Home > Trane > Thermostat > Trane Touchscreen Programmable Thermostat User Manual

Trane Touchscreen Programmable Thermostat User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Touchscreen Programmable Thermostat User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							BAS-SVX44A-EN41
    Other Thermostat Functions
    Table 9. Remote humidity sensor: Current/voltage versus humidity
    System Lockout
    The thermostat can be locked out to prevent unauthorized personnel from changing settings. A
    lockout will disable changes to the following modes: System, Fan, Scheduling, Time, and TOV. If
    a change attempt is made, the lock icon ( ) will blink (1 Hz, 20/80%) for 10 seconds on the LCD
    display and then go solid again.
    To lock the thermostat:
     Simultaneously touch and hold both setpoint increment/decrement arrows for 4 seconds as shown below. When the mode is locked, the lock icon ( ) blinks (1 Hz, 20/80%) for 5 seconds
    and then goes solid.
    To unlock the thermostat:
     Simultaneously touch and hold both increment/decrement arrows for 4 seconds. When the mode is unlocked, the lock icon ( ) will disappear.
    Current (mA)VoltageRelative HumidityRange % (±)
    41 (Estimated)0 —
    4.8 1.2 (Estimated)5 —
    5.6 1.4 10 0.5
    7.2 1.8 20 0.5
    8 2 (Low Calibration Point) 25 0.5
    10.4 2.6 40 1.0
    12 3 50 1.0
    16 4 (High Calibration Point) 75 1.5
    18.4 4.6 90 1.5
    19.2 4.8 (Estimated) 95 —
    20 5 (Estimated) 100 —
    Lock System Icon Setpoint Arrows 
    Used to Lock/
    Unlock 
    Thermostat 
    						
    							42BAS-SVX44A-EN
    Temperature Cycle Control
    The heat and cool cycling rate, expressed in cycles per hour (CPH), indicates how often heating or
    cooling system is turned on when temperature is within the temperature differential from the
    setpoint (which is 1°F [0.5°C]). There are ten options (1–10) for heat stages and five options (1–5)
    for cool stages. The number selected is the maximum number of times the stage is cycled in 1 hour.
    For example, when the system is set to 5 CPH, it runs at 12-minute cycles with variable duty cycle.
    Depending on the heating or cooling load, which is measured by feedback from the sensor
    thermistor and/or temperature error, the system could run at 50% duty cycle (6 minutes ONand
    6 minutes OFF), 80% duty cycle (9.6 minutes ONand 2.4 minutes OFF), or other variations of the
    duty cycle.
    Note: The
     cycling rate described above is active only when the temperature is within the
    temperature differential. If the temperature is outside of the temperature, the heating and
    cooling equipment will either be fully ON or fully OFF accordingly.
    The following figures show cycling control and includes general notes, if applicable, about each type
     of cool or heat system.
    Important: There is a built-in compressor protection delay. The delay guarantees a minimum of
    5 minutes between compressor cycling ON/OFF. This built-in delay is added to a
    configurable
    
    additional delay of 0 to 5 minutes as setup in Option Number 0182. The
    minimum delay will be between 5 and 10 minutes .
    Figure 20. Heat only or cool only systems 
    						
    							BAS-SVX44A-EN43
    Temperature Cycle Control
    Figure 21. Auto heat and cool systems
    Figure 22. Auto 2/heat and 2/cool systems
    General Notes:
     The number of cooling or heating cycles are fixed according to CPH setting value.
     The duty cycle is varied during the cycling control.
     There are five (5) options for cooling CPH selection and ten (10) options for heating CPH
    selection.
     The cycles per hour for first-stage compressor (Option Number 0160) is used for the first stage of heat pump systems or the first cool stage of conventional systems.
    General Notes:
     The second-stage output increases the speed of cooling and heating.
     The algorithm of cycling control is the same as the first-stage output. However, the second-stageoutput has independent cycle period setting.
     All stages used the same temperature differential around setpoint for cycling control.
     When the system is set for 2H/1C HP, the cycles for auxiliary heat (Option Number 0164) is used for the second auxiliary heat stage. 
    						
