Page 21
8.2. Cooling Operation • Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C to 30°C. • During cooling operation, the compressor will stop running and restart as shown in below figure. 8.2.1. Cooling Operation Time Diagram 21 CS-W7DKR CU-W7DKR / CS-W9DKR...
Page 22
8.3.1. Soft Dry Operation Time Diagram 8.3. Soft Dry Operation • Soft Dry operation can be set using remote control. • Soft Dry operation is applied to dehumidify and toperform a gentle cooling to the room. • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control. • W hen operation begins, Soft Dry will be switched“ON”for a maximum 10 minutes, then Soft Dry operation will be turned“OFF” for a minimum 6 minutes. After that, the Soft Dry...
Page 23
8.4. Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 25 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard. • Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting temperature as shown in below table. • Operation mode will be determine again...
Page 24
• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the circuit of JX1 at indoor electronic controller. 8.5. Operation Control (For 8.5.1 to 8.5.7 information appliesonly toCooling and Soft Dry Operation) 8.5.1. Restart Control (Time Delay Safety Control) • W hen the thermo-off temperature (temperature which compressor stops to operate) is reached during:- − Cooling operation - the compressor stops for 3 minutes (minimum) before resume...
Page 25
8.5.4. Anti-Freezing Control • If the temperature of the indoor heat exchan ger falls below 2°C continuously for 4 minutes or more, the compressor turnsoff. The fan speed setting remains the same. • This phenomenon is to protect the indoor heat exchan gerfrom freezing and to prevent higher volume of refrigerant in liquidform returning to the compressor. • Compressor will restart again when the indoor heat exchan ger temperature rises to 10°C (Recovery). • Restart control (Time Delay Safety Control)...
Page 26
(For 8.5.8 to 8.5.16 information appliesonly toHeating Operation) 8.5.8. Restart Control (Time Delay Safety Control) • W hen the thermo-off temperature (temperature which compressor stops to operate) is reached during:- − Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. • If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation stop, although the unit is turn on again within the period. •...
Page 27
8.5.11. Overload Protection Control Outdoor Fan Control • If the temperature of the indoor heat exchan ger rises to 51°C, outdoor fan stops. The outdoor fan restarts when the indoor heat exchan ger temperature falls to 49°C. Compressor high pressure protection • If the indoor heat exchan ger becomes 65°C or more, the compressor will stop and restart automatically. (Time Delay Safety Control - 4minutes waiting). • This is to reduce the pressure, as to reduce the indoor heat exchan ger temp....
Page 28
8.5.15. Anti ColdDraft Control • This operation is to prevent the Cold Draft during Heating mode operation. • The operation will start when compressor OFF (Thermo OFF) during Heating operation. • For the first 30 sec. from compressor OFF (Thermo OFF), Indoor fan speed will operate accordingly to the Indoor heat exchan ger temperature as shown below: • After 30 sec. from compressor OFF (thermo OFF), Indoor fan will run atSSLo speed only. • Anti Cold Draft Control will stop when: − Intake temperature...
Page 29
Normal Deicing Time Diagram Overload Deicing Time Diagram 29 CS-W7DKR CU-W7DKR / CS-W9DKR CU-W9DKR / CS-W12DKR CU- W12DKR
Page 30
8.6. Indoor Fan Speed Control • Indoor Fan Speed can be set using remote control. 8.6.1. Fan Speed Rotation Chart Fan Speed (rpm)CS-W7DKRCS-W9DKRCS-W12DKR SHi122013101310 Hi107011601280 Me9409801120 HLo840840960 CLo780780880 Lo-750750850 SLo700700750 SS Lo300300300 QSHi112012101210 QHi97010601180 QMe8408801020 QHLo770770890 QLo680680780 8.6.2. Automatic Fan Speed Control • W hen set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table. − Fan speed...