Operation Details Auto, Heat, Cool, DryAuto, Heat, Cool, Dr y • Enables you to enjoy the cooling effect at your preferred setting temperature. • The range of temperature can be selected from 16°C ~ 30°C. • Enables you to set the desired temperature at low fan speed which provides you with the dehumidifying surroundings. • The range of temperature can be selected from 16°C ~ 30°C. AUTO - Automatic Operation COOL - Cooling Operation DRY - Soft Dr y Operation HOW TO OPERATE Supersonic air purifying device (super alleru-buster) operates automatically while the air conditioner is switched on. Powerful, Quiet and Ion operations could be activated in all operation modes. Press OFF/ON button again to stop the operation. Troubleshooting The room has a peculiar odour. ➤ This may be a damp smell emitted by the wall, carpet, furniture or clothing in the room. Air conditioner does not cool or heat effi ciently. ➤ Ensure the temperature has been set correctly. ➤ Ensure windows and doors have been closed properly. ➤ Ensure fi lters are cleaned or replaced when necessary. ➤ Ensure inlet and outlet vents of outdoor unit have not been obstructed. In heating operation Power indicator blinking, no warm air discharge.➤ Defrost operation at outdoor unit, maximum 12 minutes. To save electricity, close the curtains when using air conditioner to prevent sunlight and heat from coming in. Hint • The unit will automatically select the operation mode according to the room temperature. • Once the operation mode is selected, the unit will operate at the standard setting temperature as shown: Room temperatureOperation modeStandard setting temperature 23°C & above Cool 25°C Below 23°C Dry 22°C Below 20°C Heat 21°C • You may press or button to change the standard setting temperature to “HI” or “LO” as shown: Operation mode HI LO Cool 27°C 23°C Dry 24°C 20°C Heat 23°C 19°C • Enables you to enjoy the warming effect at your preferred setting temperature. • The range of temperature can be selected from 16°C ~ 30°C. HEAT - Heating Operation 22 Select the desired operation. 33 Set the temperature. Start the operation. 11 AUTO COOLHEAT DRY 41 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
Operations Details • To provide fresh air effect by producing negative ions. • To achieve setting temperature quickly. It will operate for 15 minutes and return to the previous setting. ION POWERFULPowerful, Powerful, Quiet, Quiet, Ion, Fan Speed, Ion, Fan Speed, Air SwingAir Swing • To provide you with the various fan speed selections. • There are 3 levels of fan speed in addition to automatic fan speed. • Automatic fan speed: The speed of the indoor fan is automatically adjusted according to the operation. FAN SPEED • To provide a quiet environment. QUIET • To ventilate air in the room. • There are 5 selections in addition to automatic vertical air fl ow direction. • If automatic vertical airfl ow direction has been set, the louver swings up and down automatically. • Please do not adjust the vertical airfl ow direction louver manually. • Horizontal airfl ow direction louver could be adjusted manually. AIR SWING Ion operation could be activated independently. Powerful and Quiet operations could not be activated at the same time. Powerful, Quiet and Ion operations could be cancelled by pressing the respective button again. Troubleshooting ION indicator on the indoor unit is blinking. ➤ Press ION button twice. If the indicator is still blinking, please consult the dealer. Indoor fan stops occasionally during Automatic Fan Speed setting. Indoor fan stops occasionally during heating operation.➤ This is an advanced feature that helps to remove smell from the surrounding area during operation. ➤ To avoids unintended cooling effect. HOW TO OPERATE Hints If you wish to have the cool air blowing directly on you, set the airfl ow direction downward but not for an excessive length of time, as it may harm your health. Approximately 10% of electricity can be saved if you set the temperature 1°C higher in cooling operation or 2°C lower in heating operation than the desired temperature. Enables powerful operation.Enables ion operation.IONIONPOWERFULPOWERFUL Select fan speed. FAN SPEED FAN SPEED Adjust the vertical airfl ow direction louver. AIR SWINGAIR SWING Enables quiet operation. QUIETQUIET 42 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
Press CLOCK more than 10 seconds to change the time format from 24 hours to AM/PM format. For your convenience, you could set the air conditioner to operate automatically by using both ON and OFF timer. Hint Troubleshooting TIMER indicator always on. ➤ Timer is activated and the setting will repeat itself daily. POWER indicator is blinking 30 minutes before ON timer is activated.➤ The unit is determining the operation mode by sensing the room temperature. This happens when it has been set to AUTO operation mode. HOW TO OPERATE TimerTimer Operation Details • Use the ON timer to turn on the air conditioner at the desired time. This will give you a cooling or warming environment, e.g. when you return from work or wake up. • When the ON timer is set, operation will start 15 minutes for COOL/DRY or 30 minutes for AUTO/HEAT before the actual set time. • Use the OFF timer to stop the air conditioner operation at the desired time. This can save electricity while you are going out or sleeping. • The set timer will repeat daily once it is set. • If there is a power failure, you can press SET button to restore the previous setting once the power is resumed. • If the timer is cancelled, you can restore the previous setting by pressing SET button. TIMER Ensure the clock on the remote control has been set correctly. You could use the ON and OFF timers at the same time. To cancel either the ON or OFF timer, press or , then press . 11 Select ON or OFF timer. 22 Set the desired time. 33 Confi rm the setting. CANCELCANCEL Cancel the selected timer. 43 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