    							44BAS-SVX44A-EN
    Other Functional Components
    Figure 23. Auto 3/heat and 2/cool systems
    Other Functional Components
    This section provides additional information for understanding thermostat operation or
    programming. Some of the following sections refer to specific Option Numbers that are listed in
    Table 7, p. 24 .
    Sleep Mode
    Sleep mode places the CPU into a low powerstate when the thermostat is inactive.
    Note: Sleep
     mode is not implemented, but is noted here for future reference.
    Changeover Operation
    When the system is set to AUTO Mode, the thermostat automatically selects Cool ModeorHeat
    Mode depending on the room temperature and the setpoint temperature. If the changeover setting
    is set to manual, then AUTO Modecannot be selected when selecting system type and the user
    would need to manually change between Cool and Heat Modes. (Refer to 0180)
    Changeover Valve Control
    The changeover valve control (reversing valve O/B) is used only with heat pump systems. Configuration Option Number 0153 determines whether the O/B signal is active for cooling or
    heating (default is O/B active for cooling).
    General Notes:
     The third auxiliary-stage heat output is only used for 3H/2C heat pump systems.
     The algorithm of cycling control is the same as the first-stage output. However, it has
    independent cycle period setting.
     Both the first and second stage use the same temperature differential around setpoint for cycling control.
     When the system is set for 3H/2C HP, the cycles for auxiliary heat (Option Number 0164) is used for the third auxiliary heat stage. 
    						
    							BAS-SVX44A-EN45
    Other Functional Components
    Extension of Fan-on Time
    The system fan-on time is able to be extended for either or both cooling or heating mode. For
    cooling, the extension time is 90 seconds and for heating it is 40 seconds (refer to 0270 and 0271).
    Economizer/Time of Day (TOD)
    You can set the Economizer or TOD mode using Option Number #150 to one of two settings:
    Economizer Mode- TerminalAis energized with the thermostat in Occupied mode,
    Unoccupied mode with a call for cool, or a Temporary Override mode (TOV) active.
    TOD Mode- TerminalAis energized with thermostat in Occupied mode or a Temporary
    Override mode (TOV) active.
    Note:TOD isnotavailable in non-programming mode.
    The table below summarizes the bulleted statements.
    Configuration, Time, and Programming Retention
    The thermostat retains the time and date for a minimum of 5 days of loss power. If power is lost
    for more than 5 days, the time and date will need to be restored when power is returned. All
    configuration settings, system settings, and scheduling are stored in non-volatile memory which
    will retain the data indefinitely with/without power
    Note:The user can manually reset the thermostat to all default settings by changing Configuration
    Option Number 0300 to 1.
    Heat/Cool Relay Confirmation
    As a guard against inadvertent relay switching, the thermostat firmware will set/reset the output
    relays every half hour if the relationship of setpoint versus temperature is out of range as follows:
     Auto systems with cool/heat setpoints: temperature is 5°F (2.5°C) above the cool setpoint or 5°F
    (2.5°C) below the heat setpoint
     Only heat systems: temperature is above or below the heat setpoint by 5°F (2.5°C)
     Only cool systems: temperature is above or below the cool setpoint by 5°F (2.5°C)
    Deadband
    The thermostat automatically maintains a temperature deadband between the heating setpoint
    and the cooling setpoint whenever the thermostat is configured for heat and cool– this applies to
    Auto or manual H/C setup. The temperature range of the deadband is 2°F to 9°F (1.0°C to 4.5°C) and
    is specified in the installation Configuration Option 0181 (see“Configuration Option Setup,” p. 23).
    If attempting to change a temperature setpoint to within the deadband of its opposing setpoint, the
    opposing setpoint will automatically be pushed to the next value that satisfies the deadband. Table 10. Operation summary
    OccupancyCall for CoolTerminal A (Programmable Mode)Terminal A (Non-programmable 
    Mode)
    EconomizerTODEconomizerTOD
    Occupied Don’t Care Energized Energized NA NA
    Unoccupied YES Energized De-energized Energized NA
    Unoccupied NO De-energized De-energized De-energized NA
    Temporary Override Don’t Care Energized Energized NA NA 
    						
