    							 1 SERVICE INFORMATION 3
     2 FEATURES 
    4
     3 SPECIFICATION (HEAT PUMP TYPE ) 
    9
     4 SPECIFICATION (COOLING ONLY TYPE ) 
    10
     5 TECHNICAL DRAWING 
    11
     6 CIRCUITDIAGRAM 
    13
     7 OPERATING INSTRUCTION 
    25
     8 REFRIGERATION CYCLE 
    27
     9 OPERATIO N RANGE 
    28
     10  PIPE LENGTH 
    29
     11  OPERATING CHARACTERISTIC 
    31
     12  FAN PERFORMANCE 
    32
    © 2002 Matsushita Industrial Corporation. Sdn. Bhd.
    (11969-T). All rights reserved. Unauthorized copying
    and distribution is a violation of law.
    CS-W50BTP CU-V50BBP8
    CS-W50BTP CU-W50BBP8
     13  SAFETYDEVICE 33
     14  COMPONENT SPECIFICATION 
    34
     15  CAPACITY AND POWERCONSUMPTION 
    35
     16  DISCHARGE AND SUCTION PRESSURE 
    38
     17  REACHING DISTANCE 
    39
     18  SOUNDDATA 
    40
     19  TWIN AND TRIPLE 
    42
     20  WIRING MISTAKE PREVENTION 
    47
     21  TEST OPERATIO N AND SELF DIAGNOSIS 
    48
     22  SETTING OF SAVEENERGY AND THERMISTOR SWITCH 
    52
     23  GROUP CONTROL 
    53
     24  TROUBLESHOOTING  
    54
    AIR CONDITIONER
    CONTENTS
     Page  Page
    ORDER NO. MAC0210059C2 
    						
    							 25  EMERGENCY OPERATIO N 59
     26  CONTROL 
    60
     27  WIRED REMOTE CONTROLINSTALLA TION MANUAL 
    70
     28  WIRELESS REMOTE CONTROLINSTALLA TION MANUAL 
    75 29  INSTALLA TION (INDOOR UNIT) 
    82
     30  INSTALLA TION (OUTDOOR UNIT) 
    92
     31  REPLACEMENT PARTS 
    104
    2 
    						
    							1 SERVICE INFORMATION
    Caution:
    OPb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
    a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
    OPb free solder will tend to splash when heated too high (about 1100° F/600°C).
    Notice of Address setting for NEW Ceiling / NEW Outdoor Unit.
    The new Ceiling / new Outdoor models are possible to have address setting fortwin / triplecontrol or group control
    automatically when main powersupply is switched on.
    (Manual address setting is also possible by usingDSW1 switch on the indoor unit P.C. board.) However,this address setting is
    onlypossible when proper wiring connection is made and indoor unit must be of original unit
    .
    1.1. Example of trouble during test operation
    If the below phenomenon is found during test operation, wrong address setting is possible.
    Theref ore, please inspect the address setting.
     1. LCD display of the wiredremote control is not illuminated although the main powersupply switch is ‘on’.
     2. LCD display had indicated as normal illumination when power supply switch is ‘on’, however outdoo r unit cannot be operated.
    (But, it is necessary to take 3 to 5 minutes for outdoor unit to start from the timing of remote control OFF/ON button is ‘on’.)
    (For normal operation, the outdoor unit will only start its operation after 3 to 5 minutes upon pressing the OFF/ON button.)
     3. P.C. board had memorized wrong setting information.
     a. If main power supply is switched on with the wrong connection.
     b. Whenchanging the connection or combination of units due to re-installation etc.
     
        • 
    • •  • 
    W hen changing the system from twin to triple (triple to twin).
     
        • 
    • •  • 
    W hen changing the system from group control to normal one to one system.
     
