Panasonic Cu 3ke19nbucu Technical Service Manual
Here you can view all the pages of manual Panasonic Cu 3ke19nbucu Technical Service Manual. The Panasonic manuals for Air Conditioner are available online for free. You can easily download all the documents as PDF.
Page 91
9-5. In Case of Compressor Malfunction CAUTIONShould the compressor malfunction, be sure to make the switch to a replacement compressor as quickly as possible. Use only the tools indicated exclusively for R410A. See "9-3. Tools Specifically for R410A." 9-5-1. Procedure for Replacing Compressor (1) Recovering refrigerant Any remaining refrigerant inside the unit should not be released to the atmosphere, but recovered using the refrigerant recovery unit for R410A. Do not reuse the...
Page 92
Valve Single valve Charge liquid refrigerant with cylinder in up-side-down position. Single valve (with siphon tube) Charge with cylinder in normal position.Liquid Valve Liquid Charging cylinder Open Refrigerant cylinder Liquid NO! CAUTIONNever charge a large amount of liquid refrigerant at once to the unit. This may cause damage to the compressor. CAUTIONTo prevent the composition of R410A from changing, never bleed the refrigerant gas into the atmosphere while transferring the refrigerant....
Page 93
Length of tubing Evacuation timeLess than 33 ft. (10 m) More than 10 minutesMore than 33 ft. (10 m) More than 15 minutes 9-6. In Case Refrigerant is Leaking CAUTIONNever attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant. (1) Detecting Leaks Use the detector for R410A to locate refrigerant leak points. (2) Recovering refrigerant Never release the...
Page 94
9-7. Charging Additional Refrigerant 9-7-1. When Tubes are Extended Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came with the indoor unit. Charge additional refrigerant in liquid state only. 9-8. Retro-Fitting Existing Systems 9-8-1. Use of Existing Units Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to operate improperly and may result in a hazardous condition. 9-8-2. Use of...
Page 96
INSTALLATION INSTRUCTIONS CU-3KE19NBU CU-4KE24NBU CU-4KE31NBU (852-6-4190-584-00-2) APPENDIX A A-1
Page 97
For Outdoor Unit This air conditioner uses the refrigerant R410A. External diameter of service port R410A: 5/16" Split System Air Conditioner 85264190584002 2011 CV6233187853 INSTALLATION INSTRUCTIONS NOTE Contents Page IMPORTANT! Please Read Before Starting..................................2 1. GENERAL..........................................................4 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of...
Page 98
IMPORTANT! Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close...
Page 100
4 1-2. Accessories Supplied with Unit Table 1 1-3. Optional Copper Tubing Kit Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop. 1-4. Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source, you will need: 1. Deoxidized annealed copper tube for refrigerant tub- ing as detailed in...