    							BAS-SVX44A-EN46
    Other Functional Components
    Temperature Display Offset
    The offset parameter appliesonlyto theLocal Temperature Display(when Configuration Option
    Number 0210 is set to 0, 1, or 2) or to theIndoor Remote Temperature Display(when
    Configuration Option Number 0210 is set to 3). Itdoes notapply to theOutdoor Remote
    Temperature Display(when Configuration Option Number 0210 is set to either 1 or 2). The offset
    range is -3°F to 3°F (-1.5°C to 1.5°C) [Refer to 0210 and 0260]. When Configuration Option Number
    0210 is set to 4, the offset will apply after the average temperature is calculated from both the
    internal and remote temperature sensor. If one sensor goes bad, then the offset will apply to the
    remaining good temperature sensor reading.
    Humidity Display Offset
    Humidity offset allows adjustment of the humidity reading in the field. The offset range is -9% to
    9%. There is a separate humidity offset for the internal and external humidity sensor. (Refer to 0206,
    0207)
    LCD Backlight
    With Configuration Option Number 0170 set to 0 for Non-continuous Backlight, the backlight will
    turnONif any touch areas of the display screen are touched and turnOFFafter a timer expires.
    Note:When Configuration Option Number 0170 is set to 1, the backlight isONcontinuously with
    no time outs.
    Typical expiration times are:
     15 seconds fromHomescreen non-functional area touches (typically 20 seconds for a
    functional area touch plus an extra 15 seconds after returning toHomeorTOV Activescreens).
     60 seconds when inSchedule Change Mode,plus and extra 15 seconds after exiting.
     30 seconds inClean Screen Modeplus an extra 15 seconds after returning toHomeorTOV
    Activescreens.
     Backlight on during Power Up sequence plus an extra 15 seconds after arriving at theHome
    screen.
    ONcontinuously inConfiguration and Test Modes.
    Compressor Protection
    Compressor protection prevents damage to the compressor of either an air conditioning or heat
    pump system. Damage could occur if the compressor is restarted too soon after shutdown. This
    feature causes the compressor to delay between 0 to 10 minutes, depending on previous state of
    compressor (ONorOFF), and Configuration Option Number 0182.
    Note:The Heat/Cool algorithm will add anywhere from 0 to 5 minutes and Configuration Option
    Number 0182 can add an additional 0 to 5 minutes, depending on the setting.
    A time delay is activated after the compressor turnsOFF. During the delay (when there is a call for
    cool or heat pump heat), either Cool/ Heat indicator icons will blink on the LCD screen for a duration
    of 1.5 secondsONand 0.5 secondsOFF. When this time expires, eitherCool ModeorHeat Mode
    displays solid on the screen and the compressor turnsON.
    The delay timer is also activated upon initial startup and after power interruptions.
    Permanent Memory Data
    When setting up the thermostat, the schedule and configuration values are stored to permanent
    memory. These permanent values are restored each time at startup. If a Checksum error occurs in 
    						
    							BAS-SVX44A-EN47
    Other Functional Components
    permanent memory, the factory default preset parameters are used and are stored to permanent
    memory.
    The entire permanent memory data can be reset manually back to factory default data using
    Configuration Option Number 0300.
    Note:In instances where there is a loss of two (2) power cycles, the firmware limits the EEPROM
    write to five (5) writes of data for 24 hours. Thereafter, the EEPROM write capability is
    disabled. After 24 hours, the counter resets and allows five more 2-cycle power loss
    EEPROM writes for the next 24 hours.
    Compressor and Auxiliary Heat Lockout
    This function is available with only Configuration Option Number 0210 set to 2 and with one or both
    Configuration Option Numbers 0220 and 0221 set to some other setting except zero (0).
    Compressor and auxiliary heat is used for heat pump systems with more heat stages than cool
    stages. When the temperature from an outdoor sensor is:
     Above the auxiliary lockout point, only the compressor will operate on a call for heat.
     Below the compressor lockout point, only the auxiliary heat will operate on a call for heat.
     Between the compressor and auxiliary lockout points, the compressor and auxiliary heat will
    operate on a call for heat.
    There is a minimum 5°F (2.5°C) deadband between compressor and auxiliary heat lockout
    temperatures. Configuration option #220 sets the compressor lockout point; #221 sets the auxiliary
    lockout point. Refer to the following illustrations.
    Aux Lockout
    Temperature
    IPN 0221=0
    Compr Lockout
    Temperature
    IPN0220≠0
    A ux iliary  H eat O nly B oth C om pres s or H P
    and A uxiliary H eatO
    u
    t
    d
    o
    o
    r
     