CARE & CLEANING • Wipe the unit gently with a soft, dry cloth. • It is recommended to clean the air fi lters once every 2 weeks. • Purchase the replacement fi lter if it is damaged. Part no.: CWD001144 INDOOR UNIT AIR FILTER • It is recommended to clean the fi lter every 6 months. • Replace the fi lter every 3 years or purchase the replacement fi lter if it is damaged. Part no.: CZ-SA13P SUPER ALLERU-BUSTER Clean the fi lter regularly as dirty fi lters will cause unpurifi ed air, low cooling or heating capacity, unpleasant smells and higher energy consumption. The unit will become dirty and the performance of the unit will decrease after used for several seasons. Please consult an authorized dealer to perform seasonal inspections in addition to regular cleaning.• This inspection is recommended before operating the air conditioner at every season. • Check if the remote control batteries needed to be replaced. • Ensure there is no obstruction at all air intake and outlet vents. • After the start of operation for 15 minutes, it is normal if the temperature differences between air intake and outlet vents at indoor unit is:- Operation Temperature Cooling 8°C Heating 14°C • Operate the unit for 2~3 hours using ion operation to dry the internal parts. • Turn off the power supply and unplug. • Remove the remote control batteries. Switch off the power supply Switch off the power supply before cleaningbefore cleaning Hints Washing Instructions• Do not use benzene, thinner or scouring powder. • Use soaps or neutral household detergent ( ≃pH7) only. • Do not use water with temperature higher than 40°C. Pre-season Inspection Preparation for extended Non-operation • It is recommended to clean the ionizer every 6 months. IONIZERQ UIETPO WE RFULIONTIM ER POWE R Raise and Pull to remove. Wash and dry. FRONT PANELFRONT PANEL Wipe gently. INDOOR UNITINDOOR UNIT Vacuum, wash and dry. AIR FILTERAIR FILTER SUPERSONIC AIR SUPERSONIC AIR PURIFYING DEVICEPURIFYING DEVICE Clean with cotton bud. IONIZERIONIZER Remove Remove Vacuum the super alleru-buster fi lter. Vacuum, wash and dry the frame. Remove 44 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
10 Installation Instructions Required tools for Installation Works 1.Philips screw driver5.Spanner9.Gas leak detector13.Multimeter 2.Level gauge6.Pipe cutter10.Measuring tape14.Torque wrench 18 N.m (1.8 kgf.m) 42 N.m (4.2 kgf.m) 55 N.m (5.5 kgf.m) 3.Electric drill, hole core drill (ø70 mm)7.Reamer11.Thermometer15.Vacuum pump 4.Hexagonal wrench (4 mm)8.Knife12.Megameter16.Gauge manifold 10.1. Safety Precautions • Read the followin g“SAFET Y PRECA UTIONS”carefully before installation. • Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed. • The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the followin g indications. WARNINGThis indication shows the possibility of causing death or serious injury. CAUTIONThis indication shows the possibility of causing injury or damage to properties only. The items to be followed are classified by the symbols: Symbol with background white denotes item that is PROHIBITE D from doing. • Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference. WARNING 1.Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire. 2.Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 3.Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock. 4.Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury. 5.For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 6.Use the specified cable (1.5 mm2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection. 7.Wire routing must beproperly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up at connection point of terminal, fire or electrical shock. 8.When carrying outpiping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury. 9.Whenconnecting the piping, do not allow air or any substances other than the specified refrigerant (R410A) to enter the refrigeration cycle. Otherwise, this may lower the capacity, cause abnormally high pressure in the refrigeration cycle, and possibly result in explosion and injury. 10. • W hen connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A materials. • Thickness of copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm. • It is desirable that the amount of residual oil is less than 40 mg/10 m. 11.Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause fire or electrical shock. 45 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
