Home > Trane > Thermostat > Trane Touchscreen Programmable Thermostat User Manual

Trane Touchscreen Programmable Thermostat User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Trane Touchscreen Programmable Thermostat User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 12 Trane manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							BAS-SVX44A-EN21
    Power, System Tests, and Software Reset
    When exitingSystem Test Mode , the system will run a software reset and return to the
    Operating Home screen. If test 15=1, the software reset will be preceded by a Power-up Test
    (refer to Table6, p.22).
    Figure 17. Configuration button and system test mode display
    Configuration Button
    System Test Mode Display
    System 
    Test 
    Number Save and move to the next higher or 
    previous lower 
    System Test Number Increment or Decrement 
    the Test Value
    Save and move 
    to next higher
     
    System Test 
    Number
    Test 
    Value
    Test icon blinks 
    						
    							22BAS-SVX44A-EN
    Power, System Tests, and Software Reset
    Software Reset
    A watchdog timer recovers the system in the event of a software or hardware hang up or
    malfunction. The thermostat will reboot and run power-up tests if one of the following problems
    is detected:
     ExitingSystem Test Mode(power test only runs if test mode 15 is set to 1). The main variables are out of range during run time such as configuration data, active setpoint, RTC data,
    fan mode, or operation mode (EEPROM content is restored to default for this error detection).
     When three (3) cycles of power loss is detected and power returns. Any recoverable software hang up occurs due to hardware component or software bug.
    Table 6. System tests and statuses
    Test NumbersTest Value/Description
    1;
    Heat System (W, W2)• 0= Heat stages turn OFF
    • 1= Heat stage 1 turns ON and heat stage 2 turns OFF
    • 2= Heat stage 2 turns ON and heat stage 1 turns OFF
    • 3= Heat stage 1 and 2 turns ON
    2;
    Cool System (Y, Y2)• 0= Cool stages turn OFF
    • 1= Cool stage 1 turns ON and cool stage 2 turns OFF
    • 2= Cool stage 2 turns ON and cool stage 1 turns OFF
    • 3= Cool stage 1 and 2 turns ON
    3;
    Fan System (G)• 0= Fan turns OFF
    • 1= Fan turns ON
    4;
    Changeover Valve (O/B)• 0= Changeover valve turns OFF
    • 1= Changeover valve turns ON
    5;
    TOD/Economizer System (A)• 0= TOD/Economizer turns OFF
    • 1= TOD/Economizer turns ON
    6;
    Dehumidify Relay (Dh)• 0= Dh relay turns OFF
    • 1= Dh relay turns ON
    7;
    LCD Full Segment• 0= No action
    • 1= Odd segments turn ON, even segments turn OFF
    • 2= Even segments turn ON, odd segments turn OFF
    • 3= Full segment turns ON
    Note:User will have a 1-second delay to scroll to values 1, 2, and 3. Then, the selected segment test will run for 5 
    seconds.
    8;
    Touch Keys• 0= No action
    • 1= Test touch keys
    Note:Test value 1 will activate all touch areas on the display. The user can turn off each activated touch area, one at 
    a time, until all are turned off or touch Cancel to exit the test.
    9;
    Temperature for Outdoor/Remote, S1/S2 
    Sensor• 0= Display current temperature in Fahrenheit
    • 1= Display current temperature in Celsius
    10;
    Temperature for Internal Sensor• 0= Display current temperature in Fahrenheit
    • 1= Display current temperature in Celsius
    11;
    Humidity for External Hs/Hp Sensor• 0= Display current humidity setpoint
    • 1= Display current humidity
    12;
    Humidity for Internal Sensor• 0= Display current humidity setpoint
    • 1= Display current humidity
    13;
    Software Version• 0= No action
    • 1= Software revision number
    Note:Test value 1 displays the software revision number for 3 seconds and then returns to test mode.
    14;
    Filter
    • 0= No action
    • 1= Set filter countdown timer to zero (0) to display filter icon after exiting system test mode
    15;
    Run Power-up• 0= Power-up test OFF (power-up test will not run when exiting test mode)
    • 1= Power-up test ON (power-up test will run when exiting test mode)
    Note:The value 0 does not affect normal power-up. 
    						