    T
    e
    m
    p
    e
    r
    a
    t
    u
    r
    e
    15 to 45F (-9.5 to 7.0C)
    IP N0210 = 2 (H eat P um p O peration 
    w ith only C om pr Lockout )
    Aux Lockout
    Temperature
    IPN0221≠0
    Compr Lockout
    Temperature
    IPN 0220=0
    B oth C om pres s or H P
    and A uxiliary H eat Compressor HP Only
    O
    u
    t
    d
    o
    o
    r
     
    T
    e
    m
    p
    e
    r
    a
    t
    u
    r
    e
    40 to 60F (4.5 to 15.5C)
    IP N0210 = 2 (H eat P um p O peration 
    w ith only A ux Lockout)
    Aux Lockout
    Temperature
    IPN0221≠0
    Compr Lockout
    Temperature
    IPN0220≠0
    A ux iliary  H eat O nly B oth C om pres s or H P
    and A uxiliary H eat Compressor HP OnlyO
    u
    t
    d
    o
    o
    r
     
    T
    e
    m
    p
    e
    r
    a
    t
    u
    r
    e
    40 to 60F (4.5 to 15.5C)
    15 to 45F (-9.5 to 7.0C)
    IP N0210 = 2 (H eat P um p O peration 
    w ith C om pr and A ux Lockout )
    Both Compressor and Auxiliary
    Lockout Enabled
    Compressor Lockout Disabled
    and Auxiliary Lockout Enabled
    Compressor Lockout Enabled
    and Auxiliary Lockout Disabled 
    						
    							48BAS-SVX44A-EN
    Error Codes and Exceptions
    Error Codes
    Error codes indicate a possible need for technical assistance. Error codes display where the time
    of day is located. When an error occurs, the error code will blink first (for 3 seconds) and then blink
    the time of day (for 1 second) and back to the error code in 4-second intervals.
    During normal operation, the errors will be displayed in the following priority:
    E4 > E0 > E1 > E3 > E5 > E7; only the highest priority code will display. If there are multiple error
    codes, once the first code is cleared, the next code will display according to priority. The following
    table provides a list of codes and descriptions:
    Table 11.Error codes
    CodeDescription of Occurrence
    E0; Internal/External 
    Thermistor 
    (Refer to 0210)•0210= 0,1, or 2; Local internal thermistor resistance is less that 714 (209°F [98.3°C]) or greater than  
    561 k (-53.3°F [-47.5°C])
    •0210= 3; Remote external thermistor (S1, S2) resistance is less than 714 (209°F [98.3°C]) or greater than  
    561 k (-53.3°F [-47.5°C])
    •0210= 4; Either local or remote thermistor resistance is less than 714 (209°F [98.3°C]) or greater than  
    561 k (-53.3°F [-47.5°C])
    Note:When the thermistor used for control is out of range, then all Cool/Heat outputs turn OFF. The Fan AUTO mode turns 
    OFF the fan. The Fan ON mode will allow the fan to continue to run.
    Note:For Configuration Option Number 0210= 4 and only one of the thermistors is out of range, the firmware will bypass 
    averaging and only use the thermistor that is within an acceptable range to control Cool and Heat. When both thermistors 
    return to range, the temperature averaging resumes. E0 will flash if either is out of range.
    Note:For settings that use both internal/external thermistors, if the thermistor used for control is in range, then normal operation 
    should continue. However, EO should flash until the out-of-range thermistor is fixed.
    Note:For resistance >561 Ohms, tolerance is ±7%. For resistance 
    						
