Aimco Brakes Monitor UEC4800TP Instruction Manual
Here you can view all the pages of manual Aimco Brakes Monitor UEC4800TP Instruction Manual. The Aimco Brakes manuals for Monitors are available online for free. You can easily download all the documents as PDF.
Page 71
2) Initial torque error UEC provides the error when the time from start torque to cut torque is shorter than the time of initial error detect timer. eSetting value` CInitial error detect select: 1 CInitial error detect timer : 1 – 9999 [msec] eHow to set` CDetermine the setting value by monitoring the time from start torque to cut torque of the correct fastening. 3) Cycle error UEC provides the error when the time from start torque to cut torque is longer than the time of...
Page 72
#Torque Sensor Wiring Check UEC makes torque sensor cable’s damage, break or short circuit. The error detection is made when ZERO/CAL check is in action. #Error detection NEZero check UEC checks how big the voltage of torque sensor will change from 0(V) under no load condition. UEC detects ZERO error if the voltage variation (DPM display zero point) becomes greater than 6% of CAL value. OECAL check UEC checks whether sensor setting value in UEC is appropriate to the...
Page 73
&Auto ZERO This is a function to do correct torque value measurement by doing automatic correction measured torque variation due to torque sensor’s ZERO point deviation. UEC memorizes ZERO point deviation confirmed by ZERO/CAL check, includes the deviation degree in torque sensor signal, and converts the adjusted torque signal to torque value. This auto ZERO will not function when ZERO/CAL error. Examples of AUTO ZERO 1) When ZERO/CAL check detects plus (+) side deviation....
Page 74
16Torque waveform measuring procedure Following explains how to measure the torque waveform by using the memory HiCORDER or memory scoop. 1) Make sure that the setting values are correctly set up, especially check if the connected torque sensor’s sensor specifications and the torque sensor setting value agree with appropriate CAL value. 2) Connect the waveform measurement equipment to the ANALOG OUTPUT terminal of UEC- 4800TP. Note) UK-PLUG’s...
Page 75
# ANALOG OUTPUT terminal UEC outputs the analog torque signal voltage in real time by having the torque sensor output signal voltage amplified by 1000 times, filtered and attenuated. 1) Torque sensor output voltage specification table Following is output voltage (x V) when rated load torque is applied to torque sensors. Output voltage changes per sensor specifications. Torque sensor specifications ANALOG output voltage ( x V) 480i 2000x10-6 DC 1.5V 700i 750x10-6...
Page 76
& Error Error message & contents ZERO Error When more than o6p deviation off from rated value is detected. CAL Error When more than 100o6p deviation off from rated value is detected Buffer Full Error This error is fired when more angle data to a buffer than the memory unit can accommodate is flowed into it (buffer overflow). The memory capacity is programmable on mode settings of “Waveform Memory Function Select”. Setting Error When not settable setting value is input....
Page 77
D/A Error When D/A of board is broken down or causes malfunction for some reasons. SUM Check Error When the setting data memorized in RAM have error. Blown Fuse 1) When the AC fuse (Refer to 4.2 Rear panel H) is blown, you cannot power on UEC. 2) When the DC24V fuse on the board inside UEC housing is blown, following phenomenon occurs. CTool does not shut off even if the torque reaches CUT torque. CTool’s lamp does not light.
Page 78
Error display screen When UEC detects the error that is not related to the fastening or maintenance, cause and the countermeasures can be displayed on the touch panel screen. 1) Touch the error message to move to the cause and countermeasure screen. It goes same on the WAVE FORM MONITOR screen and the TORQUE/ANGLE WAVE FORM MONITOR screen. 2) When UEC detects an error, keep touching on the monitor screen to move to the error and countermeasure...
Page 79
Recommended Action Error Recommended Action ZERO Error CAL Error CBe sure to set the sensor switch to the tool connected. CReplace the tool and sensor cable assembly. CGet the sensor values to agree with the EC tool connected. CCheck that the tool is running while the CAL checking is being made. If so, stop running the tool. Buffer Full Error CSet the setting of “Waveform memory function select to 4. Setting Error CCheck and correct the mode settings parameters...
Page 80
19. Networking The controller has several networking options available including Ethernet and hardwired field bus. All parameters pertaining to networking are configured in the web interface via its Ethernet . 19.1 Ethernet Each Ethernet connection can be configure d to communicate with most popular plant equipment including data collection servers, laptop software, and PLCs. Ethernet ports by default are set to an IP address of 10.10.30.150 and need to be changed before being put into...