    							BAS-SVX44A-EN23
    Configuration Option Setup
    This section provides information about changing system configurations. For reference,Table 7,
    p. 24, lists the Configuration Option Numbers, corresponding values, and descriptions.
    NOTICE
    Adverse Control System Behavior!
    Improper configuration setup could cause unwanted, possibly adverse control system behavior.
    Be sure to configure the thermostat according to your system type.
    To change the installation configuration: 1. Apply electrical power to the thermostat.
    2. Refer to Table7, p.24to determine the correct configuration options. For convenience, either
    print out this table or write down the selections and other notes listed.
    3. Activate Configuration
     Option Setupmode by:
    WARNING
    Live Electrical Components!
    The circuit board is energized. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform this step. Failure to follow
    all electrical safety precautions when exposed to live electrical components could result in death
    or serious injury.
    a. Removing the thermostat cover as shown in the section, “Mounting the Backplate,” p.10.
    b. Pressing and holding the Configurationbutton
     for 3 seconds. The configuration wrench
    icon displays solid along with the configuration option number and value (refer to
    Figure 18below).
    Figure 18. Configuration button and configuration mode display
    Note: Configuration
     mode automatically ends if no buttons are pressed for 10 minutes.
    4. Next, press the center or(as shown) to increment or decrement the Option
     Number.
    Note:Changing the Option Number with the up/down arrows will also Save the Option Value. In addition,
    the OK will increment the Option Number and Save the Option Value.
    5. Press the right side or(as shown) to increment or decrement the Option Value.
    6. To Savesettings,
     exitConfiguration Mode and return to theHomescreen:
    Push the configuration button momentarily as shown in Figure 18
     Touch and hold for 2 seconds
     A 10-minute time out after the last touch in Configuration Mode
    Configuration
    Button
    Option 
    Number Option 
    Value
    Save to move to the next 
    higher or previous lower 
    Option Number
    Increment or Decrement 
    the Option ValueSave and move to 
    next higher 
    Option Number 
    or hold for 2 
    seconds to save 
    and exit 
    Configuration 
    Mode 
    						
