Page 21
Introduction Related Documents/Media Strata DK I&M 5/99xix ©Keyprint 2000 User Guide provides instructions for the Keyprint 2000 software printing package which allows you to print and store custom button label keystrips for Strata DK 2000- series 10-button or 20-button digital telephones, 20-button add-on modules, and 60-button digital DSS consoles. ©Strata DK Programming Manual provides all instructions necessary to program the system and system record sheets, including ACD. ©Strata DK...
Page 22
Introduction Related Documents/Media xxStrata DK I&M 5/99 ©Insight DK CD-ROM which includes Insight DK software, the upgrade to Insight DK Plus, Demo software, Insight DK documentation and training modules. ©Insight DK Installation Guide explains how to set up the network, install the server software, install clients and explains how the data files are organized. ©Insight DK Supervisor Guide provides instructions for using the Strata DK Insight and Insight DK Plus MIS for the Supervisor of a call...
Page 23
Strata DK I&M 5/991-1 DK14 InstallationDK14 Installation1 This chapter explains how to install the Strata DK14 system. It includes information on site requirements, wiring diagrams, and step-by-step instructions on how to install the unit(s), the ground wiring, AC power cabling, reserve power (battery backup) cabling, and PCB cabling. Inspection 1. When the system is received, examine all packages carefully and note any visible damage. If any damage is found, do not open the packages. Contact the...
Page 24
DK14 Installation Site Requirements 1-2Strata DK I&M 5/99 Input Power The system requires an input power source of 115VAC ± 10VAC, 50/60 Hz, 10 amps. The AC outlet is recommended to be dedicated and unswitched, with a solid third-wire ground. (See “AC Power and Grounding Requirements” on Page 1-3 for details). This is to eliminate interference from branch circuit motor noise or the like, and to prevent accidental power-off. To avoid accidental power turn-off, Toshiba recommends that you do not use...
Page 25
DK14 Installation AC Power and Grounding Requirements Strata DK I&M 5/991-3 DK14 Installation AC Power and Grounding Requirements The DK14 requires a solid earth ground for proper operation. The AC power cord contains a conductor for the “third-wire ground” provided by the commercial power outlet. The third-wire ground should be the only ground necessary for the DK14; this ground must originate at the buildings main power distribution panel and have a solid connection to earth ground. (See...
Page 26
DK14 Installation AC Power and Grounding Requirements 1-4Strata DK I&M 5/99 AC Power and Third-wire Ground Test Test the “third-wire ground” for continuity by either measuring the resistance between the third prong terminal (earth ground) and a metal cold water pipe (maximum: 1 ohm), or by using a commercially available earth ground indicator. If neither procedure is possible, perform the following earth ground test procedure. äTo perform the earth ground test procedure 1. Obtain a suitable...
Page 27
DK14 Installation KSU Mounting Considerations Strata DK I&M 5/991-5 DK14 InstallationKSU Mounting Considerations The KSU is designed to be mounted on a wall or other vertical surface. Toshiba recommends using the following method. Pre-installation 1. Loosen the screws on the front cover of the KSU, and remove the cover (Figure 1-3). 2. Move the SW1 RAM Storage Battery jumper plug strap on the motherboard to the ON position (Figure 1-4). 3. If the DK14 is less than one mile from the central office...
Page 28
DK14 Installation KSU Mounting Considerations 1-6Strata DK I&M 5/99 Mounting the KSU 1. Make sure the power supply switch is turned OFF. 2. Place the KSU on the desired location on the mounting surface and mark the location of the four screw holes (there is one on each corner). See Figures 1-3 and 1-5. 3. Make sure the location of the KSU meets the minimum clearance requirements. 4. Drill holes on these marks. 5. Secure screws approximately two thirds of the way into the top two holes on the...
Page 29
DK14 Installation Reserve Power Battery Strata DK I&M 5/991-7 DK14 Installation Reserve Power Battery A second HPFB can be installed directly above the unit to supply backup reserve power. äTo install the Reserve Power Battery and Charger (HPFB) 1. Place the HPFB directly above the DK14 KSU (Figure 1-7). 2. Mark the location of the two screw holes, then drill holes. 3. Screw the two screws two-thirds into the mounting surface. 4. Hang the HFPU on the screws then tighten the screws into the mounting...
Page 30
DK14 Installation Power Supply Removal and Replacement 1-8Strata DK I&M 5/99 8. Dress and tie-wrap the HPFB cables. 9. To mount a second HPFB, repeat Steps 1~4, then plug the second HPFB connector in the first HPFB and connect an FG wire between each HPFB FG screw. 10. To test the HPFB, remove the DK14 AC plug from the AC outlet. The DK14 AC LED will go out, but the DK14 DC LED remains on. Also the system remains in normal working order and the HPFB 24V LED remains on. 11. If it is desired to turn...