    							13.2. Relationship Between The Condition Of The Air Conditioner And
    Pressure And Electric Current
    Cooling ModeHeating Mode
    Condition of the air
    conditonerLow PressureHigh PressureElectric current
    during operationLow PressureHigh PressureElectric current
    during operation
    Insufficient refrigerant
    (gas leakage)
    Clogged capillary tube
    or Strainer
    Short circuit in the
    indoor unit
    Heat radiation
    deficiency of the
    outdoor unit
    Inefficient compression
     • 
    Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
    13.3. Diagnosis Methods Of A Malfunction Of A Compressor And 4-way
    Valve
    Nature of faultSymptom
     • 
    Electric current during operation becomes approximately 20% lower than the normal value.
    Insufficient compressing of a compressor • 
    The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
     • 
    The difference between high pressure and low pressure becomes almost zero.
     • 
    Electric current reaches a high level abnormally, and the value exceeds the limit of an
    ammeter. In some cases, a breaker turns off.
    Locked compressor
     • 
    The compressor is a humming sound.
     • 
    Electric current during operation becomes approximately 80% lower than the normal value.
    Insufficient switches of the 4-way valve
     • 
    The temperature different between from the discharge tube to the 4-way valve and from
    suction tube to the 4-way valve becomes almost zero.
    71
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							14 Technical Data
    14.1. Thermostat Characteristics
    14.1.1. CS-W7DKE CS-W9DKE CS-W12DKE
    72
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							14.2. Sensible Capacity Chart
    14.2.1. 
    CS-W7DKE
    230VOutdoor Temp. (°C)
    Indoor wet
    bulb temp.30354046
    TCSHCIPTCSHCIPTCSHCIPTCSHCIP
    17.0°C2.281.730.652.131.660.701.981.590.751.801.510.81
    19.0°C2.300.71
    19.5°C2.501.810.662.341.740.712.181.670.761.981.590.82
    22.0°C2.731.880.672.551.810.732.371.740.782.161.660.84
    14.2.2. 
    CS-W9DKE
    230VOutdoor Temp. (°C)
    Indoor wet
    bulb temp.30354046
    TCSHCIPTCSHCIPTCSHCIPTCSHCIP
    17.0°C2.732.070.782.551.980.842.371.910.902.161.810.97
    19.0°C2.750.85
    19.5°C2.992.170.792.802.080.852.602.000.912.371.910.98
    22.0°C3.262.250.813.052.160.872.842.080.932.581.991.00
    14.2.3. 
    CS-W12DKE
    230VOutdoor Temp. (°C)
    Indoor wet
    bulb temp.30354046
    TCSHCIPTCSHCIPTCSHCIPTCSHCIP
    17.0°C3.572.711.033.342.601.103.102.491.182.822.371.27
    19.0°C3.601.12
    19.5°C3.922.831.043.662.721.123.412.621.203.102.501.30
    22.0°C4.272.941.063.992.831.143.722.731.223.382.601.32
    TC - Total Cooling Capacity(kW)Indoor 27°C/19°C
    SHC - Sensible Heat Capacity(kW)Outdoor 35°C/24°C
    IP - Input Power(kW)
    73
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							14.3. Operation Characteristics
    14.3.1. CS-W7DKE CU-W7DKE
    74
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							14.3.2. CS-W9DKE CU-W9DKE
    75
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							14.3.3. CS-W12DKE CU-W12DKE
    76
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							15 Exploded View (Indoor Unit)
    15.1. CS-W7DKE CS-W9DKE CS-W12DKE
    Note:
    The above explode d view is for the purpose of parts disassembly and replacement.
    The non-numbered parts are not kept as standard service parts.
    77
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							16 Replacement Parts List (Indoor Unit)
    16.1. CS-W7DKE CS-W9DKE CS-W12DKE
    REF. NO.PART NAME & DESCRIPTIONQTY.CS-W7DKECS-W9DKECS-W12DKEREMARKS1CHASSY COMPLETE1CWD50C1377←←2FAN MOTOR1CWA921181←←03CROSS FLOW FAN COMPLETE1CWH02C1031←←4BEARING ASS’Y1CWH64K007←←5SCREW - CROSS FLOW FAN1CWH4580304←←6EVAPORATOR1CWB30C1597←CWB30C15837FLARE NUT1CWT25086(1/4”)←←8FLARE NUT1CWT25087 (3/8”)←CWT25096 (1/2”)9HOLDER SENSOR1CWH32143←←10DISCHARGE GRILLE COMPLETE1CWE20C2366←←11VERTICAL VANE9CWE241150←←12CONNECTING BAR1CWE261066←←13CONNECTING BAR1CWE261070←←14AIR SWING MOTOR1CWA98260←←015LEAD WIRE - AIR SWING MOTOR1CWA67C3977←←16CAP - DRAIN TRAY1CWH521096←←17HORIZONTAL VANE1CWE241173←←18BACK COVER CHASSIS1CWD932454←←19CONTROL BOARD CASING1CWH102259←←20TERMINAL BOARD COMPLETE1CWA28C2074←CWA28C2071021POWER SUPPLY CORD1CWA20C2159←←22ELECTRONIC CONTROLLER - MAIN1CWA743658CWA743656CWA743558024SENSOR COMPLETE1CWA50C2122←←025CONTROL BOARD FRONT COVER1CWH131195←←26INDICATOR COMPLETE1CWE39C1115←←027INDICATOR HOLDER1CWD932429←←28INDICATOR HOLDER1CWD932430←←29CONTROL BOARD TOP COVER1CWH131207←←30REMOTE CONTROL COMPLETE1CWA75C2604←←031FRONT GRILLE COMPLETE1CWE11C3125←←032INTAKE GRILLE1CWE22C1154←←33GRILLE DOOR1CWE141073←←34AIR FILTER2CWD001144←←35SCREW - FRONT GRILLE2XTT4+16C←←36CAP - FRONT GRILLE2CWH521109←←37DRAIN HOSE1CWH851063←←38INSTALLATION PLATE1CWH361067←←39BAG COMPLETE - INSTALLATION SCREW1CWH82C067←←40FULCRUM1CWH621046←←41ELECTRONIC CONTROLLER - IONIZER1CWA743675←←042CASING - IONIZER1CWD932464←←43CASING - IONIZER1CWD932431←←44ION GENERATOR1CWH94C0001←←45SUPERSONIC AIR PURIFYING DEVICE1CWH91C1013←←46ELECTRONIC CONTROLLER SUPERSONIC1CWA743874←←047SUPER ALLERU BUSTER FILTER1CWD00C1133←←48FRAME FR AIR FILTER SUPERSONIC1CWD011026←←49FRAME FR AIR FILTER SUPERSONIC1CWD011027←←
    (Note)
     • All parts are supplie d from PHAAM, Malaysia (Vendor Code: 061).
     • “O”marked parts are recommended to be kept in stock.
    78
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							17 Exploded View (Outdoor Unit)
    17.1. CU-W7DKE CU-W9DKE
    Note:
    The above explode d view is for the purpose of parts disassembly and replacement.
    The non-numbered parts are not kept as standard service parts.
    79
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						
    							17.2. CU-W12DKE
    Note:
    The above explode d view is for the purpose of parts disassembly and replacement.
    The non-numbered parts are not kept as standard service parts.
    80
    CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE 
    						