Page 51

Outdoor Unit  : CU-3KE19NBU
Indoor Unit  : CS-MKE12NB4U × 3
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
1.
Rating conditions (#) 
:  Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB
:  Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling operation...

Page 52

Outdoor Unit  : CU-4KE24NBU
Indoor Unit  : CS-MKE9NKU × 3
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
1.
Rating conditions (#) 
:  Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB
:  Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling operation...

Page 53

Outdoor Unit  : CU-4KE24NBU
Indoor Unit  : CS-KE18NB4UW + CS-MKE12NB4U + CS-MKE12NB4U
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
1.
Rating conditions (#) 
:  Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB
:  Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection...

Page 54

Outdoor Unit  : CU-4KE31NBU
Indoor Unit  : CS-MKE9NKU × 4
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
1.
Rating conditions (#) 
:  Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB
:  Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling operation...

Page 55

Outdoor Unit  : CU-4KE31NBU
Indoor Unit  : CS-MKE9NB4U × 4
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
1.
Rating conditions (#) 
:  Indoor Unit Entering Air Temp. 80 °F (26.7 °C) DB / 67 °F (19.4 °C) WB
:  Outdoor Ambient Temp. 95 °F (35 °C) DB
2.
3. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling operation...

Page 56

Outdoor Unit  : CU-3KE19NBU
Indoor Unit  : CS-MKE9NKU × 3
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
5-3.  Cooling Capacity (Low Ambient)
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
NOTE
1.
2. Above data represents the value when the operation frequency of a compressor is fixed.Above data does not take Freeze Prevention Protection during cooling operation into account.
For this reason, the value may vary from the actual cooling...

Page 57

Outdoor Unit  : CU-3KE19NBU
Indoor Unit  : CS-MKE12NB4U × 3
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
NOTE
 RATING CAPACITY:    17,400 BTU/h       AIR FLOW RATE: 706 CFM
INDOOROUTDOOR
 ENT. TEMP. 
oF (oC)     AMBIENT TEMP. oF (oC)
W B DB 15 25 35 45 55
(-9.4) (-3.9) (1.7) (7.2) (12.8)
TC 17,850 17,720 17,690 17,750 17,600
72 (22.2) SHC 15,590 17,720 15,590 15,590 15,450
59 76 (24.4) SHC 17,850...

Page 58

Outdoor Unit  : CU-4KE24NBU
Indoor Unit  : CS-MKE9NKU × 3
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
NOTE
 RATING CAPACITY:    23,200 BTU/h       AIR FLOW RATE: 777 CFM
INDOOR OUTDOOR
 ENT. TEMP. 
oF (oC)     AMBIENT TEMP. oF (oC)
W B DB 15 25 35 45 55
(-9.4) (-3.9) (1.7) (7.2) (12.8)
TC 23,390 23,310 23,350 23,510 23,420
72 (22.2) SHC 18,350 23,310 18,350 18,350 18,350
59 76 (24.4) SHC 20,910...

Page 59

Outdoor Unit  : CU-4KE24NBU
Indoor Unit  : CS-KE18NB4UW + CS-MKE12NB4U + CS-MKE12NB4U
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
NOTE
 RATING CAPACITY:    22,000 BTU/h       AIR FLOW RATE: 812 CFM
INDOOROUTDOOR
 ENT. TEMP. 
oF (oC)     AMBIENT TEMP. oF (oC)
W B DB 15 25 35 45 55
(-9.4) (-3.9) (1.7) (7.2) (12.8)
TC 22,260 22,160 22,190 22,350 22,240
72 (22.2) SHC 18,570 22,160 18,570 18,570 18,570
59...

Page 60

Outdoor Unit  : CU-4KE31NBU
Indoor Unit  : CS-MKE9NKU × 4
Power Supply  :  230V Single Phase 60Hz
< Cooling Capacity (Low Ambient) >
TC : Total Cooling Capacity (BTU/h)   SHC : Sensible Heat Capacity (BTU/h)
NOTE
 RATING CAPACITY:    30,600 BTU/h       AIR FLOW RATE: 1,036 CFM
INDOOROUTDOOR
 ENT. TEMP. 
oF (oC)     AMBIENT TEMP. oF (oC)
W B DB 15 25 35 45 55
(-9.4) (-3.9) (1.7) (7.2) (12.8)
TC 30,870 30,760 30,800 31,010 30,890
72 (22.2) SHC 24,260 30,760 24,260 24,260 24,260
59 76 (24.4) SHC 27,890...