Page 51
CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3. Please make flare after inserting the flare nut onto the copper pipes. 10.3.4. (a)EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION) WHENINSTAL LING AN AIR CONDITIONER, BE SURE TO EVACU ATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the...
Page 52
(1)* *Connect the manifold gauge to the service port of 3-way valve. Measure the pressure.(2)* *Keep it for 5-10 minutes. Ensure that the pressure indicated on the gauge is the same as that of measured during the first time. 10.3.5. (b) AIR PURGING OF THE PIPING AND INDOOR UNIT The remaining air in the Refrigeration cycle which contains moisture may cause malfunction on the compressor. 1. Remove the caps from the 2-way and 3-way valves. 2. Remove the service-port cap from the 3-way valves. 3. To open...
Page 53
DISPOSAL OF OUTDOOR UNITDRAIN WATER • If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm. • If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it isrecommended not to use a drain elbow, for the drain water freezes and the fan will not rotate. CHECK THE DRAINAGE • Open front panel and remove air filters. (Drainage checking can be carried out without removing the front grille.) • Pour a glass of water into the drain...
Page 54
11 Installation and Servicing Air Conditioner Using R410A 11.1. OUTLINE 11.1.1. About R410ARefrigerant 1. Converting air conditio ners to R410A Since it was declared in1974 that chlorofluoroca rbons (CFC), hydro chlorofluoroca rbons (HCFC) and other substances pose a destructive danger to the ozone layer in the earth´s upper stratosphere (20 to 40 km above the earth), measures have been taken around the world to prevent this destruction. The R22 refrigerant which has conventionally been used in ACs is...
Page 55
d. R410A refrigerating machine oil Conventionally , mineral oil or a synthet ic oil such as alkylbe nzene has been used for R22 refrigerating machine oil. Becaus e of the poor compatibility between R410A and conventional oils like mineral oil, however, there is a tendency for the refrigerating machine oil to collect in the refrigerating cycle. For this reason, polyest er and other synthet ic oils which have a high compatibility with R410A are used as refrigerating machine oil. Becaus e of the high...
Page 56
11.2.2. R410ATools 1. Cooper tube gauge for clearance adjustment (used when flaring with the conventional flaring tool (clutch type)) • This gauge makes iteasy to set the clearance for the copper tube to 1.0-1.5 mm from the clamp bar of the flaring tool. 2. Flaring tool (clutch type) • In the R410A flaring tool, the receiving hole for the clamp bar is enlarged so the clearance from the clamp bar can be set to 0-0.5 mm, and the spring inside the tool is strengthened to increase the strength of the...
Page 57
5. Charging hose • The pressure resistance of the charging hose has been raised to match the higher pressure of R410A . The hose material has also been changed to suit HFC use, and the size of the fitting has been changed to match the manifold ports. 6. Vacuum pump adaptor • W hen using a vacuum pump for R410A , it is necessary to install an electromagnetic valve to prevent the vacuum pump oil from flowing back into the charging hose. The vacuum pump adaptor is installed for that purpose. if the...
Page 58
8. Electronic scale for refrigerant charging • Because of the high pressure and fast vaporizing speed of R410A , the refrigerant cannot be held in a liquid phase inside the charging cylinde r when charging is done using the charging cylinde r method, causing bubble s to form in the measurement scale glass and making it difficult to see the reading. (Naturally, the conventional R22 charging cylinde r cannot be used because of the differen ces in the pressure resistance, scale gradation, connecting port...
Page 59
11.3. REFRIGERANT PIPING WORK Whenworking with refrigerant piping, the followin g points must be carefully observed: no moisture od dust must be allowed to enter the piping, and there must be no refrigerant leaks. 1. Procedure and precautions for flaring work a. Cut the pipe Use a pipe cutter, and cutslowly so the pipe will not be deformed. b. Remove burrs and clean shavings from the cut surface If the shape of the pipe end is poor after removing burrs, or if shavings adhere to the flared area, it may...
Page 60
2. Procedure and precautions for flare connection Table 11 R410A flaring dimensionsNominal diameterOutside diameter (mm)Wall thickness (mm)A (mm) R410A flaring tool, clutch typeConventional flaring tool Clutch typeWing-nuttype 1/46.350.80 - 0.51.0 - 1.51.5 - 2.0 3/89.520.80 - 0.51.0 - 1.51.5 - 2.0 1/212.700.80 - 0.51.0 - 1.52.0 - 2.5 Table 12 R410A flaring dimensionsNominal diameterOutside diameter (mm)Wall thickness (mm)A (mm) R410A flaring tool, clutch typeConventional flaring tool Clutch...