Home > Panasonic > Air Conditioner > Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual

Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							51 
    						
    							22.1. Energy save setting
     
        • 
    • •  • 
    Upper and lower limit can be set for the setting temperature
    during cooling and heating operation. (The factory shipment
    setting has an upper limit of 31°C and a lower limit of 16°C.)
     1. While operation is stopped, press theTEMP UP and TEMP
    DOWNbuttons simultaneousl y.
     2. To set an upper limit
    Press the OPERATION button until HEAT is display ed.
    ↓
    Press the TEMP UP or TEMPDOWNbutton to set the
    temperature.
    ↓
    Press the SET button to complete the upper limit setting.
    Example:
    If the heating display is set to 28°C, setting the temperature
    to higher than 28°C will not be possible.
    * Upper and lower limits cannot be set at the same time.
     3. To set a lower limit
    Press the OPERATION button until COOL is display ed.
    ↓
    Press the TEMP UP or TEMPDOWNbutton to set the
    temperature.
    ↓
    Press the SET button to complete the lower limit setting.
    Example:
    If the cooling display is set to 22°C, setting the temperature
    to lower than 22°C will not be possible.
    * Press the CANCEL button to cancel the setting.
    22.2. Switching to the remote
    control thermistor
     
        • 
    • •  • 
    The temperature detection thermistor used for detecting the
    indoor temperature can be switched between the thermistor
    at the indoor unit and the thermistor at the remote control
    unit. (The factory shipment setting is at the indoor unit side.)
     1. While operation is stopped, press and hold theTEST RUN
    button, TEMP UP button and TEMPDOWNbutton
    simultaneousl y.
    Press theFORWARD orBACK timer button to change the
    temperature detection setting.
     2. Press the SET button to complete the setting.
    To change the setting, repeat the above operation.
    22 SETTING OF SAVE ENERGY AND THERMISTOR SWITCH
    52 
    						
    							Setting group for 1 remote control unit
     
        • 
    • •  • 
    W hen using a remote control thermostat, the thermostat
    setting is used for all indoor units in the group.
     
        • 
    • •  • 
    During group control, up to a maximum of 16 indoor units
    can be connected. (Do not mix heat pump units and
    cooling-only units.)
     
        • 
    • •  • 
    Do not mix manua l settings and automatic settings. (Manual
    settings take priority.)
     
        • 
    • •  • 
    The master unit and slave units can be centralized
    controlled during group control.
    Automatic setting for group control
     
        • 
    • •  • 
    If the power supplie s for indoor units which are connected
    are turned on simultaneousl y, the indoor unit numbe rs will
    Automatic address resetting for group control
    Set the DIP switches 1 to 4 to OFF and stop the operation.
    Then press the “AIR SWING AUTO” “OPERATION ” and “Air
    conditioner No.” buttons simultaneousl y. Then addresses will
    be momentarily reset, and then automatic address setting will
    be carried out once more.be determined automatically after approximately 1 minute.
    (DIP switch settings are not necessary.)
    NOTE:
     
        • 
    • •  • 
    Correct wiring connections are a basic requirement for
    automatic setting. If the wires are connected incorrectly
    when the power is turned on, the settings will not be made
    correctly and operation will not be possible.
     
        • 
    • •  • 
    W hen address numbe rs are set automatically , you will not
    know which address numbe r corresponds to which indoor
    unit.
     
        • 
    • •  • 
    Do not turn off the power supply for at least 1 minute during
    automatic address setting, otherwise the settings will not be
    made correctly.
    Notewithregard to the Mini-cassette
    Whencarrying out group control of a Mini-cassette system
    using a single wireless remote control, be sure to disconnect
    the connectors for all receptor circuit boards except the one for
    indoor unit. No. 1, before turning on the power. (The same
    action as for the slave units in twin and triple systems is
    necessary.)
    23 GROUP CONTROL
    53 
    						
    							If test operation does not proceed correctly
    Carry out test operation after approximately 12 hours have passed
    since the power was turned on (crankcase heater is energized). If
    operation is started by using the remote control within 1 minute of
    turning on the power, the outdoor unit settings will not be made
    correctly and correct operation will not be possible.
    If the following symptoms occur after turning on the power,
    check the wiring connections once more.
     