        • 
    • •  • 
    W hen making the replacement of units of master and slave etc.
    1.2. Caution during test operation
    Do not touch the remote control button and do not change any wirings for one minute when the main powersupply switch is ‘on’.
    (Because the unit is having automatic address setting during the first one minute.)
    1.3. Caution during automatic address setting
    When the mainpower supply switch is ‘on’, the P.C. board willautomatically memorize the connecting system.
    Consequently , when initial power supply is ‘on’, there mustn’t be any interchanging of units even of the same type andsame
    capacity unit.
    Theref ore, connection of the unit to another system is prohibited.
    3 
    						
    							2.1. New design
    2.1.1. Gentle curved styling
     
        • 
    • •  • 
    The base has gentle curves which express a functional
    beauty . It spreads the air quietly over a wide area.
    2.2. Such quietness!
    2.2.1. Several new mechanism add up to
    low 49 dB noise (W50BT - High
    Fan Speed)
     1. Delta throat fan
    A delta throat (projection) has been attached to the fan
    outlet to suppress the generation of vortexes. This helps
    maintain air flow speed even at lower fan speeds and is
    effective in reducing noise.
     2. Reflux orifice
    The orifice at the intake port is equipped with an air flow
    guide which minimizes the flow disturbances which occur at
    the orifice and inside the impeller.
    This reduces pressure losses inside the casing and also
    helps reduce noise.
     3. Adoption of wing-shaped vanes
     
        • 
    • •  • 
    The vanes of the fan have been changed to
    “aerodynamic ” shaped vanes, so that the air flow more
    smoothly over the vane surfaces and noise is thus
    suppressed.
     
        • 
    • •  • 
    Side filters have been adopted in the pipe partitions.
    These allow the air intake space to be increased and
    also further reduce noise.
    2.2.2. Automaticswinging louvre
     
        • 
    • •  • 
    The horizon tal air flow angle is a wide 100 degrees
    (manual). The louvre can swing automatically (through 70
    degrees vertically) using theremote control. This increases
    the area of comfortable air flow and warms the air even to
    floor level.
    2.2.3. Newly-shaped louvre
     
        • 
    • •  • 
    The newly-shaped louvre and air outlet effectively distribute
    the air flow. During cooling, this stops warm air from
    collecting near the louvre, and prevents freezing.
    2 FEATURES
    4 
    						
    							2.3. Easy installation
    2.3.1. Easy suspension
     
        • 
    • •  • 
    A suspension bolt fixing bracket with 4-point support is
    attached to the main unit, which increases the space
    available for installa tion.
    2.3.2. Two installation methods :
    standard andwall
     
        • 
    • •  • 
    In additio n to the standard (1) ceiling installa tion, a wall (2)
    installa tion method (using a wall-hanging bracket) is
    available for cases where the ceiling is too high for the main
    unit to be suspended.
    2.4. Piping
    2.4.1. 3-direction pipe lead-out
     
        • 
    • •  • 
    The refrigerant piping can lead out in one of three directions
    (right, rear-right and top-right), and the drain pipe direction
    can be selected from four directions (right, rear-right, left
    and rear-left).
    2.5. Easy maintenance
    2.5.1. Long life filter (standard
    equipment)
     
        • 
    • •  • 
    In general office environments, cleanin g (maintenance ) is
    not required until after approximately 2,500 hours of
    operation, thus reducing maintenance work.
     
        • 
    • •  • 
    For optimum comfort, it is recommended to clean the air
    filter every 1-1/2 months.
    2.5.2. Maintenance is possible from
    underneath the unit.
     
