Additional Location Requirements
for Remote Evaporator Only
The remote evaporator must be
installed indoors, unless:
– ambient temperatures are always
above 32 F.
– the system circulating liquid is a non-
freezing glycol-type solution, selected
for the prevailing ambient
temperatures.
– the evaporator is protected from
freezing by properly installed and
applied insulation and heat tape.
Caution: To prevent internal
damage due to freezing, do not
install the outdoor unit without
adequate...

Page 32

32RTAA-IOM-3
Rigging
The Model RTAA chiller should be
moved by lifting. Refer to Figures 14
thru 17 for typical unit lifting and
operating weights. Refer to the rigging
diagram that ships with each unit for
specific “per unit” weight data.
WARNING: To prevent injury or
death and unit damage, capacity
of lifting equipment must exceed
unit lifting weight by an
adequate safety factor.
Lifting Procedure
Caution: To prevent damage do not use
a forklift to lift the unit.
[ ] Install clevis connectors through...

Page 33

33RTAA-IOM-3
Figure 14
Rigging and Lifting Weights for
RTAA Packaged Unit
NOTES:
1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH. ADJUST TO
KEEP UNIT LEVEL WHILE LIFTING.
2. DO NOT FORK LIFT UNIT.
3. WEIGHTS ARE TYPICAL FOR UNITS WITH R-22 CHARGE.
4. DEDUCT 740 FROM TOTAL WEIGHT FOR UNITS WITHOUT
ARCHITECTURAL LOUVER PANELS.130-200 Tons
without Domestic Water Heater
NOTES:
1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH. ADJUST TO
KEEP UNIT LEVEL WHILE LIFTING.
2. DO NOT FORK LIFT UNIT.
3....

Page 34

34RTAA-IOM-3
Figure 15
Rigging and Lifting Weights for
RTAA Packaged Unit – 240-300 Tons
NOTES:
1. LIFTING CHAINS (CABLES) WILL NOT BE THE SAME LENGTH.
ADJUST TO KEEP UNIT LEVEL WHILE LIFTING.
2. DO NOT FORK LIFT UNIT.
3. WEIGHTS ARE TYPICAL FOR UNITS WITH R-22 CHARGE.
4. DEDUCT 1166 FROM TOTAL WEIGHT FOR UNITS WITHOUT
ARCHITECTURAL LOUVER PANELS.
NOTES:
1. LIFTING CHAINS (CABLES) WILL NOT BE
THE SAME LENGTH. ADJUST TO KEEP
UNIT LEVEL WHILE LIFTING.
2. DO NOT FORK LIFT UNIT.
3. WEIGHTS ARE TYPICAL FOR...

Page 35

35RTAA-IOM-3
Figure 17
Rigging and Lifting Weights for
RTAA Outdoor Unit with
Remote Evaporator Option
NOTES:
1. LIFTING CHAINS (CABLES) WILL NOT BE
THE SAME LENGTH. ADJUST TO KEEP
UNIT LEVEL WHILE LIFTING.
2. DO NOT FORK LIFT UNIT.
3. WEIGHTS ARE TYPICAL FOR UNITS
WITH R-22 CHARGE.
4. DEDUCT 740 FROM TOTAL WEIGHT FOR
UNITS WITHOUT ARCHITECTURAL
LOUVER PANELS. 

Page 36

36RTAA-IOM-3
Unit Isolation and
Leveling
For additional reduction of sound and
vibration, use one of the two mounting
methods outlined below:
1. Construct an isolated concrete pad
for the unit or provide concrete
footings at each of the eight unit
mounting points. Mount the unit
directly to the concrete pads or
footings. Level the unit using the
base rail as a reference. The unit
must be level within 1/4 over the
entire length. Use shims as
necessary to level the unit.
2. Install the optional spring...

Page 37

37
RTAA-IOM-3
RTAA-SA-2000B
Figure 18 
Spring Isolator Placement for
Typical RTAA Packaged Unit – 130 to 200 Tons 
without Domestic Water Heater 

Page 38

38
RTAA-IOM-3
RTAA-SA-2002C
Figure 19 
Spring Isolator Placement for
Typical RTAA Packaged Unit – 240-400 Tons 

Page 39

39
RTAA-IOM-3
RTAA-SA-2003A
Figure 20 
Spring Isolator Placement for
Typical RTAA Outdoor Unit with 
Remote Evaporator Option 

Page 40

40
RTAA-IOM-3
RTAA-SA-2008A
Figure 21 
Spring Isolator Placement for 
Typical RTAA Unit with Heat Recovery 
Domestic Water Heater 