        • 
    • •  • 
    For standard installation
    (System example)
     1. The main power is turned on while the indoor-outdoo r
    transmission wires are not connected (open circuit at
    section A)
    Symptom:
    Remote control unit... “CHECK” flashes
    NOTE:
    Indoor unit... LED2 on printed circuit board flashes
    Outdoor unit... LED3 and LED7 on printed circuit board
    flash
     2. The main power is turned on while the indoor-outdoo r
    power supply wires are not connected (open circuit at
    section B)
    Symptom:
    Remote control unit... Display of “No power supply”
    NOTE:
    Indoor unit... No display
    Outdoor unit... LED3 and LED7 on printed circuit board
    flash
     3. The main power is turned on while the remote control
    unit connection cord is not connected (open circuit at
    section C)
    Symptom:
    Remote control unit... Display of “No power supply”NOTE:
    Indoor unit... LED1 on printed circuit board stays
    illuminated
    Outdoor unit... LED1 on printed circuit board stays
    illuminated
    (When remote controldisplay shows “Power supply ”)
    (When remote controldisplay shows “No power supply ”)
    Remedy
     1. Turn off the main power.
    ↓
     2. Conne ct the disconnected wire correctly.
    ↓
     3. Turn on the main power.
    ↓
     4. After 1 minute, start the operation using the remote
    control.
    (Indoor unit operation will start according to the remote
    control setting.)
    (Outdoor unit operation will start after 3-5 minutes.)
    NOTE:
    The “CHECK” display on theremote control and the
    flashing of LEDs on the printed circuit boards will not occur
    immediately. They will appear 3-6 minutes after the main
    power is turned on.
    24 TROUBLESHOOTING
    54 
    						
    							 1. The main power is turned on while the transmission
    wires between the indoor unit(s) are not connected
    (open circuit at section A)
    Symptom:
    Nothing abnormal appears on the remote control
    display . If operation is started in this condition, the
    combination of the 50BB outdoo r unit and the 14BB4
    indoor unit (master unit) will result in abnormal
    operation.
    ↓
    If operation continues, an abnormality will occur on the
    refrigeration cycle and operation will stop.
     
        − 
    − −  − 
    Remote control... “CHECK” flashes
     
        − 
    − −  − 
    Indoor unit (master)... The LEDs on the printed
    circuit board flash and operation stops
     
        − 
    − −  − 
    Indoor unit (slave)... LED1 on the printed circuit
    board illuminates and the unit does not operate at all
     
        − 
    − −  − 
    Outdoor unit... The LEDs on the printed circuit board
    flash and operation stops
     2. The main power is turned on while the power supply
    wires between the indoor unit(s) are not connected
    (open circuit at section B)
    Symptom:
    Same as above. If operation continues, an abnormality
    will occur on the refrigeration cycle and operation will
    stop.
    ↓
     
        − 
    − −  − 
    Remote control... “CHECK” flashes
     
        − 
    − −  − 
    Indoor unit (master)... The LEDs on the printed
    circuit board flash
     
        − 
    − −  − 
    Indoor unit (slave)... The LEDs on the printed circuit
    board do not illuminate and the unit does not
    operate at all
     
        − 
    − −  − 
    Outdoor unit... The LEDs on the printed circuit board
    flash and operation stops
     3. The main power is turned on while the remote controlconnection cord is not connected (open circuit at section
    C)
    Symptom:
     
        − 
    − −  − 
    Remote control unit.. . Display of “No powersupply ”
     
        − 
    − −  − 
    Indoor unit (master)... LED1 on the printed circuit
    board stays illuminated and the unit does not
    operate
     
        − 
    − −  − 
    Indoor unit (slave)... LED1 on the printed circuit
    board stays illuminated and the unit does not
    operate
     
        − 
    − −  − 
    Outdoor unit... LED1 on the printed circuit board
    stays illuminated and the unit does not operate
    Remedy
     1. Turn off the main power.
    ↓
     2. Conne ct the disconnected wires correctly.
    ↓
     3. Turn on the main power.
    ↓
     4. After 1 minute, start the operation using the remote
    control.
    (Indoor units’ operation will start according to the remote
    control setting.)
    (Outdoor unit operation will start after 3-5 minutes.)
    If slave units do not operate even after the wiring has been
    corrected (automatic addressing is not possible)
     1. Check that DIP switches 1 to 4 and DIP switch 8 are all
    set to OFF, and then stop operation.
    ↓
     2. Press the ADDRESS RESET button(SW3) at the
    outdoo r unit for approximately 4 seconds
    (The self-diagnosis LEDs 2 to 8 will illuminate in order,
    and the system is reset once they are all illuminated.)
    The above procedure cannot be used to carry out automatic
    address resetting during group control.
    55 
    						
    							 1. The main power is turned on while the transmission
    wires between the indoor unit and the outdoor unit are
    not connected (open circuit at section A)
    Symptom:
    Operation of indoor unit No. 1 and indoor unit No. 3 is
    possible.
    However, “CHECK” flashes in the remote controldisplay
    for 3-5 minutes after the main power is turned on.
     