        • 
    • •  • 
    If the bottom panel is detached, the drain pan can then be
    removed and installe d from underneath the unit, and
    inspection and servicing of component such as the control
    panel also becomes easier.
    2.6. Auto fan mode (indoor unit)
     
        • 
    • •  • 
    Auto fan mode is added beside s high, medium and low. It
    automatically adjusts the fan speed according to the indoor
    unit’s temperature.
    2.7. Hot start system (heat pump
    models)
    2.8. Automatic changeover
    function (heat pump models)
     
        • 
    • •  • 
    The unit automatically switches between cooling and
    heating in accordance with operating load in order to
    maintain a comfortable indoor temperature.
    5 
    						
    							2.9.1. Product features
     
        • 
    • •  • 
    Low-noise design improves comfort in surrounding
    areas
     1. The noise-suppressing winglet fan is a result of new
    research into vane design theory. The unique curved
    shape suppresses the generation of vortexes, thus
    reducing air flow noise.
     2. The adoption of double -orifice rings reduces air
    passage resistance.
     3. Strengthening of the noise insulation materials in the
    compressor and the sealing-in of mechanical noise
    allows vibration noise to be greatly enclosed and
    suppressed.
     4. The heat exchan ger has an L-shaped design to allow air
    to flow more smoothly.
     5. Noise is automatically reduced further during night-time
    operation with lower outdoor air temperatures.
    2.10. Greatly improved workability
    increases system renewal
    capability
     
        • 
    • •  • 
    Pipes that are one size larger can also be connected for
    renewal.
     
        − 
    − −  − 
    If renewing the system, existing refrigerant pipes can be
    utilized so that only the indoor and outdoo r units need to
    be replaced.
     
        − 
    − −  − 
    For example, liquid and gas pipesfrom 10years ago
    can be connected to current pipes with the same size or
    one size larger. Effective utilization of materials reduces
    working time and trouble. (Adaptor sockets are not
    supplie d.)
    2.9. Low-noise outdoor units
    6 
    						
    							 
        • 
    • •  • 
    Additional refrigerant charging unnecessary for 30 m
     
        − 
    − −  − 
    All models do not require any additio nal charging of
    refrigerant for 30 m of pipe length. This makes
    installa tion much easier.
     
        • 
    • •  • 
    Drain water dripping-prevention structure
     
        − 
    − −  − 
    The base of the outdoo r unit is provided with a single
    drain hole in order to prevent drain water from leaking
    out of the unit. By connecting a drain elbow and a
    discharge pipe, water leakages can be prevented even
    when the unit is installe d to a wall.
     
        • 
    • •  • 
    Save space design allows units to be installed side-by-
    side continuously
     
        − 
    − −  − 
    Servicing after installa tion can be carried out by
    removing the front covers.
     
        • 
    • •  • 
    Long pipe design for refrigerant pipes
     
        − 
    − −  − 
    Maximum piping length of 50m for all models.
     
        • 
    • •  • 
    Internal pipe connection
     
        − 
    − −  − 
    Pipes are connected inside the units (inside the side
    covers), making the final appearance more attractive.
     
        − 
    − −  − 
    Pipes can be diverted outward in any of four directions
    (forward, right, down, rear).
     
        − 
    − −  − 
    Small liquid pipe diameters of 9.52mm for 50BB models,
    making installa tion work much easier.
     
        • 
    • •  • 
    Centralized draining method
     
        − 
    − −  − 
    Even when multiple outdoo r units are installe d to a wall,
    the drain outlets can be concentrated into a single drain
    pipe. This makes installa tion easier and also improves
    appearance.
    2.11. A brand-new control method
    using the latest in technology
     
        • 
    • •  • 
    Easier power supply wiring connection
    Power supply wiring and other wiring tasks can be carried
    out more easily.
     
        − 
    − −  − 
    Twin non-polar wires used to connect indoor and
    outdoor units.
     
        − 
    − −  − 
    Adoption of connection error prevention circuits for drive
    wires and signal wires. If a connection error is made, the
    relay does not operate and current does not flow to the
    circuit boards.
     
        • 
    • •  • 
    Twin and Triple operation
     
        − 
    − −  − 
    Simultaneous air conditioning of wide spaces and
    corners is possible. Indoor units of different
    horsepowers can even be used in combination.
     
