10.2.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) 10.2.2. HOW TO FIX INSTALLATION PLATE The mounting wall is strong and solid enough to prevent it from the vibration. The centre of installation plate should be at more than 450 mm at right and left of the wall. The distance from installation plate edge to ceiling should more than 67 mm. From installation plate left edge to unit’s left side is 47 mm. From installation plate right edge to unit’s right is 73 mm. : : :For left side piping, piping connection for liquid should be about 14 mm from this line. For left side piping, piping connection for gas should be about 56 mm from this line. For left side piping, piping connecting cable should be about 785 mm from this line. 1. Mount the installation plate on the wall with 5 screws or more. (If mounting the unit on the concrete wall consider using anchor bolts.) • Always mountthe installation plate horizontally by aligning the marking-off line with the thread and using a level gauge. 2. Drill the piping plate hole with ø70 mm hole-core drill. • Line according to the arrows marked on the lower left and right side of the installation plate. The meeting point of the extended line is the centre of the hole. Another method is by putting measuring tape at position as shown in the diagram above. The hole centre is obtained by measuring thedistance namely 150 mm and 125 mm for left and right hole respectively. • Drill the piping hole at either the right or the left and the hole should be slightly slanted to the outdoor side. 10.2.3. TO DRILL A HOLE IN THE WALL AND INSTALL A SLEEVE OF PIPING 1. Insert the piping sleeve to the hole. 2. Fix the bushing to the sleeve. 3. Cut the sleeve until it extrudes about 15 mm from the wall. CautionWhen the wall ishollow, please be sure to use the sleeve for tubeass’y to prevent dangers caused by mice biting the connecting cable. 4. Finish by sealing thesleeve withputty orcaulking compound at the final stage. 10.2.4. INDOOR UNIT INSTALLATION 1. For the right rear piping 2. For the right and right bottom piping 10.2. INDOOR UNIT 41 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
3. For the embedded piping (This can be used for left rear piping & left bottom piping also.) 42 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
10.2.5. CONNECT THE CABLE TO THE INDOOR UNIT 1. The inside and outside connecting cable can be connected without removing the front grille. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (C7BK, C9BK, C12BK, V7BK, V9BK, V12BK) or 5 (A7BK, A9BK, A12BK, W7BK, W9BK, W12BK) × 1.5 mm 2flexible cord, type designation 245 IEC57 or heavier cord. • Ensure the color of wires of outdoor unit and the terminal Nos. are the same to the indoor’s respectively. • Earth lead wire shall be longer than the other lead wires as shown in the figure forthe electrical safetyin case of the slipping out of the cord from the anchorage. • Secure the cable onto the control board with the holder (clamper). INSTALLATION OFAIR PURIFYING FILTERS 1. Open the front panel. 2. Remove the air filters. 3. Put air purifying filters(left) and solar refreshing deodorizing filter (right) into place as shown in illustration below. 43 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
HOW TO TAKE OUT FRONT GRILLE Please follow the steps below to take out front grille if necessary such as when servicing. 1. Set the vertical airflow direction louver to the horizontal position. 2. Slide down the two caps on the front grille as shown in the illustration below, and then remove the two mounting screws. 3. Pull the lower section of the front grille towards you to remove the front grille. When reinstalling the front grille, first set the vertical airflow direction louver to the horizontal position and then carry out above steps 2 -3 in the reverse order. AUTO SWITCH OPERATION The below operations will be performed by pressing the “AUTO” switch. 1. AUTO OPERATION MODE The Auto operation will be activated immediately once the Auto Switch is pressed. 2. TEST RUN OPERATION (FOR PUMP DOWN/SERV ICING PURPOSE) The Test Run operation will be activated if the Auto Switch is pressed continuously for more than 5 sec. to below 10 sec.. A “pep” sound will occur at the fifth sec., in order to identify the starting ofTest Run operation 3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF The ON/OFF of Remote Controller receiving sound can be change over by pressing the “AUTO” Switch continuously for 10 sec. and above. A “pep”, “pep” sound will occur at the tenth sec., in order to indicate the “ON/OFF” change over of remote control receiving sound. 