Page 31
31RTAA-IOM-3 Additional Location Requirements for Remote Evaporator Only The remote evaporator must be installed indoors, unless: – ambient temperatures are always above 32 F. – the system circulating liquid is a non- freezing glycol-type solution, selected for the prevailing ambient temperatures. – the evaporator is protected from freezing by properly installed and applied insulation and heat tape. Caution: To prevent internal damage due to freezing, do not install the outdoor unit without adequate...
Page 32
32RTAA-IOM-3 Rigging The Model RTAA chiller should be moved by lifting. Refer to Figures 14 thru 17 for typical unit lifting and operating weights. Refer to the rigging diagram that ships with each unit for specific “per unit” weight data. WARNING: To prevent injury or death and unit damage, capacity of lifting equipment must exceed unit lifting weight by an adequate safety factor. Lifting Procedure Caution: To prevent damage do not use a forklift to lift the unit. [ ] Install clevis connectors through...
Page 33
33RTAA-IOM-3 Figure 14 Rigging and Lifting Weights for RTAA Packaged Unit NOTES: 1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH. ADJUST TO KEEP UNIT LEVEL WHILE LIFTING. 2. DO NOT FORK LIFT UNIT. 3. WEIGHTS ARE TYPICAL FOR UNITS WITH R-22 CHARGE. 4. DEDUCT 740 FROM TOTAL WEIGHT FOR UNITS WITHOUT ARCHITECTURAL LOUVER PANELS.130-200 Tons without Domestic Water Heater NOTES: 1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH. ADJUST TO KEEP UNIT LEVEL WHILE LIFTING. 2. DO NOT FORK LIFT UNIT. 3....
Page 34
34RTAA-IOM-3 Figure 15 Rigging and Lifting Weights for RTAA Packaged Unit – 240-300 Tons NOTES: 1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH. ADJUST TO KEEP UNIT LEVEL WHILE LIFTING. 2. DO NOT FORK LIFT UNIT. 3. WEIGHTS ARE TYPICAL FOR UNITS WITH R-22 CHARGE. 4. DEDUCT 1166 FROM TOTAL WEIGHT FOR UNITS WITHOUT ARCHITECTURAL LOUVER PANELS. NOTES: 1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH. ADJUST TO KEEP UNIT LEVEL WHILE LIFTING. 2. DO NOT FORK LIFT UNIT. 3. WEIGHTS ARE TYPICAL FOR...
Page 35
35RTAA-IOM-3 Figure 17 Rigging and Lifting Weights for RTAA Outdoor Unit with Remote Evaporator Option NOTES: 1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH. ADJUST TO KEEP UNIT LEVEL WHILE LIFTING. 2. DO NOT FORK LIFT UNIT. 3. WEIGHTS ARE TYPICAL FOR UNITS WITH R-22 CHARGE. 4. DEDUCT 740 FROM TOTAL WEIGHT FOR UNITS WITHOUT ARCHITECTURAL LOUVER PANELS.
Page 36
36RTAA-IOM-3 Unit Isolation and Leveling For additional reduction of sound and vibration, use one of the two mounting methods outlined below: 1. Construct an isolated concrete pad for the unit or provide concrete footings at each of the eight unit mounting points. Mount the unit directly to the concrete pads or footings. Level the unit using the base rail as a reference. The unit must be level within 1/4 over the entire length. Use shims as necessary to level the unit. 2. Install the optional spring...
Page 37
37 RTAA-IOM-3 RTAA-SA-2000B Figure 18 Spring Isolator Placement for Typical RTAA Packaged Unit – 130 to 200 Tons without Domestic Water Heater
Page 38
38 RTAA-IOM-3 RTAA-SA-2002C Figure 19 Spring Isolator Placement for Typical RTAA Packaged Unit – 240-400 Tons
Page 39
39 RTAA-IOM-3 RTAA-SA-2003A Figure 20 Spring Isolator Placement for Typical RTAA Outdoor Unit with Remote Evaporator Option
Page 40
40 RTAA-IOM-3 RTAA-SA-2008A Figure 21 Spring Isolator Placement for Typical RTAA Unit with Heat Recovery Domestic Water Heater