        − 
    − −  − 
    Master unit and slave-units can be set automatically in
    twin and triple systems. No address setting is
    necessary.
     
        − 
    − −  − 
    Multiple indoor units can be operated simultaneousl y
    with a single remote control. Note that individual
    operation is not possible.
     
        • 
    • •  • 
    Separate indoor/outdoor unit power supplies
    The power supply can be connected to (1) just the outdoo r
    units, or (2) to both the indoor and outdoor units.
     
        • 
    • •  • 
    Easy test operation
    Test operation can be carried out for both indoor and
    outdoor units.
     
        • 
    • •  • 
    Automatic setting initialization function
    (Remote control
    and Indoor unit)
    In accordance with the indoor and outdoor units connected
    and the connection methods, conditions such as the
    connection configuration (twin or triple format) and remote-
    control functions such as automatic louvre operation and
    cooling or heating mode are automatically detected and set
    instantly.
    7 
    						
    							2.12. Wired Remote Control
     
        • 
    • •  • 
    The new design include s an easily- visible red pilot lamp.
    The power can be turned on and off at a single touch,
    without openin g the cover.
     
        • 
    • •  • 
    Has a built-in thermistor, allowing indoor temperature
    detection in accordance with indoor conditions by switching
    with main unit thermistor.
     
        • 
    • •  • 
    Twin non-polar wires make installa tion work easy. (10 m
    cable supplie d as accessory.)
    2.13. Wireless Remote Control
     
        • 
    • •  • 
    New design with compact size. (Operation range within
    approximately 8 m.)
     
        • 
    • •  • 
    Built-in timer with ON/OFF timer setting (within 24 hours)
    WiredWireless
    Heat PumpCZ-RD51PCZ-RL51P
    CoolingCZ-RD51PCZ-RL01P
    NOTE: Both of the above remote control is packed separately
    from the indoor unit.
    2.14. Group Control Equipment
    8 
    						
    							3 SPECIFICATION (HEAT PUMP TYPE )
    CS-W50BTP / CU-W50BBP8
    ITEM / MODELIndoor UnitOutdoor unit
    Main BodyCS-W50BTPCU-W50BBP8
    RemoteCZ-RD51P (Wired)
    ControlCZ-RL51P (Wireless)
    Cooling CapacitykW14.0
    BTU/h47,700
    Heating CapacitykW16.0
    BTU/h54,600
    Refrigerant Charge-lessm30
    Standard Air Volume for High Speedm3/min35
    cfm1236
    Outside Dimension (H x W x D)mm250 x 1600 x 7001220 x 1100 x 320
    inch9-27/32 x 62-31/32 x 27-9/1648-1/24 x 43-5/16 x 12-19/32
    Net Weightkg47115
    lbs104254
    Piping
    ConnectionRefrigerantGasmm (inch)O.D Ø 19.05 (3/4) Flared Type
    Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type
    DrainmmO.D Ø 20I.D Ø 20 x 1
    CompressorType, Number of Set-Hermetic-1 (Scroll), 1
    Starting Method-Direct on-line starting
    MotorType-2-pole 3-phase induction motor
    Rated OutputkW-4.10
    FanType, Number of SetSirocco fanPropeller fan
    MotorType4-pole single phase induction motor6-pole single phase induction motor
    Rated OutputkW0.140.055 x 2
    Air-heat ExchangerSlit-fin typeX-Louvre-fintype
    Refrigerant ControlCoolCapillary tube-
    Heat-Capillary tube
    Refrigerant Oil (Charged)litre-MMMAPOE
    Refrigerant (Charged)kg-R407C (4.4)
    (oz)(155)
    Running
    AdjustmentControl SwitchWireless or Wired RemoteControl-
    Room Temperatu reThermosta t (Main Body)-
    Safety DevicesInternal protector for compressor, Internal thermostat for fan motor,
    Crankcase heater, High and heating pressure switch, Current transformer
    Noise LeveldB (A)Hi 49 Lo 45Cooling 56, Heating 58
    Power level dBCooling : Hi 66 Lo 62
    Heating : Hi 66 Lo 62Cooling 69, Heating 71
     1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
    temperature of 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.)
     2. Heating capacities are based on indoor temperature of 20°C D.B. (68°F D.B.) and outdoor air temperature of 7°C D.B.
    (44.6°F D.B.), 6°CW.B.(42.8°F W.B.)
    ELECTRICAL DATA (50Hz)
    ITEM / MODELCS-W50BTP, CU-W50BBP8
    Condition by JIS B 8615
    VoltsV380400415
    Phase3N3N3N
    Power ConsumptionkWCool5.355.355.35
    Heat5.455.455.45
    Running CurrentACool9.29.29.2
    Heat9.29.29.2
    Starting CurrentA696969
    Power Factor%Cool888481
    Heat908682
    *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
    PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz
    9 
    						