10.3. OUTDOOR UNIT 10.3.1. SELECT THE BEST LOCATION (Refer to “Select the best location” section) 10.3.2. INSTALL THE OUTDOOR UNIT • After selecting the best location, start installation according to Indoor/Outdoor Unit Installation Diagram. 1. Fix the unit on concreteor rigid frame firmly and horizontally by bolt nut. (ø10 mm). 2. When installing at roof, please consider strong wind and earthquake. Please fasten theinstallation standfirmly with bolt or nails. 10.3.3. CONNECTING THE PIPING Connecting The Piping To Indoor Unit Please make flare after inserting flare nut (locate at joint portion of tube assembly) onto the copper pipe. (In case of using long piping) Connect the piping • Align the center of piping and sufficiently tighten the flare nut with fingers. • Further tighten the flare nut with torque wrench in specified torque as stated in the table. MODELPiping size (Torque) GasLiquid C7BK, C9BK, A7BK, A9BK, V7BK, V9BK, W7BK, W9BK3/8” (42 N.m)1/4” (18 N.m) C12BK, A12BK, V12BK, W12BK1/2” (55 N.m)1/4” (18 N.m) Connecting The Piping To Outdoor Unit Decide piping length and then cut by using pipe cutter. Remove burrs from cut edge. Make flare after inserting the flare nut (located at valve) onto the copper pipe. Align center of piping to valves and then tighten with torque wrench to the specified torque as stated in the table. 44 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
CUTTING AND FLARING THE PIPING 1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. 3. Please make flare after inserting the flare nut onto the copper pipes. 10.3.4. (a) EVACUATION OF THE EQUIPMENT (FOR EUROPE & OCEANIA DESTINATION) WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. 1. Connect a charging hose with a push pin to the Low andHigh side of a charging set andthe service port ofthe 3-wayvalve. • Be sure to connect the end of the charginghose with the push pin to the service port. 2. Connect the center hose of the charging set to avacuum pump with check valve, orvacuum pump and vacuum pump adaptor. 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Thenevacuate the air approximately ten minutes. 4. Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately five minutes. Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE. 5. Disconnect the charging hose from the vacuum pumpand from the service portof the3-way valve. 6. Tighten the service port capsof the 3-wayvalve at torque of 18 N.m with a torque wrench. 7. Remove the valve caps of both ofthe 2-wayvalve and3-way valve.Position both of the valves to “OPEN” using a hexagonal wrench (4 mm). 8. Mount valve caps onto the2-wayvalve and the3-way valve. • Be sure to check for gas leakage. CAUTION • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure: • If the leak stops when the piping connections are tightened further, continue working from step 3. • If the leak does not stop when the connections are retightened, repair the location of leak. • Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may cause frostbite. 45 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
(1)* *Connect the manifo ld gauge to the service port of 3-way valve. Measure the pressure. 10.3.6. CONNECT THE CABLE TO THE OUTDOOR UNIT 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 (C7BK, C9BK, C12BK, V7BK, V9BK, V12BK) or 5 (A7BK, A9BK, A12BK, W7BK, W9BK, W12BK) × 1.5 mm 2flexible cord, type designation 245 IEC57 or heavier cord. 3. Secure the cable onto the control board with the holder (clamper). 4. Attach the control board cover back to the original position (2)* *Keep it for 5-10 minutes. Ensure that the pressure indicated on the gauge is the same as that of measured during the first time. with the screw. 10.3.5. (b) AIR PURGING OF THE PIPING AND INDOOR UNIT The remaining air in the Refrigeration cycle which contains moisture may cause malfunction on the compressor. 1. Remove the caps fromthe 2-way and3-wayvalves. 2. Remove the service-portcap from the3-wayvalves. 3. To open the valve, turn the valvestem of 2-wayvalve counter-clockwise approx. 90° and hold it there for ten seconds, then close it. 4. Check gas-leakage of the connecting portion of the pipings. For the left pipings, refer to item 4(A). 5. To open2-wayvalve again, turn the valve stem counter-clockwise until it stops. 4(A). Checking gas leakage for the left piping. 46 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