    							24BAS-SVX44A-EN
    Configuration Option Setup
    Installation OptionsTable 7. Installer configuration setup menuOpt.
    No.
    Name
    Def
    Values/Descriptions
    Notes
    0100
    Te m p e r a t u r e  i n d i c a t i o n /
    Resolution 0 • 0= °F, 1 degree resolution
    • 1= °F, 0.5 degree resolution
    • 2= °C, 1 degree resolution • 3= °C with 0.5 degree resolution
    • 4= °C with 0.1 degree resolution
    This setting affects indoor temperature display and setpoint display 
    resolutions. Outdoor temperature display area is always ±1 resolution 
    for both F and C. Refer to Option 0210.
    0110
    Clock Format
    12 • 12= 12-hour clock • 24= 24-hour clock
    0120
    Year11 • 11–99 Available year range: 2011–2099. This va
    lue is updated to the real time 
    clock after setting. Day of the  week is updated automatically.
    0121
    Month 1 • 1–12 This value is updated to the real time
     clock after setting. Day of the week 
    is updated automatically.
    0122
    Day 1 • 1–31 Month dependent: this value is upda
    ted to the real time clock after 
    setting. Day of the week is updated automatically.
    0125
    Daylight Savings 2 • 0= Disabled
    • 1= US (1987), changeover at 2:00am
    • 2= US (2007), changeover at  2:00am • 3= Europe, changeover at 1:00am
    • 4= Manual, changeover at 2:00am
    0126
    0127
    0128
    0129
    • Spring Ahead Month
    • Spring Ahead Day
    •Fall Back Month
    •Fall Back Day
    •03
    •01
    •11
    •01• 01-12
    • 01-31
    • 01-12
    • 01-31 Options available only if 0125 is set to 4.
    0130
    System Selection
    8 • 1= 1H/1C (Conv) 1st Stage Heat 
    (W), 1st Stage Comp (Y), Fan (G)
    • 2= 1H/1C (HP) 1st Stage Comp (Y),  Changeover (O/B), Fan (G)
    • 3= 1H (Conv) 1st Stage Heat (W),  without fan
    • 4= 1H (Conv) 1st Stage Heat (W),  Fa n  ( G )
    • 5= 1C (Conv) 1st Stage Comp (Y),  Fa n  ( G )
    • 6= 2H/1C (HP) 1st Stage Comp (Y),  Changeover (O/B), Auxiliary Heat 
    (W1), Fan (G) • 7= 2H/2C (Conv) 1st & 2nd Stage 
    Heat (W,W2), 1st & 2nd Stage Comp 
    (Y,Y2), Fan (G)
    • 8= 2H/1C (Conv) 1st & 2nd Stage  Heat (W,W2), 1st Stage Comp (Y), 
    Fa n  ( G )
    • 9= 1H/2C (Conv) 1st Stage Heat  (W), 1st & 2nd Stage Comp (Y,Y2), 
    Fa n  ( G )
    • 10= 2H/2C (HP) 1st & 2nd Stage  Comp (Y,Y2), Changeover (O/B), Fan 
    (G)
    • 11= 3H/2C (HP) 1st & 2nd Stage  Comp (Y,Y2), Changeover (O/B), 
    Auxiliary Heat (W1), Fan (G)
    0140
    Schedule Options 1 0=Non-programmable 1= Programmable
    0150
    TOD/Economizer Output 
    (Terminal A)0 • 0= Unused
    •1= TOD energizes terminal  A during 
    occupied period, not during 
    unoccupied period. • 2= Economizer energizes terminal 
    A 
    during a call for cool. TOD is not available in Non-programmable Mode. (Refer to Option 0140)
    0151
    Heat Fan Operation
    0 0= System controls fan 1= Thermostat controls fanOnly shown for conventional system wi
    th heat stages and fan capability. 
    For heat pump, the fan relay operates with thermostat control.
    0153
    Reversing Value O/B 0 0= O/B ON when call for cool 1= O/B ON when call for heat Only shown for heat pump systems.
    0160
    Cycles Per Hour (CPH) 
    [First Stage Compressor]3 1–5
    Only for systems with cool or HP stage. (Refer to Option 0130.) Selection 
    in this stage changes 2nd stage cool default CPH.
    0161
    CPH (Second Stage 
    Compressor)3 1–5
    Only for systems with 2-cool or HP stages. (Refer to Option 0130.) 
    						