    							4 SPECIFICATION (COOLING ONLY TYPE )
    CS-W50B TP / CU-V50BB P8
    ITEM / MODELIndoor UnitOutdoor unit
    Main BodyCS-W50BTPCU-V50BBP8
    RemoteCZ-RD51P (Wired)
    ControlCZ-RL01P (Wireless)
    Cooling CapacitykW14.0
    BTU/h47,700
    Refrigerant Charge-lessm30
    Standard Air Volume for High Speedm3/min35
    cfm1236
    Outside Dimension (H x W x D)mm250 x 1600 x 7001220 x 1100 x 320
    inch9-27/32 x 62-31/32 x 27-9/1648-1/24 x 43-5/16 x 12-19/32
    Net Weightkg47112
    lbs104247
    Piping
    ConnectionRefrigerantGasmm (inch)O.D Ø 19.05 (3/4) Flared Type
    Liquidmm (inch)O.D Ø 9.52 (3/8) Flared Type
    DrainmmO.D Ø 20I.D Ø 20 x 1
    CompressorType, Number of Set-Hermetic-1 (Scroll), 1
    Starting Method-Direct on-line starting
    MotorType-2-pole 3-phase induction motor
    Rated OutputkW-4.10
    FanType, Number of SetSirocco fanPropeller fan
    MotorType4-pole single phase induction motor6-pole single phase induction motor
    Rated OutputkW0.140.055 x 2
    Air-heat ExchangerSlit-fin typeX-Louvre-fintype
    Refrigerant ControlCapillary tubeCapillary tube
    Refrigerant Oil (Charged)litre-MMMAPOE
    Refrigerant (Charged)kg-R407C (4.4)
    (oz)(155)
    Running
    AdjustmentControl SwitchWireless or Wired RemoteControl-
    Room Temperatu reThermosta t (Main Body)-
    Safety DevicesInternal protector for compressor, Internal thermostat for fan motor,
    Crankcase heater, High pressure switch, Current transformer
    Noise LeveldB (A)Hi 49 Lo 4556
    Power level dBHi 66 Lo 6269
     1. Cooling capacities are based on indoor temperature of 27°C D.B. (80.6°F D.B.), 19.0°C W.B. (66.2°F W.B.) and outdoor air
    temperature of 35°C D.B. (95°F D.B.), 24°CW.B.(75.2°F W.B.)
    ELECTRICAL DATA (50Hz)
    ITEM / MODELCS-W50BTP, CU-V50BBP8
    Condition by JIS B 8615
    VoltsV380400415
    Phase3N3N3N
    Power ConsumptionkWCool5.355.355.35
    Running CurrentACool9.29.29.2
    Starting CurrentA696969
    Power Factor%Cool888481
    *Power Factor means total figure of compressor, indoor fan motor and outdoor fan motor.
    PanasonicPower sourceAC, 3N~380V, 400V, 415V 50Hz
    10 
    						