10.3.7. PIPE INSULATION 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap the insulated piping end to prevent water from going inside the piping. 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM with thickness 6 mm or above. DISPOSAL OFOUTDOOR UNIT DRAINWATER • If a drain elbow is used, the unit should be placed on a stand which is taller than 3 cm. • If the unit is used in an area where temperature falls below 0°C for 2 or 3 days in succession, it is recommended not to use a drain elbow, for the drain water freezes and the fan will not rotate. CHECK THEDRAINAGE • Open front panel and remove air filters. (Drainage checking can be carriedout without removing the front grille.) • Pour a glass of water into the drain tray-styrofoam. • Ensure that water flows out from drain hose of the indoor unit. EVALUATION OF THEPERFORMANCE • Operate the unit at cooling operation mode for fifteen minutes or more. • Measure the temperature of the intake and discharge air. • Ensure the difference between the intake temperature and the discharge is more than 8°C. 47 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
NOTE:These equipment shall be connected to a suitable mains network with a main impedance less than the following: CS-A9BKP / CU-A9BKP5: 0.44Ω CS-C12BKP / CU-C12BKP5: 0.47Ω CS-A12BKP / CU-A12BKP5: 0.47Ω CS-V12BKP / CU-V12BKP5: 0.45Ω CS-W12BKP / CU-W12BKP5: 0.45Ω CHECK ITEMS Is there any gas leakage at flare nut connections? Has the heat insulation been carried out at flare nut connection? Is the connecting cable being fixed to terminal board firmly? Is the connecting cable being clamped firmly? Is the drainage OK? (Refer to “Check the drainage” section) Is the earth wire connection properly done? Is the indoor unit properly hooked to the installation plate? Is the power supplyvoltage complied with rated value? Is there any abnormal sound? Is the cooling operation normal? Is the thermostat operation normal? Is the remote control’s LCD operation normal? Is the air purifying filter installed? 48 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
11 2-way, 3-way Valve 2-way Valve (Liquid Side)3-way Valve (Gas Side) WorksShaft PositionShaft PositionService Port ShippingCloseCloseClose (With valve cap)(With valve cap)(With cap) EvacuationCloseCloseOpen (Installation and(Counter-Clockwise)(Clockwise)(Push-pin) Re-installation) OperationOpenOpenClose (With valve cap)(With valve cap)(With cap) Pumping downCloseOpenOpen (Transferring)(Clockwise)(Counter-Clockwise)(Connected manifo ld gauge) EvacuationOpenOpenOpen (Servicing)With vacuumpump Gas chargingOpenOpenOpen (Servicing)(Withchargingcylinder) Pressure checkOpen (Servicing)OpenOpen(Connected manifo ld gauge) Gas releasingOpen (Servicing)OpenOpen(Connected manifo ld gauge) 49 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5
11.1.1. Evacuation of Installation WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in the following procedure. 1. Connect a charging hose with a push pin to the Low side of a charging set and the service port of a 3-way valve. • Be sure to connect the endof the charging hose with the push pin to the service port. 2. Connect the centre hose of the charging set to a vacuum pump. 3. Turn on the power switchof the vacuum pump and make sure that the needle in the gauge moves from 0 MPa (0 cmHg) to -0.1 MPa (-76 cmHg). Then evacuate the air for approximately ten minutes. 4. Close the Lowside valveof the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not move after approximately five minutes. BE SURE TO TAKE THISPROCEDURE IN ORDER TO AVOID GAS LEAKAGE.If air remain in the indoor unit and refrigeration pipes, it will affect the compressor, reduce tocooling capacity, and could lead to a malfunction. 5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-wayvalve. 6. Tighten the service port cap ata torque of 18 N.m with a torque wrench. 7. Remove the valvecaps of the2-wayvalve and the 3- way valve.Position both of thevalves to“open” using a hexagonal wrench (4 mm). 8. Mount thevalve capsonto the 2-wayand 3-way valves. • Be sure to check for gas leakage. CautionIf gauge needle does not move from 0 cmHg to -76 cmHg in step (3) above, take the following measures: If the leaks stop when the piping connections are tightened further, continue working from step (3). If the leaks do not stop when the connections are retightened, repair the location of the leak. 11.1. Evacuation of the Equipment (For Europe & Oceania Destination) Procedure: 50 CS-W7BKP CU-W7BKP5 / CS-W9BKP CU-W9BKP5 / CS-W12BKP CU-W12BKP5