Page 81
8-2. Trouble Diagnosis by Error Monitor Lamps 8-2-1. Location of the Error Monitor Lamps Remove the top plate of outdoor unit and the cover of Electrical Component Box. The Power Lamp and Error Monitor Lamps are located on the P.C.Board of Electrical Component Box. (Fig.1) 8-2-2. Display of the Error Monitor Lamps If a protective device has activated or there is a sensor failure in the outdoor unit, the 4 error monitor lamps on the outdoor control circuit board will indicate the nature of the...
Page 82
8-3-1. Checking the outdoor unit 8-3. Checking the Outdoor System 8-3-2. Checking the defrost operation Work procedure Apply 220 V AC between terminals L1 and L2 on the outdoor unit terminal plate. • Short-circuit the T-RUN terminal to the COM terminal of TEST/T-RUN terminals. •The LED (red) on the control board must illuminate. • The compressor, fan motor, 4-way valve, and solenoid valve (for the hot gas bypass) must turn ON. (They turn ON about (70) seconds later after the power is turned ON.)...
Page 83
8-4. Trouble Diagnosis of Each Part 8-4-1. Problems of Each Part and Inspection Points For details about the inspection points, refer to the Inspection Points for Each Part. Problems Inspection pointsIndoor unit Indoor unit does not operate. Self-Diagnostics check Indoor controller (control unit) Indoor fan motor Room temperature sensor Heat exchanger temperature sensor Inter-unit cable Switch circuit board Outdoor control circuit board Diode module HIC Electrolytic capacitor Fuse Compressor...
Page 84
Problems Inspection pointsIndoor unit Indoor unit does not operate. Breaker Refrigerant gas pressure(9) (10) Operation lamp blinking. Operation lamp does not illuminate. Indoor fan dose not turn. Outdoor unit does not operate. Outdoor fan dose not turn. 4-way valve does not operate. The compressor (only) does not operate. The compressor stops on occasion. The compressor speed does not increase. The outdoor air temperature is high, however defrost operation occurs. Defrost operation does not occur. The...
Page 85
No voltage on circuit board (7) Electric expansion valve When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions. Labels are applied to the valve body and coil, corresponding to the connector colors, to identify them. Controller check Voltage varies 0 ohm No temperature change Temperature changes Replace the coil. Open and close the electric expansion valve by hand to check it. Replace the electric expansion valve.This part is normal. Check...
Page 86
(8) Branch tubing temperature sensor Check that the sensor is securely contained in the thermostat holder. (9) Breaker Check whether or not the breaker has been tripped. Check that the breakers and fuses used are of the specified capacity. Check that the breaker and its line are exclusive for A/C use. (10) Refrigerant gas pressure Start a COOL test run, and messure the temperatures of the A/C intake air and discharge air. Compare the values with the performance charts. If the values are higher than the...
Page 87
8-5. Trouble Diagnosis of Fan Motor This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil resistance, and the following procedure should be used to check the motor. Perform the trouble diagnosis by Test Run mode described on Installation Instructions of indoor unit. [Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble [Trouble symptom 2] The fan motor does not rotate when the outdoor unit is...
Page 88
9. REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 9-1. Characteristics of New Refrigerant R410A 9-1-1. What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22. 9-1-2. Components (mixing proportions) HFC32 (50%) / HFC125 (50%) 9-1-3. Characteristics Less toxic, more chemically stable refrigerant The...
Page 89
Tubing precautions Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily cover the ends of the tubing with caps or tape prior to installation. Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since air conditioners with R410A are subject to higher pressure than those using R22 and R407C. No addition of compressor oil for R410A No additional charge of compressor oil is permitted. No...
Page 90
9-3. Tools Specifically for R410A For servicing, use the following tools for R410A Gauge manifold Charging hose Gas leak detector Refrigerant cylinder Charging cylinder Refrigerant recovery unit Vacuum pump with anti-reverse flow (*1) (Solenoid valve-installed type, which prevents oil from flowing back into the unit when the power is off, is recommended.) Vacuum pump (*2)...can be used if the following adapter is attached. Vacuum pump adapter (reverse-flow prevention adapter) (*3). (Solenoid...