CAUTION 1.The equipment must be earthed. It may cause electrical shock if grounding is not perfect. 2.Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at surrounding of the unit, it may cause fire. 3.Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the furniture. ATTENTION 1.Selection of the installation location. Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance. 2.Power supply connection to the room air conditioner. Connect the power supply cord of the room air conditioner to the mains using one of the following method. Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency. In some countries, permanent connection of this room air conditioner to the power supply is prohibited. 1. Power supply connection to the receptacle using a power plug. Use an approved 10A power plug with earth pin for the connection to the socket.. 2. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker for the permanent connection. It must be a double pole switch with a minimum 3.5 mm contact gap. 3.Do not release refrigerant. Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of the liquid refrigerant, it may cause frostbite. 4.Installation work. It may need two people to carry out the installation work. 5.Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc. 46 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
Attached access ories Applica ble piping kit CZ-3F5, 7BP (V7DK, V9DK,W7DK, W9DK) CZ-4F5, 7, 10BP (V12DK , W12DK) Select the best location INDOOR UNIT • There should not be any heat source or steam near the unit. • There should not be any obstacles blocking the air circulation. • A place where air circulation in the room is good. • A place where drainage can be easily done. • A place where noise prevention is taken into conside ration. • Do not install the unit near the door way. • Ensure the spaces indicate d by arrows from the wall, ceiling, fence or other obstacles. • Recommended installation height for indoor unit shall be at least 2.3 m. OUTDOOR UNIT • If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the conden ser is not obstructed. • There should not be any animal or plant which could be affected by hot air discharged. • Keep the spaces indicate d by arrows from wall, ceiling, fence or other obstacles. • Do not place any obstacles which may cause a short circuit of the discharged air. • If piping length is over the rated length, addition al refrigerant should be added as shown in the table. Indoor/outdoor Unit Installation Diagram • This illustration is for explana tion purposes only. The indoor unit will actually face a differen t way. 47 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
10.2.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) 10.2.2. HOW TO FIX INSTALLATION PLATE The mounting wall is strong and solid enough to prevent itfrom the vibration. The centre of installation plate should be at more than 450 mm at right and left of the wall. The distance from installation plate edge toceiling should more than 67 mm. From installation plate left edge to unit’s left side is 74 mm. From installation plate right edge to unit’s right is 94 mm. : : :For left side piping, piping connection for liquid should be about 15 mm from this line. For left side piping, piping connection for gas should be about 45 mm from this line. For left side piping, piping connection cable should be about 800 mm from this line 1. Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the concrete wall conside r using anchor bolts.) • Alwaysmount the installation plate horizontally by aligning the marking-off line with the thread and using a level gauge. 2. Drill the piping plate hole withø70 mm hole-core drill. • Line according to the arrows marked on the lower left and right side of the installation plate. The meeting point of the extended line is the centre of the hole. Anothe r method is by putting measuring tape at position as shown in the diagram above. The hole centre is obtaine d by measuring the distance namely 150 mm and 125 mm for left and right hole respectively. • Drill the piping hole at either the right or the left and the hole should be slightly slanted to the outdoor side. 10.2.3. TO DRILL A HOLE IN THEWALL AND INSTALL A SLEEVE OF PIPING 1. Insert the piping sleeve to the hole. 2. Fix the bushing to the sleeve. 3. Cut the sleeve until it extrudes about 15 mm from the wall. CautionWhen thewall is hollow, please be sure to use the sleeve for tube ass’y to prevent dangers caused by mice biting the connecting cable. 4. Finish by sealing the sleeve with putty or caulking compound at the final stage. 10.2.4. INDOOR UNIT INSTALLATION 1. For the right rear piping 2. For the right and right bottom piping 10.2. Indoor Unit 48 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
3. For the embedded piping (This can be used for left rear piping & left bottom piping also.) 49 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
10.2.5. CONNECT THECABLE TO THE INDOOR UNIT 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connec ting cable between indoor unit and outdoor unit shall be approved polychl oroprene sheathed 3 (V7DK, V9DK, V12DK ) or 5(W7DK, W9DK, W12DK)×1.5 mm 2 flexible cord, type designa tion 245 IEC 57 or heavier cord. • Ensure the color of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. • Earth lead wire shall be longer than the other lead wires as shown in the figure for the electrical safety in case of the slipping out of the cord from the anchorage. • Secure the cable onto the control board with the holder (clamper). 50 CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE