:WORK SELECT B Alternatives (Pick up 6 among the following alternatives) ●LS1 ●LS2 ●LS3 ●RESET ●NOK RESET ●QL ●PASS ●W.SEL.A...
Page 29
29 (1) Choice among terminal block output alternatives ・Choose output signal alternatives for use in Output Terminal Block OUT1~5. ・This setting is common among WORK No. 1~4. Initial Setting OUT1: COUNT OK OUT2: COUNT NOK OUT3:OK (Fastening OK) OUT4:NOK (Fastening NOK) OUT5:BUZZER ( Buzzer Output) Alternatives (Pick up 5 among the following alternatives) ● COUNT OK ●COUNT NOK ●OK ●NOK ●BUZZER ●WARNING ●W.1.C.OK ●W.2.C.OK ●W.3.C.OK ●W.4.C.OK ●CYCLE COUNT 1...
Page 30
30 WIRING DIAGNOSIS(Terminal Block Wiring Diagnosis) Wiring diagnosis will be performed through monitoring input status of external wires mated to UTM-1500 Input Terminal Block and through Output Terminal Block forced output. (1)Input Wiring Diagnosis ・○ indicate the absence of Terminal Block input ・● indicate the presence of Terminal Block input (2)Output Wiring Diagnosis ・Select any of the terminals by touching . The selected terminal will accompany “_“...