Page 61
ADS XiLog+ System User Manual 55 7. Feed the battery cable f rom the new battery through the hole in the battery holder. 8. Place and properly position the battery into the holder. 9. Insert the battery holder back into the XiLog+, and secure it with the two screws. 10. Connect the battery cable to the circuit board . 11. Slide the circuit board into the rails inside the housing . 12. Place the yellow cover back onto the XiLog+ and into position. 13. Turn the yellow cover...
Page 63
ADS XiLog+ System User Manual 57 C H A P T E R 5 9 -Channel Connections Two options are available for wiring the outputs on the XiLog+ 9 : • NXG- 302 Expansion Box • NXG- 303 Bare Wire Cable NXG-302 Expansion Box ADS offers an expansion box for the wiring. Make connections based on the figures below. Seal any unused connectors on the box with a blank to prevent damage to the connection box.
Page 64
ADS XiLog+ System User Manual 58 Note: Each voltage input has a 2- , 5-, or 10- volt range, based on the position of the jumper next to the appropriate input. Verify the correct position. Selecting the wrong position could r esult in damage to the logger. NXG-303 Bare Wire Cable
Page 65
ADS XiLog+ System User Manual 59 R represents the following: V= 0 -2 volts; R=0Ω V= 0 -5 volts; R=69k8Ω , ±0.1%, 25ppm V= 0 -10 volts; R=187k Ω, ±0.1%, 25ppm
Page 67
ADS XiLog+ System User Manual 61 C H A P T E R 6 Appendices T his chapter contain s import ant instructional and referenc e information regarding the XiLog+ FastTrack software, meter scaling, battery life, and airfreight restrictions.
Page 68
ADS XiLog+ System User Manual 62 Appendix A: XiLog+ FastTrack Software The XiLog+ FastTrack software primarily is designed for expediting the process of programming the logger , viewing the current logger configuration, and testing the signal strength. Although the PrimeWorks configuration process is much more comprehensive, FastTrack represents an efficient and effective alternative for deploy ing and/or testing the logger quic kl y in the field. Note: The XiLog+ FastTrack...
Page 69
ADS XiLog+ System User Manual 63 Viewing the Current Configuration To view the current configuration programmed into the logger, click on the View button at the bottom of the XiLog+ FastTrack application window. Programming the Logger 1. Edit the name of the logger in the Site Name field, when necessary. 2. Edit the phone number (when applicable) in the Phone N umber field. 3. Designate the parameters under the Transmission header in the following way: Enter the time at which the...
Page 70
ADS XiLog+ System User Manual 64 Select the interval at which the data will be logged and averaged (as necessary) from the Interval drop-down list. Sending 5- or 10- minute data will require sending more than one SMS per channel per day. Choosing Off will prevent the channel from recording measurements. 5. Designate the parameters under the Pressure Channel 1 header in the following wa y: Select the unit of meas ure in which to log the data from the Units drop- down list. ...