    When the [Centrally 
    controlled] message 
    is displayed  Being centrally controlled, operation is not 
    possible. 
    Blackout?
      After recovery from blackout, press  
    again.
      àIf operation does not start, turn off the circuit 
    breaker and consult the dealer of purchase 
    about the symptom and Model No.
    Is the circuit breaker 
    turned off?   Turn it on and press  again.   àIf operation does not start, turn off the circuit 
    breaker and consult the dealer of purchase 
    about the symptom and Model No.
    Is [Assigning] 
    blinking?   After blinking stops, press  again.  àIf operation does not start, turn off the circuit 
    breaker and consult the dealer of purchase 
    about the symptom and Model No.
    Is [] displayed?
    Alarm indication (e.g.)
    Defective indoor unit No.
      If any of the following alarm indications 
    appears, stop operation once and restart 
    approx. 1 minute later.
    (Alarm indication, off)
    [•E04  •E06  •P10  •P20  •H06]
      àIf the indication does not reappear, use the unit.
      àIf the indication reappears or an alarm 
    indication other than the above (combination of 
    numbers and characters such as E, F, H, L and 
    P) appears, stop operation, turn off the circuit 
    breaker and consult the dealer of purchase 
    about alarm indication, Model No. and indoor 
    unit No.
    Cannot stop the 
    operation.
    Or the unit starts to 
    run automatically 
    even if 
     (Off) button 
    is pressed.
      Check if the outing function is activated or not. 
    (
    )
      Check control by central control device.
    •  If you need to contact for servicing, check the back cover of the operating instructions for indoor 
    units or outdoor units.
    Troubleshooting
    If operation does not start by pressing ...
    Check the following before asking for repair. 
    						
    							42(EN)
    Model No.CZ-RTC3
    Dimensions (H) 120 mm x (W) 120 mm x (D) 16 mm
    Weight 180 g
    Temperature/
    Humidity range 0 ˚C to 40 ˚C / 20 % to 80 % (No condensation)
    *Indoor use only.
    Power Source DC16 V (supplied from indoor unit)
    Clock Precision
    ± 30 seconds/month (at normal temperature 25 
    ˚C) 
    *Adjust periodically.
    Holding 
    time 72 hours (When fully charged)
    *Approx. 8 hours are required for full charge.
    Number of 
    connected indoor 
    units Up to 8 units
    Specifi
     cations