    							25
    0162
    CPH (First Stage 
    Conventional Heat)5 1–10
    Only for conventional systems with heat stages. (Refer to Option 0130.) 
    Selection in this stage changes default CPH of 2nd stage heat.
    0163
    CPH (Second Stage 
    Conventional Heat)9 1–10
    Only for conventional systems with two stages of conventional heat.
    0164
    CPH for Auxiliary Heat 9 1–10 Only shown for 2H/1C HP or 3H/2C HP systems. (Refer to Option 0130.)
    0165
    CPH for Emergency Heat 9 1–10Only shown for 2H/1C HP or 3H/2C HP systems. (Refer to Option 0130.)
    0170
    Continuous Backlight
    0 0= Backlight ON time is limited 1= Backlight ON continuously
    0180
    Changeover 1 0= Manual 1= AutoOnly for systems with both heat and cool stages. (Refer to Option 0130.)
    0181
    Deadband
    3 • 2= 2°F (1°C)
    •3= 3°F (1.5°C)
    •4= 4°F (2.0°C)
    •5= 5°F (2.5°C) •6= 6°F (3.0°C)
    •7= 7°F (3.5°C)
    •8= 8°F (4.0°C)
    •9= 9°F (4.5°C) Only applies to auto or manual changeover systems. (Refer to Option 
    0180.)
    0182
    Minimum Compressor Off 
    Time
    5 • 0= 0 minutes
    • 1= 1 minute
    • 2= 2 minutes • 3= 3 minutes
    • 4= 4 minutes
    • 5= 5 minutes Only for systems with cool stage or heat pump. (Refer to Option 0130.) 
    This setting will extend the compressor 
    OFF time beyond any other 
    delays incorporated in the Heat/Cool software algorithm.
    0190
    Power Supply Frequency 0 0= 60 Hz 1= 50 HzPower supply input is 24 Vac nominal at either 60 Hz or 50 Hz.
    0200
    Dehumidify Sensor 
    Selection1 • 0= Humidity display and function is 
    disabled
    •1= Internal humidity sensor  enabled 2= External humidity sensor enabled
    For external humidity control, a 4–20 mA humidity sensor must be 
    connected to the Hp and Hs terminals to avoid error code 
    E1.
    0205
    Dehumidification Control 0 0= Active Control 1= Passive ControlActive control toggles Dh output terminal 
    ON and  OFF as specified by 
    the dehumidify algorithm and is used with a device having its own 
    dehumidification equipment. Passive co ntrol runs cool mode for up to 1 
    extra minute whenever there is a call for cool and dehumidification.
    0206
    Internal Humidity Offset 
    Adjustment 0 -9% to 9% in 1% increments
    Allows adjustment of the internal relative humidity reading to account 
    for accuracy, tolerance, and potential 
    drift. FW should use the adjusted 
    value for display and humidity control.
    0207
    External Humidity Offset 
    Adjustment 0 -9% to 9% in 1% increments
    Allows adjustment of the external relative humidity reading to account 
    for accuracy, tolerance, and potential 
    drift. FW should use the adjusted 
    value for display and humidity control.
    0210
    Temperature Sensor 
    Selection  0 • 0= Internal sensor only (10k)
    • 1= Internal sensor for H/C control (outdoor for display only) [10k]
    • 2= internal sensor for H/C control  (outdoor for Compr/Aux lockout 
    control([10k] • 3= Remote indoor sensor for H/C 
    control (10k)
    • 4= Use average temperature =  (local+S1/S2)/2 for H/C control. Setting 2 applies only to HP systems and is disabled on all conventional 
    systems. 
    For setting 1, 2, or 4; if either temp
    erature sensor is out of range, then 
    the  E0 error code will display.
    0220
    Heat Pump Compressor 
    Lockout Point 0•0= None
    • 15= 15°F (–9.5°C)
    • 20= 20°F (–6.5°C)
    • 25= 25°F (–4.0°C) • 30= 30°F (–1.0°C)
    • 35= 35°F (1.5°C)
    • 40= 40°F (4.5°C)
    • 45= 45°F (7.0°C) Only for heat pump systems with more
     heat stages than cool stages and 
    remote outdoor control sensor. (Refer to Option 0130 and Option 0210.) 
    Note: A 5°F (2.5°C) deadband between heat pump and auxiliary 
    lockout will be enforced.
    0221
    Heat Pump Auxiliary 
    Lockout Point 0•0= None
    • 40= 40°F (4.5°C)
    • 45= 45°F (7.0°C) • 50= 50°F (10.0°C)
    • 55= 55°F (13.0°C)
    • 60= 60°F (15.5°C) Only for heat pump systems with more
     heat stages than cool stages and 
    remote outdoor control sensor. (Refer to Option 0130 and Option 0210.) 
    Note: A 5°F (2.5°C) deadband between heat pump and compressor 
    lockout will be enforced.
    0230
    Temporary Override 
    Duration Limit 3•0= zero hours
    • 1= one hour
    • 2= two hours • 3= three hours
    • 4= four hours
    Used for temporary override (TOV) starting duration time. Setting of 
    zero 
    does not disable TOV.
    Table 7. Installer configuration setup menu (continued)Opt.
    No.
    Name
    Def
    Values/Descriptions
    Notes 
    						