    							BAS-SVX44A-EN49
    Error Codes and Exceptions
    Exceptions
    There are exceptions to be noted when using the thermostat.These exceptions are:
     If the indoor or outdoor temperature is lower or higher than the measuring range, the
    temperature display will blink either“--F”(Fahrenheit) or“--C”(Celsius) at 1.5 secondsONand
    0.5 secondsOFF. All other outputs remain functional. Display range is -45°F to 199°F (-42.8°C
    to 92.8°C))
     If the system fails to access EEPROM for 10 minutes, the system will blink withE3(3s= Error
    Code and 1s= Time Display). However, it will continue to operate at its current mode (refer to
    the section,
    “Error Codes,” p.48).
     If any of the above exceptions listed should occur, the temperature control will continue to
    operate normally and all outputs remain functional.
     The humidity sensor error blinks 1.5 secondsONand 0.5 secondsOFFin the humidity reading
    area and blink Error Code E1 (3s= Error Code and 1s= Time Display). The humidity function will
    continue to operate for readings 0% to 100% for both internal/external humidity sensors.
    However, the humidity function will shut down for a communication error with the internal
    humidity sensor and with less that 4 mA for external humidity sensor. 
    						
    							50BAS-SVX44A-EN
    Troubleshooting
    Use the following table to diagnose and resolve problems.
    Table 12.Troubleshooting
    ProblemSolution
    Error code E0 - 
    Thermistor error.• For configuration option #210 set to 1, 2, 3, or 4: 
    Check the sensor terminals S1 and S2 for secure connection. If wires are securely connected, try replacing the 
    sensor. If the error persists, have the thermostat serviced or replaced by a qualified Trane supplier.
    Error code E1 or “--” 
    flashing in humidity 
    display• Humidity reading is outside of the measurable range or there is an error with the humidity sensor.
    • For internal humidity sensor, try a power cycle to see if the sensor recovers.
    • For external humidity sensor, check Hs and Hp terminals and/or ensure that the remote humidity sensor is not 
    damaged or malfunctioning. Replace if necessary.
    • If there is no recovery, have the thermostat serviced or replaced by a qualified Trane supplier.
    Error code E4 - Input 
    voltage out of range• Check the input voltage to the thermostat. It must be within the range of 18 Vac to 32 Vac RMS.
    Error codes E3 or E7 • Cycle the power to the thermostat. 
    • If it does not recover to normal operation, have it serviced or replaced by a qualified Trane supplier.
    Error code E5 - RTC 
    (Real Time Clock)• Set the clock from the Home screen.
    • Power cycle the unit.
    • If E5 remains, have the thermostat serviced or replaced by a qualified Trane supplier.
    Blank display • Check the power supply. 
    • If the power supply is ok, have the thermostat serviced or replaced by a qualified Trane supplier.
    Icons display missing or 
    only partially showing• Run Test #7 (refer to the section, “System Tests,” p. 20) to view odd, even, and full icon segment display.
    • Power cycle the thermostat.
    • If problem persists, have the thermostat serviced or replaced by a qualified Trane supplier.
    Erratic display 
    appearance or contrast• Check the power supply (24 Vac nominal) and frequency setting (Configuration Option Number 0170).
    • Cycle the power to the thermostat.
    • After verifying the power supply and frequency setting, have the thermostat serviced or replaced by a qualified 
    Trane supplier.
    Display screen does not 
    respond• Make sure the thermostat modes are not locked (refer to the section, “System Lockout,” p. 41).
    • Cycle the power to the thermostat.
    • Run Test #8 to confirm touch response.
    • If the screen is not locked and cycling the power do not solve the problem, have the thermostat serviced or replaced 
    by a qualified Trane supplier.
    “--F” or “--C” flashes • Temperature is outside of the measurable range. The temperature display should return when the temperature 
    is within the measurable range.
    • For Remote Temperature Reading; if temperature is within measurable range (refer to Table 11, p. 48) then check/
    replace the remote temperature sensor.
    • For Local Temperature Reading; if temperature is within measurable range, then have the thermostat serviced or 
    replaced by a qualified Trane supplier.
    Fan settings are not 
    visible• Check the system status. If the system is OFF, the fan settings will not appear.
    • Check the Configuration Option Numbers 0130 and 0151 to verify that the fan is enabled.
    Relays do not turn ON • Go to Test Modes 1–6 (refer to the section, “System Tests,” p. 20) to toggle the relay(s) in question. If the relay(s) 
    do not toggle in test mode, then have the thermostat serviced or replaced by a qualified Trane supplier. 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Touchscreen Programmable Thermostat User Manual