Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual
Have a look at the manual Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
22.1. Energy save setting • • • • Upper and lower limit can be set for the setting temperature during cooling and heating operation. (The factory shipment setting has an upper limit of 31°C and a lower limit of 16°C.) 1. While operation is stopped, press theTEMP UP and TEMP DOWNbuttons simultaneousl y. 2. To set an upper limit Press the OPERATION button until HEAT is display ed. ↓ Press the TEMP UP or TEMPDOWNbutton to set the temperature. ↓ Press the SET button to complete the upper limit setting. Example: If the heating display is set to 28°C, setting the temperature to higher than 28°C will not be possible. * Upper and lower limits cannot be set at the same time. 3. To set a lower limit Press the OPERATION button until COOL is display ed. ↓ Press the TEMP UP or TEMPDOWNbutton to set the temperature. ↓ Press the SET button to complete the lower limit setting. Example: If the cooling display is set to 22°C, setting the temperature to lower than 22°C will not be possible. * Press the CANCEL button to cancel the setting. 22.2. Switching to the remote control thermistor • • • • The temperature detection thermistor used for detecting the indoor temperature can be switched between the thermistor at the indoor unit and the thermistor at the remote control unit. (The factory shipment setting is at the indoor unit side.) 1. While operation is stopped, press and hold theTEST RUN button, TEMP UP button and TEMPDOWNbutton simultaneousl y. Press theFORWARD orBACK timer button to change the temperature detection setting. 2. Press the SET button to complete the setting. To change the setting, repeat the above operation. 22 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH 52
Setting group for 1 remote control unit • • • • W hen using a remote control thermostat, the thermostat setting is used for all indoor units in the group. • • • • During group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units and cooling-only units.) • • • • Do not mix manua l settings and automatic settings. (Manual settings take priority.) • • • • The master unit and slave units can be centralized controlled during group control. Automatic setting for group control • • • • If the power supplie s for indoor units which are connected are turned on simultaneousl y, the indoor unit numbe rs will Automatic address resetting for group control Set the DIP switches 1 to 4 to OFF and stop the operation. Then press the “AIR SWING AUTO” “OPERATION ” and “Air conditioner No.” buttons simultaneousl y. Then addresses will be momentarily reset, and then automatic address setting will be carried out once more.be determined automatically after approximately 1 minute. (DIP switch settings are not necessary.) NOTE: • • • • Correct wiring connections are a basic requirement for automatic setting. If the wires are connected incorrectly when the power is turned on, the settings will not be made correctly and operation will not be possible. • • • • W hen address numbe rs are set automatically , you will not know which address numbe r corresponds to which indoor unit. • • • • Do not turn off the power supply for at least 1 minute during automatic address setting, otherwise the settings will not be made correctly. Notewithregard to the Mini-cassette Whencarrying out group control of a Mini-cassette system using a single wireless remote control, be sure to disconnect the connectors for all receptor circuit boards except the one for indoor unit. No. 1, before turning on the power. (The same action as for the slave units in twin and triple systems is necessary.) 23 GROUP CONTROL 53
If test operation does not proceed correctly Carry out test operation after approximately 12 hours have passed since the power was turned on (crankcase heater is energized). If operation is started by using the remote control within 1 minute of turning on the power, the outdoor unit settings will not be made correctly and correct operation will not be possible. If the following symptoms occur after turning on the power, check the wiring connections once more. • • • • For standard installation (System example) 1. The main power is turned on while the indoor-outdoo r transmission wires are not connected (open circuit at section A) Symptom: Remote control unit... “CHECK” flashes NOTE: Indoor unit... LED2 on printed circuit board flashes Outdoor unit... LED3 and LED7 on printed circuit board flash 2. The main power is turned on while the indoor-outdoo r power supply wires are not connected (open circuit at section B) Symptom: Remote control unit... Display of “No power supply” NOTE: Indoor unit... No display Outdoor unit... LED3 and LED7 on printed circuit board flash 3. The main power is turned on while the remote control unit connection cord is not connected (open circuit at section C) Symptom: Remote control unit... Display of “No power supply”NOTE: Indoor unit... LED1 on printed circuit board stays illuminated Outdoor unit... LED1 on printed circuit board stays illuminated (When remote controldisplay shows “Power supply ”) (When remote controldisplay shows “No power supply ”) Remedy 1. Turn off the main power. ↓ 2. Conne ct the disconnected wire correctly. ↓ 3. Turn on the main power. ↓ 4. After 1 minute, start the operation using the remote control. (Indoor unit operation will start according to the remote control setting.) (Outdoor unit operation will start after 3-5 minutes.) NOTE: The “CHECK” display on theremote control and the flashing of LEDs on the printed circuit boards will not occur immediately. They will appear 3-6 minutes after the main power is turned on. 24 TROUBLESHOOTING 54