    							26BAS-SV X44A-EN
    Configuration Option Setup
    0231
    Starting Default Number 
    of Periods2 2= two periods 4= four periods
    Provides starting default number of periods for all days of the week.
    0232
    Starting Default Period 
    Occ/Unocc Definitions4
    If option #0231 is set to 2
     Day— Night
    •0= UnOcc— UnOcc
    •1= UnOcc— Occ
    •2= UnOcc— UnOcc
    •3= UnOcc— Occ
    •4= Occ— UnOcc
    •5= Occ— Occ
    •6= Occ— UnOcc
    •7= Occ— Occ
    •8= UnOcc— UnOcc
    •9= UnOcc— Occ
    • 10= UnOcc— UnOcc
    • 11= UnOcc— Occ
    • 12= Occ—UnOcc
    • 13= Occ—Occ
    • 14= Occ—UnOcc
    • 15= Occ—Occ If option #0231 is set to 4
      Morn—
    Day—Evening— Night
    •0= UnOcc— UnOcc—UnOcc— Unocc
    •1= UnOcc— UnOcc—Unocc— Occ
    •2= UnOcc— UnOcc—Occ— UnOcc
    •3= UnOcc— Unocc—Occ— Occ
    •4= UnOcc— Occ—UnOcc— UnOcc
    •5= UnOcc— Occ—UnOcc— Occ
    •6= UnOcc— Occ—Occ— UnOcc
    •7= UnOcc— Occ—Occ— Occ
    •8= Occ— UnOcc—UnOcc— UnOcc
    •9= Occ— UnOcc—UnOcc— Occ
    • 10= Occ— UnOcc—Occ— UnOcc
    • 11= Occ— UnOcc—Occ— Occ
    • 12= Occ— Occ—UnOcc— UnOcc
    • 13= Occ— Occ—UnOcc— Occ
    • 14= Occ— Occ—Occ— UnOcc
    • 15= Occ— Occ—Occ— Occ Occupancy setting can be changed during scheduling for each period/
    day.
    0233
    Days Options for 
    Scheduling Mode
    3 • 0= 1 day; Mo-Su all days share the 
    same schedule
    • 1= 5+1+1 days; Mo-Fr share a  schedule. Sa and Su each have an 
    independent schedule • 2= 5+2 days; Mo-Fr share a 
    schedule. Sa-Su share a schedule.
    • 3= 7 days; Each day has an  independent schedule Any value toggle of Option 0233 will reset the schedule to the default 
    values of Options 0231 and 0232, and in addition, return the schedule 
    to default values.
    0240
    Heat Temperature Range  90 40–90; 40°F to 90°F
    4–32; 4°C to 32°COnly for systems with heat stage. (Refer to Option 0130.)
    0241
    Cool Temperature Range  50 50–99; 50°F to 99°F
    10–37; 10°C to 37°COnly for systems with cool stage. (Refer to Option 0130.)
    0260
    Te m p e r a t u r e  D i s p l a y  
    Offset0 • –3= –3°F (–1.5°C)
    • –2= –2°F (–1.0°C)
    • –1= –1°F (–0.5°C)
    •0= None •1= 1°F (0.5°C)
    •2= 2°F (1.0°C)
    •3= 3°F (1.5°C)
    Only applies to control temperature and display temperature for internal 
    and indoor remote sensor. Does not apply to outdoor temperature for 
    display.
    0270
    Extended Fan-on Time 
    Heat
    0 0= OFF 90= ninety seconds
    This option is not available if Option 0151=0 or if system is cool only. 
    (Refer to Option 0130.)
    0271
    Extended Fan-on Time 
    Cool0 0= OFF 40= forty seconds
    This option is not available for systems with heat only. (Refer to Option 
    0130.)
    0275
    Filter Change Indicator 1 • 0= OFF
    • 1= 30 days
    • 3= 90 days • 4= 120 days
    • 6= 180 days
    • 12= 365 days Filter change disabled in 
    OFF. Timer values start on first power-up or 
    reset of an active filter change icon.
    0300
    Restore Factory Defaults 0 0= No 1= YesNo= No action; Yes= Resets all parameters to default except calendar/
    daylight savings time/system selection.
    Table 7. Installer configuration setup menu (continued)Opt.
    No.
    Name
    Def
    Values/Descriptions
    Notes 
    						
    							BAS-SVX44A-EN27
    Operation
    If configured properly, the touch-screen programmable thermostat will control HVAC equipment
    to maintain room temperature automatically. This section provides general descriptive and
    procedural information intended for daily operation.
    Thermostat Icon Descriptions
    The illustration below provides a description of all icons for the thermostat. Bubbled letters in red
    correspond to the letters indicated in each section title.
    Note: In
    normal operations, not all icons are visible.
    Figure 19. Icon descriptions
    Mo Tu We Tu Fr
    Days of the week
    (Mo–Fr shown selected
    Sa and Su shown unselected)
    Confirm
    Screen 
    cleaning
    timer Setpoint display
    from top clockwise: 
    
