Trane Rtaaiom3 Manual
Here you can view all the pages of manual Trane Rtaaiom3 Manual. The Trane manuals for Cooler are available online for free. You can easily download all the documents as PDF.
Page 11
11RTAA-IOM-3 Figure 1 Typical RTAA Packaged Unit 130 - 200 Ton (Front/Side Exterior View) Condenser Coils Connection Access for Control Voltage and InterlocksStarter and Power Panel Nameplate Control PanelLine Voltage Connection Access
Page 12
12RTAA-IOM-3 Figure 2 Typical RTAA Packaged Unit 130 - 200 Ton (Rear/Side Exterior View) Chilled Water OutletChilled Water Inlet
Page 13
13RTAA-IOM-3 Figure 3 Typical RTAA Packaged Unit 240-400 Tons Control PanelEvaporator Outlet Inlet
Page 14
14RTAA-IOM-3 Figure 4 Typical RTAA Unit (Rear Exterior View) Condenser Fans/Motors Condenser Liquid Line Filter Electronic Expansion Valves Liquid Line Filter Condenser
Page 15
15RTAA-IOM-3 Figure 5 Typical RTAA Unit (with Remote Evaporator Option) (Rear Exterior View) Condenser Fans/Motors Circuit #1Condenser Fans/Motors Circuit #2 Condenser Circuit #1Condenser Circuit #2 Circuit #1 Field Refrigerant Piping ConnectionsCircuit #2 Field Refrigerant Piping Connections
Page 16
16RTAA-IOM-3 Table 1 General RTAA Mechanical Specifications Size130 140 155 170 185 200Compressor Quantity 2 2 2 2 2 2 Nominal Size(1)(Tons) 70/70 70/70 85/70 100/70 100/85 100/100 Evaporator Water Storage (Gallons) 49 46 73 69 62 61 (Liters) 184 175 277 261 234 231 Min. Flow (GPM) 156 156 186 186 222 222 (L/Sec) 9.8 9.8 11.7 11.7 14.0 14.0 Max. Flow (GPM) 504 504 612 612 720 720 (L/Sec) 31.8 31.8 38.6 38.6 45.4 45.4 Condenser Oty of Coils 4 4 4 4 4 4 Coil Length (In) 214/214 214/214 240/214 240/214...
Page 17
17RTAA-IOM-3 Table 1 (Continued from previous page) General RTAA Mechanical Specifications Size240 270 300 340 370 400Compressor Quantity (1) 2/1 1-1/1 2/1 2/2 1-1/2 2/2 Nominal Size (1)(Tons) 70/100 100-70/100 100/100 70/100 100-70/100 100/100 Evaporator Water Storage (Gallons) 151 143 135 124 116 108 (Liters) 572 523 511 470 439 407 Min. Flow (GPM) 288 288 288 408 408 408 (L/Sec) 18.2 18.2 18.2 25.7 25.7 25.7 Max. Flow (GPM) 1080 1080 1080 1440 1440 1440 (L/Sec) 68.1 68.1 68.1 90.8 90.8 90.8 Condenser...
Page 18
18RTAA-IOM-3 Figure 6 Remote Evaporator Refrigerant Suction Line Circuit #1Refrigerant Suction Line Circuit #2 Entering Chilled Water Temp. SensorsLeaving Chilled Water Temperature Sensor Evaporator Refrigerant Temperature Sensors Electronic Expansion Valve Sight Glass Filter/Dryer Terminal Box Refrigerant Liquid Line Circuit #1
Page 19
19RTAA-IOM-3 RTAA Model Circuit/Tons Compressor/Tons130 1 70 A 70 270 B70 140 1 70 A 70 270 B70 155 1 85 A 85 270 B70 170 1 100 A 100 270 B70 185 1 100 A 100 285 B85 200 1 100 A 1012 100 B 100 RTAA Model Circuit/Tons Compressor/Tons240 1 140 A 70 B70 2 100 C 100 270 1 170 A 100 B70 2 100 C 100 300 1 200 A 100 B 100 2 100 C 100 340 1 140 A 70 B70 2 200 C 100 D 100 370 1 170 A 100 B70 2 200 C 100 D 100 400 1 200 A 100 B 100 2 200 C 100 D 100 Table 2 RTAA Refrigerant Circuit Designations and Capacities...
Page 20
20RTAA-IOM-3 Warnings and Cautions Warnings and Cautions appear in boldface type at appropriate points in this manual. Warnings are provided to alert personnel to potential hazards that can result in personal injury or death; they do not replace the manufacturer’s recommendations. Cautions alert personnel to conditions that could result in equipment damage. Your personal safety and reliable operation of this machine depend upon strict observance of these precautions. The Trane Company assumes noliability...