1. The main power is turned on while the transmission wires between the indoor unit(s) are not connected (open circuit at section A) Symptom: Nothing abnormal appears on the remote control display . If operation is started in this condition, the combination of the 50BB outdoo r unit and the 14BB4 indoor unit (master unit) will result in abnormal operation. ↓ If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop. − − − − Remote control... “CHECK” flashes − − − − Indoor unit (master)... The LEDs on the printed circuit board flash and operation stops − − − − Indoor unit (slave)... LED1 on the printed circuit board illuminates and the unit does not operate at all − − − − Outdoor unit... The LEDs on the printed circuit board flash and operation stops 2. The main power is turned on while the power supply wires between the indoor unit(s) are not connected (open circuit at section B) Symptom: Same as above. If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop. ↓ − − − − Remote control... “CHECK” flashes − − − − Indoor unit (master)... The LEDs on the printed circuit board flash − − − − Indoor unit (slave)... The LEDs on the printed circuit board do not illuminate and the unit does not operate at all − − − − Outdoor unit... The LEDs on the printed circuit board flash and operation stops 3. The main power is turned on while the remote controlconnection cord is not connected (open circuit at section C) Symptom: − − − − Remote control unit.. . Display of “No powersupply ” − − − − Indoor unit (master)... LED1 on the printed circuit board stays illuminated and the unit does not operate − − − − Indoor unit (slave)... LED1 on the printed circuit board stays illuminated and the unit does not operate − − − − Outdoor unit... LED1 on the printed circuit board stays illuminated and the unit does not operate Remedy 1. Turn off the main power. ↓ 2. Conne ct the disconnected wires correctly. ↓ 3. Turn on the main power. ↓ 4. After 1 minute, start the operation using the remote control. (Indoor units’ operation will start according to the remote control setting.) (Outdoor unit operation will start after 3-5 minutes.) If slave units do not operate even after the wiring has been corrected (automatic addressing is not possible) 1. Check that DIP switches 1 to 4 and DIP switch 8 are all set to OFF, and then stop operation. ↓ 2. Press the ADDRESS RESET button(SW3) at the outdoo r unit for approximately 4 seconds (The self-diagnosis LEDs 2 to 8 will illuminate in order, and the system is reset once they are all illuminated.) The above procedure cannot be used to carry out automatic address resetting during group control. 55
1. The main power is turned on while the transmission wires between the indoor unit and the outdoor unit are not connected (open circuit at section A) Symptom: Operation of indoor unit No. 1 and indoor unit No. 3 is possible. However, “CHECK” flashes in the remote controldisplay for 3-5 minutes after the main power is turned on. − − − − Remote control... “CHECK” flashes − − − − Indoor unit No. 2... LED2 on the printed circuit board flashes (both master and slave units) − − − − Outdoor unit No. 2... LED3 and LED7 on the printed circuit board flash 2. The main power is turned on while the power supply wires between the indoor units are not connected (open circuit at section B) Symptom: Operation of indoor unit No. 1 and indoor unit No. 3 is possible However, if operation is then started in this condition, the combination of the 28BB outdoo r unit and the 14BT indoor unit (master unit) will result in abnormal operation of indoor unit No. 2. ↓ If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop − − − − Remote control... “CHECK” flashes (indoor unit No. 2 abnormality) − − − − Indoor unit No. 2... LED2 on the printed circuit board flashes (both master and slave units) − − − − Outdoor unit No. 2... The LEDs on the printed circuit board flash 3. The main power is turned on while the remote control connection cord is not connected (open circuit at section C)Symptom: Nothing abnormal appears on the remote control display , and operation of indoor unit. No. 1 and indoor unit No. 2 is possible. However, indoor unit No. 3 cannot be operated. • • • • Remedy 1. Turn off the main power. ↓ 2. Conne ct the disconnected wires correctly. ↓ 3. Turn on the main power. ↓ 4. After 1 minute, start the operation using the remote control. (Indoor units’ operation will start according to the remote control setting.) (Outdoor units’ operation will start after 3-5 minutes.) If slave units do not operate even after the wiring has been corrected (automatic addressing is not possible) 1. Check that DIP switches 1 to 4 and DIP switch 8 are all set to OFF, and then stop operation. ↓ 2. Press the “AIR SWING AUTO”, “OPERATION ” and “A/C No.” buttons simultaneousl y. The addresses will be momentarily reset, and then automatic address setting will be carried out once more. The above procedure cannot be used to carry out automatic address resetting of twin/triple control. (Note on automatic address setting) The printed circuit boards automatically store the connected system configuration when power is supplie d. As a result, once the power has been turned on for these printed circuit boards, the units can not be changed about within the system, even if the units are of the same model and have same capacity. 56
1. Automatic address setting (don’t need to set dip-switch) If the wiring is connected properly as above example, the address is set automatically by the main powersupply . An indoor unit with remote control will be set as the master. If the power source is installe d to indoor units and outdoo r units separately, turn on the switch by following the procedure: outdoor unit, then indoor unit with control, and finally other indoor units. When theslave units do not operate (when address cannot be set) 1. Automatic address setting (don’t need to set dip-switch) If the wiring is connected properly as above example, the AC numbe rs are set automatically by the main power supply. An indoor unit withremote control will be set as the master. If the power source is installe d to indoor units and outdoo r units separately, turn on the switch by following theReset the address by following the procedure: a. After making sure that dip-switches No. 1 to 4 and No. 8 are OFF, stop the operation. b. Push address reset button(SW3) on theoutdoor unit PC board for 4 seconds. Self-diagnosis LED No. 2 to 8 will start blinking in order. And when all 7 pieces of LEDs (No. 2 ~ 8) are illuminated, the address for the slave unit has been reset. Important:The address for the group control cannot be reset, using the above mentioned procedure. 2. Manua l address setting (by dip-switchDSW1) Whensetting the address manua lly, set the dip-switch of the PC board of the indoor unit as follows: procedure: outdoor unit, then indoor unit with control, and finally other indoor units. The AC numbe r will be set at random. When theslave units do not operate (when address cannot be set) 57
Reset the address by following the procedure: a. Make sure that dip-switches No. 1 to 4 and No. 8 are OFF, stop the operation. b. Simultaneously, push buttons “AIR SWING AUTO”, “OPERATION ” and “A/C No.”. The address will be reset and new address will be set. Important:The address for the Twin/Triple control cannot be reset, using the above mentioned procedure. 2. Manua l address setting (by dip-switchDSW1) Whensetting the address manua lly, set the dip-switch of the PC board of the indoor unit as follows: 3. Manua l address setting (by dip-switchDSW1) Whensetting the address manua lly, set the dip-switch of the PC board in the indoor unit as follows: Procedures of deleting memory for twin/triple control system 1. Switch off the main power supply. 2. Set the No. 8 pin of dip switch (DSW1) at the indoor unit’s P.C. board to “ON” position. 3. Switch on the main power supply for a minute and then turn it off. 4. Set the No. 8 pin of dip switch (DSW1) to “OFF” position. Procedures of deleting memory for group control system 1. Switch off the main power supply. 2. Set the No. 1 until No. 4 pin of dip switch (DSW1) at the indoor unit’s P.C. board to “ON” position. (Make sure No. 8 pin of dip switch (DSW1) is at “OFF” position) 3. Switch on the main power supply for a minute and then turn it off. 4. Set the No. 1 pin until No. 4 pin of dip switch (DSW1) to “OFF” position. (Important notice) Above procedures are meant for deletin g memory on indoor unit’s P.C. board. And it is not for Address reset. Indoor unit P.C. board layout Below drawing shows the location of dip switch 1(DSW1) on the indoor unit P.C. board. Dip switch 1 (DSW1). [to be used for manual setting] 58
Emergencyoperation • • • • Emergency operation of outdoor unit Emergency operation can be carried out by setting the DSW1switch on the printed circuit board of the outdoor unit to the EMERGENCY position. However, emergency operation is only carried out when an abnormality is detected by the indoor/outdoor temperature thermistors. The resistance values of each thermistor are measured as shown in the table below to determine if there is an abnormality. Thermistor resistance table Temperatu reResistance value (kΩ )±5% Room temperature thermistorPipe temperature thermistor -20°C205.8197.8 -10°C114.6111.9 -5°C87.385.4 0°C67.065.8 5°C51.851.0 10°C40.439.9 15°C31.730.7 20°C25.125.0 25°C20.020.0 30°C16.116.0 40°C10.410.6 50°C6.97.1 60°C4.74.9 70°C----3.5 80°C----2.5 90°C----1.8 100°C----1.4 The pipe temperature thermistor resistance value are the same for the indoor and outdoor units. − − − − Set only the thermistor which shows an abnormality to the condition as shown in the table below to carry out emergency operation. ThermistorCooling modeHeating mode Indoor unitRoom temperatureFixed at 25°C Pipe temperatureShortedOpen ThermistorCooling modeHeating mode Outdoor unitDischarge temperatureOpenShorted Heat exchanger outlet temperatureShortedOpen − − − − Refer to the circuit diagram for the connection locations for each thermistor. − − − − If there is an abnormality in the roomtemperature thermistor, the temperature will be fixed at 25°C regardless of the remote controldisplay . NOTE: − − − − Any abnormalities detected by the temperature thermistors are ignored during emergency operation, therefore, long-term operation in this mode should be avoided. − − − − After emergency mode operation has been completed and normal operation is to be resumed, turn off the power supplie s for the indoor and outdoor units and set theDSW1switch to NORMAL position. − − − − Self-diagnosis LEDs 4 to 6 will flash during emergency operation. 25 EMERGENCY OPERATION 59
26 CONTROL Description of basic Functions 26.1. Cooling mode operation time chart (*1) Outdoor unit fan start control during cooling At the start of cooling mode and drying mode operation, the outdoo r unit heat exchan ger outlet temperature is detected in order to set the fan speed. Operation is carried out at the fan speed detected for 30 seconds. After 30 seconds, the heat exchan ger outlet temperature is detected and the outdoo r unit fan speed is changed automatically . (*2) Cooling low outdoor temperature protection When theoutlet temperature of the heat exchan ger drops to less than 12°C for a continuous period of 10 minutes, the outdoor unit stops. This is cancelled after 3 minutes (re-start prevention) • • • • Remote control display s and indoor unit operation continue during thistime. • • • • The 10 minutes countdown is cleared if the compressor stops or if the temperature at the outdoor unit outlet rises to 13.5°C or higher. 60