    
    
    
    Heat indicator,
    Cool indicator
    Outdoor temperature/
    humidity display 
    from top to 
    bottom:
     in Fahrenheit/Celsius
    
     
    Top clockwise:
    
    
    
    From left:
    
    
    From left:
     
    
    
    
     From top to bottom:
     Fahrenheit/Celsius
     (morning/day/
    evening/night)
     
     
    
    AB
    C
    D
    E
    F
    GH
    I
    J 
    						
    							28BAS-SVX44A-EN
    Functions
    There are common functions on the programmable thermostat that require initial setting or
    changing. This section describes the following setup modes:
     Time setup, dehumidify setup, and system mode setup
     Fan mode and temporary override (TOV) mode
     Schedule setup
     Table of default settings and worksheet
    Note: The
     touch screen can be locked out to prevent unauthorized personnel from changing
    settings. A lockout will disable changes to System, Fan, Scheduling, Time and TOV. If the lock
    icon ( ) is displayed on the LCD screen, the user will need to unlock the touch screen to
    allow changes (refer to the section, “System Lockout,” p.41).
    Time Setup
    To set or change the time:
    1. From the Homescreen,
     touchto activate the Time Setting Mode. The LCD screen displays
    hours:minutes (with the hours blinking to indicate it is selected) and either AM or PM (AM/PM
    is
     not shown for 24-hour clock) as shown:
    Note: To
    change clock to either 12-hour or 24-hour readout, refer to Option Number 0110 in
    Table7, p.24).
    2. Touch either orto switch between hours or minutes.
    3. Touch orto increment or decrement the hours/minutes. Touch and hold either
    button for more than 1 second to fast scroll through values.
    4. Touch to save and exit Time
     Setting Mode.
    Note: A
    20-second time out will also save and exit Time Setting Mode.
    5. Touch to exit without saving any changes.
    Dehumidify Setup
    Note:This function is displayed only for systems configured with dehumidify enabled. (Refer to
    Configuration Option Number 0200).
    To set or change dehumidification: 1. Touch to activate theDehumidify
     Setting Mode. The LCD screen displays the current
    humidity setpoint with adjustment arrows.
    2. Touch orto increment or decrement the humidity setpoint by 1% increments. Touch
    and hold either button for more than 1 second to fast scroll through values.
    Note: Dehumidification
     setpoint can be adjusted from 30% to 80%.
    3. Touch to save and exit Dehumidify
     Setting Mode.
    Note: A
    20-second time out will also save and exit Dehumidify Setting Mode.
    4. Touch to exit without saving any changes.
    DEFIJ
    DEF 
    						
    							BAS-SVX44A-EN29
    Functions
    System Mode Setup
    Note:If unable to change the system mode to a desired setting, check the system type setting and
    the manual/auto-changeover setting (refer to the section, “Configuration Option Setup,”
    p. 23) to verify how the thermostat is configured with heat and cool modes, and that it
    permits manually changing them. (Refer to Configuration Option Numbers 0130 and 0180).
    Depending upon the model and system type, the thermostat can be set to one of five modes:
    Cooling, Heating,Emergency
    
    Heat,AUTO ,orOFF .
    Note: All
    system icons may not be available– this is configuration setup dependent.
    To set the system mode: 1. Touch area to activate theSystem
     Mode Setup. All system mode settings available
    are visible with the current system setting blinking. Each touch in the system selection box will
    step
     to the next available setting as shown below.
    2. Choose a system mode and then either touch or a 20-second time out will save the system
    mode setting and return to the Homescreen.
    Note: Touching
     another active area on the display screen (such as clean screen, clock,
    humidity, or schedule) will also save the system mode setting selected in Step 2 and
    activate the newly selected system setting.
    Touching Cancel() will exit system mode setup without saving any changes
    .
    Fan Mode
    Note: The fan is only displayed on systems configured with the fan enabled. If disabled, then the
    fan icon on the LCD screen is not visible. The Fan mode is typically configured in Schedule
    Setup. Fan mode changes from the Home screen initiates an override (TOV) [refer to the
    section, “Schedule Setup,” p. 31].
    There are two fan modes. Each are indicated by an icon on the display:
    To
    