        − 
    − −  − 
    Remote control... “CHECK” flashes
     
        − 
    − −  − 
    Indoor unit No. 2... LED2 on the printed circuit board
    flashes (both master and slave units)
     
        − 
    − −  − 
    Outdoor unit No. 2... LED3 and LED7 on the printed
    circuit board flash
     2. The main power is turned on while the power supply
    wires between the indoor units are not connected (open
    circuit at section B)
    Symptom:
    Operation of indoor unit No. 1 and indoor unit No. 3 is
    possible
    However, if operation is then started in this condition,
    the combination of the 28BB outdoo r unit and the 14BT
    indoor unit (master unit) will result in abnormal operation
    of indoor unit No. 2.
    ↓
    If operation continues, an abnormality will occur on the
    refrigeration cycle and operation will stop
     
        − 
    − −  − 
    Remote control... “CHECK” flashes (indoor unit No.
    2 abnormality)
     
        − 
    − −  − 
    Indoor unit No. 2... LED2 on the printed circuit board
    flashes (both master and slave units)
     
        − 
    − −  − 
    Outdoor unit No. 2... The LEDs on the printed circuit
    board flash
     3. The main power is turned on while the remote control
    connection cord is not connected (open circuit at section
    C)Symptom:
    Nothing abnormal appears on the remote control
    display , and operation of indoor unit. No. 1 and indoor
    unit No. 2 is possible.
    However, indoor unit No. 3 cannot be operated.
     
        • 
    • •  • 
    Remedy
     1. Turn off the main power.
    ↓
     2. Conne ct the disconnected wires correctly.
    ↓
     3. Turn on the main power.
    ↓
     4. After 1 minute, start the operation using the remote
    control.
    (Indoor units’ operation will start according to the remote
    control setting.)
    (Outdoor units’ operation will start after 3-5 minutes.)
    If slave units do not operate even after the wiring has been
    corrected (automatic addressing is not possible)
     1. Check that DIP switches 1 to 4 and DIP switch 8 are all
    set to OFF, and then stop operation.
    ↓
     2. Press the “AIR SWING AUTO”, “OPERATION ” and “A/C
    No.” buttons simultaneousl y.
    The addresses will be momentarily reset, and then
    automatic address setting will be carried out once more.
    The above procedure cannot be used to carry out automatic
    address resetting of twin/triple control.
    (Note on automatic address setting)
    The printed circuit boards automatically store the connected
    system configuration when power is supplie d. As a result,
    once the power has been turned on for these printed circuit
    boards, the units can not be changed about within the
    system, even if the units are of the same model and have
    same capacity.
    56 
    						
    							 1. Automatic address setting (don’t need to set dip-switch)
    If the wiring is connected properly as above example, the
    address is set automatically by the main powersupply . An
    indoor unit with remote control will be set as the master. If
    the power source is installe d to indoor units and outdoo r
    units separately, turn on the switch by following the
    procedure: outdoor unit, then indoor unit with control, and
    finally other indoor units.
    When theslave units do not operate (when address cannot
    be set)
     1. Automatic address setting (don’t need to set dip-switch)
    If the wiring is connected properly as above example, the
    AC numbe rs are set automatically by the main power
    supply. An indoor unit withremote control will be set as the
    master.
    If the power source is installe d to indoor units and outdoo r
    units separately, turn on the switch by following theReset the address by following the procedure:
     a. After making sure that dip-switches No. 1 to 4 and No.
    8 are OFF, stop the operation.
     b. Push address reset button(SW3) on theoutdoor unit
    PC board for 4 seconds. Self-diagnosis LED No. 2 to 8
    will start blinking in order. And when all 7 pieces of LEDs
    (No. 2 ~ 8) are illuminated, the address for the slave unit
    has been reset.
    Important:The address for the group control cannot be
    reset, using the above mentioned procedure.
     2. Manua l address setting (by dip-switchDSW1)
    Whensetting the address manua lly, set the dip-switch of
    the PC board of the indoor unit as follows:
    procedure: outdoor unit, then indoor unit with control, and
    finally other indoor units. The AC numbe r will be set at
    random.
    When theslave units do not operate (when address cannot
    be set)
    57 
    						
