BAS-SVX44A-EN41 Other Thermostat Functions Table 9. Remote humidity sensor: Current/voltage versus humidity System Lockout The thermostat can be locked out to prevent unauthorized personnel from changing settings. A lockout will disable changes to the following modes: System, Fan, Scheduling, Time, and TOV. If a change attempt is made, the lock icon ( ) will blink (1 Hz, 20/80%) for 10 seconds on the LCD display and then go solid again. To lock the thermostat: Simultaneously touch and hold both setpoint...
Page 42
42BAS-SVX44A-EN Temperature Cycle Control The heat and cool cycling rate, expressed in cycles per hour (CPH), indicates how often heating or cooling system is turned on when temperature is within the temperature differential from the setpoint (which is 1°F [0.5°C]). There are ten options (1–10) for heat stages and five options (1–5) for cool stages. The number selected is the maximum number of times the stage is cycled in 1 hour. For example, when the system is set to 5 CPH, it runs at 12-minute cycles...
Page 43
BAS-SVX44A-EN43 Temperature Cycle Control Figure 21. Auto heat and cool systems Figure 22. Auto 2/heat and 2/cool systems General Notes: The number of cooling or heating cycles are fixed according to CPH setting value. The duty cycle is varied during the cycling control. There are five (5) options for cooling CPH selection and ten (10) options for heating CPH selection. The cycles per hour for first-stage compressor (Option Number 0160) is used for the first stage of heat pump systems or the first...
Page 44
44BAS-SVX44A-EN Other Functional Components Figure 23. Auto 3/heat and 2/cool systems Other Functional Components This section provides additional information for understanding thermostat operation or programming. Some of the following sections refer to specific Option Numbers that are listed in Table 7, p. 24 . Sleep Mode Sleep mode places the CPU into a low powerstate when the thermostat is inactive. Note: Sleep mode is not implemented, but is noted here for future reference. Changeover Operation When...
Page 45
BAS-SVX44A-EN45 Other Functional Components Extension of Fan-on Time The system fan-on time is able to be extended for either or both cooling or heating mode. For cooling, the extension time is 90 seconds and for heating it is 40 seconds (refer to 0270 and 0271). Economizer/Time of Day (TOD) You can set the Economizer or TOD mode using Option Number #150 to one of two settings: Economizer Mode- TerminalAis energized with the thermostat in Occupied mode, Unoccupied mode with a call for cool, or a...
Page 46
BAS-SVX44A-EN46 Other Functional Components Temperature Display Offset The offset parameter appliesonlyto theLocal Temperature Display(when Configuration Option Number 0210 is set to 0, 1, or 2) or to theIndoor Remote Temperature Display(when Configuration Option Number 0210 is set to 3). Itdoes notapply to theOutdoor Remote Temperature Display(when Configuration Option Number 0210 is set to either 1 or 2). The offset range is -3°F to 3°F (-1.5°C to 1.5°C) [Refer to 0210 and 0260]. When Configuration...
Page 47
BAS-SVX44A-EN47 Other Functional Components permanent memory, the factory default preset parameters are used and are stored to permanent memory. The entire permanent memory data can be reset manually back to factory default data using Configuration Option Number 0300. Note:In instances where there is a loss of two (2) power cycles, the firmware limits the EEPROM write to five (5) writes of data for 24 hours. Thereafter, the EEPROM write capability is disabled. After 24 hours, the counter resets and...
Page 48
48BAS-SVX44A-EN Error Codes and Exceptions Error Codes Error codes indicate a possible need for technical assistance. Error codes display where the time of day is located. When an error occurs, the error code will blink first (for 3 seconds) and then blink the time of day (for 1 second) and back to the error code in 4-second intervals. During normal operation, the errors will be displayed in the following priority: E4 > E0 > E1 > E3 > E5 > E7; only the highest priority code will display. If there are...
Page 49
BAS-SVX44A-EN49 Error Codes and Exceptions Exceptions There are exceptions to be noted when using the thermostat.These exceptions are: If the indoor or outdoor temperature is lower or higher than the measuring range, the temperature display will blink either“--F”(Fahrenheit) or“--C”(Celsius) at 1.5 secondsONand 0.5 secondsOFF. All other outputs remain functional. Display range is -45°F to 199°F (-42.8°C to 92.8°C)) If the system fails to access EEPROM for 10 minutes, the system will blink withE3(3s=...
Page 50
50BAS-SVX44A-EN Troubleshooting Use the following table to diagnose and resolve problems. Table 12.Troubleshooting ProblemSolution Error code E0 - Thermistor error.• For configuration option #210 set to 1, 2, 3, or 4: Check the sensor terminals S1 and S2 for secure connection. If wires are securely connected, try replacing the sensor. If the error persists, have the thermostat serviced or replaced by a qualified Trane supplier. Error code E1 or “--” flashing in humidity display• Humidity reading is...