    enter fan mode:
    1. Touch area to activate the Fan
     Display Modeand the active fan mode will blink.
    Note: Touching ,, another active area, or a 20-second time out will return to the Home
    screen without making changes to the fan.
    EFG
    Cooling Mode; cools the room to bring it down to the cooling setpoint. 
    Heating Mode; heats the room to bring it up to the heating setpoint. 
    Emergency Heat Mode; heats the room using the emergency heat mode equipment.
    AUTO Mode; switches automatically between heating and cooling modes as required. OFF Mode; turns  OFF both heat and cool modes regardless of the room temperature.  OFF 
    mode also disables the fan relay.
    Emergency
    Heat Cool Auto H/C Off
    HeatOFF
    EFG
    Fan AUTO Mode; turns the fan ON and 
    OFF as needed according to equipment configuration.
    Fan ON Mode;  runs the fan continuously. 
    						
    							30BAS-SVX44A-EN
    Functions
    2. Next, touch in the fan selection box to put the thermostat intoTOV Temporary Override
    Mode and to step to the next available setting as shown below.
    3. Refer to the next section, Temporary
     Override (TOV) Setupto set overrides or touch to
    cancel and return to the Homescreen.
    Temporary Override (TOV) Setup
    TOV allows the user to temporarily override the scheduled temperature setpoint and/or fan
    settings. There are two ways to enter TOV Mode from the Home screen:
     Quick
    TOV : Touch the Occ ( ) or Unocc () icon from the Home screen. A TOV session will
    start up using the last occupied schedule setpoint settings, the last occupied fan setting, and the
    default
     TOV time period (Option Number 0230). Touch OKor wait for a 20-second time out to
    put the thermostat into quick TOV Active Mode;OR
     User
    Configurable TOV : Touch either the Up or Down arrow to blink the setpointfor 20 seconds.
    Touch of the Up or Down arrows within 20 seconds to change the setpoint and put the thermostat into TOV Setpoint Change Mode; OR
    Touch the Fan to blink the present Fan setting for 20 seconds. Touch the Fan area within 20 seconds
     to change the Fan setting and put the thermostat into TOV Setpoint Change Mode.
    In TOV
    Setpoint Change Mode , further adjustments can be made to the setpoint or Fan mode
    with the Up, Down, or Fan areas.
    Note: For
     Auto H/C systems, use the cool mode icon ( ) or the heat mode icon () to toggle
    between cool and heat setpoints respectively.
     To adjust the TOV time period: Touch
    the clock icon ( ) to enter TOV Time Setup Mode. The left/right arrow ( or )
    will toggle between Days/Hours and the middle Up/Down arrows ( or ) will
    increment or decrement the time.
    Note: A
    second touch of the clock icon ( ) will put the thermostat intoHold Mode
    which holds the TOV settings indefinitely until canceled by the user. Additional
    touches
     of the clock icon ( ) will toggle the thermostat between DAYS/HOURS
    and Hold .
     Toggle
    back to readjust the setpoint(s) by touching the thermometer icon ( ).
    Touch area to activate the desired settings. Active TOV is indicated by a solid non-blinking
    hourglass ( ).
    Note: Desired
     settings are also activated after a 20-second time out.
     Cancel the
     TOV time period, touch at any time to cancel and exit TOV Mode.
    General Notes:
     TOV setup has three modes:TOV Setpoint Setup,TOV Time Setup, andTOV Active.
     If Fan is enabled, then TOV Fan setting can be changed in either TOV
     Setpoint ModeorTOV
    Time Setting Mode.
     If a TOV is in active status, then those TOV settings become the starting setpoints if entering into a
     new User Configurable TOV session.
     Fan icons do not display on the LCD screen if the system is not configured for fans.
     The confirm icon is not displayed when the user is in TOV
     Active Mode.
    On Mode:
    Arrows Flash
    Auto Mode:
    Auto Flashes
    BCEFG 
    						
    All Trane manuals Comments (0)

    Related Manuals for Trane Touchscreen Programmable Thermostat User Manual