    							Reset the address by following the procedure:
     a. Make sure that dip-switches No. 1 to 4 and No. 8 are
    OFF, stop the operation.
     b. Simultaneously, push buttons “AIR SWING AUTO”,
    “OPERATION ” and “A/C No.”. The address will be reset
    and new address will be set.
    Important:The address for the Twin/Triple control cannot
    be reset, using the above mentioned
    procedure.
     2. Manua l address setting (by dip-switchDSW1)
    Whensetting the address manua lly, set the dip-switch of
    the PC board of the indoor unit as follows:
     3. Manua l address setting (by dip-switchDSW1)
    Whensetting the address manua lly, set the dip-switch of
    the PC board in the indoor unit as follows:
    Procedures of deleting memory for twin/triple control
    system
     1. Switch off the main power supply.
     2. Set the No. 8 pin of dip switch (DSW1) at the indoor unit’s
    P.C. board to “ON” position.
     3. Switch on the main power supply for a minute and then turn
    it off.
     4. Set the No. 8 pin of dip switch (DSW1) to “OFF” position.
    Procedures of deleting memory for group control system
     1. Switch off the main power supply.
     2. Set the No. 1 until No. 4 pin of dip switch (DSW1) at the
    indoor unit’s P.C. board to “ON” position.
    (Make sure No. 8 pin of dip switch (DSW1) is at “OFF”
    position)
     3. Switch on the main power supply for a minute and then turn
    it off.
     4. Set the No. 1 pin until No. 4 pin of dip switch (DSW1) to
    “OFF” position.
    (Important notice)
    Above procedures are meant for deletin g memory on indoor
    unit’s P.C. board. And it is not for Address reset.
    Indoor unit P.C. board layout
    Below drawing shows the location of dip switch 1(DSW1) on
    the indoor unit P.C. board.
    Dip switch 1 (DSW1). [to be used for manual setting]
    58 
    						
    							Emergencyoperation
     
        • 
    • •  • 
    Emergency operation of outdoor unit
    Emergency operation can be carried out by setting the
    DSW1switch on the printed circuit board of the outdoor
    unit to the EMERGENCY position. However, emergency
    operation is only carried out when an abnormality is
    detected by the indoor/outdoor temperature thermistors.
    The resistance values of each thermistor are measured
    as shown in the table below to determine if there is an
    abnormality.
    Thermistor resistance table
    Temperatu reResistance value (kΩ
    )±5%
    Room temperature
    thermistorPipe temperature
    thermistor
    -20°C205.8197.8
    -10°C114.6111.9
    -5°C87.385.4
    0°C67.065.8
    5°C51.851.0
    10°C40.439.9
    15°C31.730.7
    20°C25.125.0
    25°C20.020.0
    30°C16.116.0
    40°C10.410.6
    50°C6.97.1
    60°C4.74.9
    70°C----3.5
    80°C----2.5
    90°C----1.8
    100°C----1.4
    The pipe temperature thermistor resistance value are
    the same for the indoor and outdoor units.
    
     
        − 
    − −  − 
    Set only the thermistor which shows an abnormality
    to the condition as shown in the table below to carry
    out emergency operation.
    ThermistorCooling modeHeating mode
    Indoor unitRoom temperatureFixed at 25°C
    Pipe temperatureShortedOpen
    ThermistorCooling modeHeating mode
    Outdoor unitDischarge temperatureOpenShorted
    Heat exchanger outlet
    temperatureShortedOpen
     
        − 
    − −  − 
    Refer to the circuit diagram for the connection
    locations for each thermistor.
     
        − 
    − −  − 
    If there is an abnormality in the roomtemperature
    thermistor, the temperature will be fixed at 25°C
    regardless of the remote controldisplay .
    NOTE:
     
        − 
    − −  − 
    Any abnormalities detected by the temperature
    thermistors are ignored during emergency operation,
    therefore, long-term operation in this mode should
    be avoided.
     
        − 
    − −  − 
    After emergency mode operation has been
    completed and normal operation is to be resumed,
    turn off the power supplie s for the indoor and
    outdoor units and set theDSW1switch to NORMAL
    position.
     
        − 
    − −  − 
    Self-diagnosis LEDs 4 to 6 will flash during
    emergency operation.
    25 EMERGENCY OPERATION
    59 
    						
    							26 CONTROL
    Description of basic Functions
    26.1. Cooling mode operation time chart
    (*1)
    Outdoor unit fan start control during cooling
    At the start of cooling mode and drying mode operation, the outdoo r unit heat exchan ger outlet temperature is detected in order
    to set the fan speed.
    Operation is carried out at the fan speed detected for 30 seconds.
    After 30 seconds, the heat exchan ger outlet temperature is detected and the outdoo r unit fan speed is changed automatically .
    (*2)
    Cooling low outdoor temperature protection
    When theoutlet temperature of the heat exchan ger drops to less than 12°C for a continuous period of 10 minutes, the outdoor unit
    stops.
    This is cancelled after 3 minutes (re-start prevention)
     
        • 
    • •  • 
    Remote control display s and indoor unit operation continue during thistime.
     
        • 
    • •  • 
    The 10 minutes countdown is cleared if the compressor stops or if the temperature at the outdoor unit outlet rises to 13.5°C or
    higher.
    60 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual