Home > Panasonic > Air Conditioner > Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual

Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 10737 Panasonic manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							41 
    						
    							19.1. Twin and Triple Operation
     
        • 
    • •  • 
    Simultaneous air conditioning of wide spaces and corners is
    possible. Indoor units with different horsepowers can even
    be used in combination.
     
        • 
    • •  • 
    The master unit and slave units are set automatically when
    the power is turned on. At this time, the indoor unit which is
    connected to the remote control unit becomes the master
    unit.
    (If automatic setting is not possible, carry out the settings
    manua lly.)
     
        • 
    • •  • 
    No distinction is made between master unit and slave units
    (slave unit 1 and slave unit 2) at the indoor unit or remote
    control.
     
        • 
    • •  • 
    Install the remote control to the master unit. (It cannot be
    connected to slave units.)
    If indoor unit models with louvres and models without
    louvres have been connected together, use an indoor unit 
        • 
    • •  • 
    Master unit and slave-units can be set automatically in twin
    and triple systems. No address setting is necessary.
     
        • 
    • •  • 
    Multiple indoor units can be operated simultaneousl y with a
    single remote control unit. Note that individual operation is
    not possible.
    with louvres as the master unit.
     
        • 
    • •  • 
    The remote control termostat can also be set.
     
        • 
    • •  • 
    Optional circuit boards can only be installe d to the master
    unit.
     
        • 
    • •  • 
    Setting the master unit and slave units can also be carried
    out manua lly by using DIP switches. However, manua l
    settings will alwaystake priority. If you have made manua l
    settings but would like to return to using automatic settings,
    set all slave unit DIP switches (refer to the table below) to
    the OFF position, and then press the ADDRESS RESET
    button on the outdoor unit (SW3 on the outdoor unit printed
    circuit board).
    (Do not mix manua l settings and automatic settings.)
    19 TWIN AND TRIPLE
    19.1.1. Twin and triple operation setting
    42 
    						
    							19.1.2. Automatic address setting fortwin
    and triple systems
    Procedure: Turn on the power supply for the indoor
    and outdoor units.
    Operation: Automatic address setting will start 10 to
    30 seconds after the power supply is
    turned on, and will be completed after
    about 1 minute.
    If the power supplies for the indoor unit and outdoor unit cannot be
    turned on at the same time, turn on the power supply for the outdoor
    unit, the indoor unit which is connected to the remote control, and then
    the other indoor units in that order.
    If the order of turning on the power supply is incorrect, the master unit
    setting may overlap. In such a case, turn on the power supplies for all
    units in the correct order as given above, or carry out a twin/triple
    automatic address reset (press dip switch 3 on the outdoor unit
    continuously for 4 seconds or longer).
     
        • 
    • •  • 
    The indoor unit which is connected to the remote control will
    have priority for becoming the master unit.
     
        • 
    • •  • 
    The master unit thermostat will be used as the indoor
    temperature thermostat. If the master unit thermostat is
    turned on, the slave unit thermostats cannot be adjusted
    even if they happen to be on.
     
        • 
    • •  • 
    If address setting using the DIP switches is carried out after
    automatic address setting has been carried out, use DIP
    switch No. 3(SW3) on theoutdoo r unit to carry out
    automatic address resetting.
     
        • 
    • •  • 
    If you would like to designate a particular indoor unit as the
    master unit because no master unit has been set, use the
    DIP switches on the slave units to make setting.
    If automatic address setting is carried out once and then the slave unit
    address are set, the address will then be stored inside the EEPROM.
    Thus it is not necessary to repeat automatic address setting if the
    power is turned off and back on again.
    19.1.3. DIP switch settings for twin/triple
    slave unit addresses
    Procedure: Turn off the power supply, and then set
    DIP switch 1-8 to ON.
    The unit will become slave unit 1.
    (Set DIP switches 1-1 and 1-8 both to
    ON.
    The unit will become slave unit 2.)Turn on the power supply.
    Operation: The unit will operate as slave unit 1.
    Automatic address setting is not carried
    out at this time.
    If the setting is made while the power is still turned on, it is easier to
    mis-combine the setting with group settings. So, the setting should be
    made while the power is turned off.
     
        • 
    • •  • 
    Only slave unit addresses can be set in this way. Master
    unit setting is not possible.
     
        • 
    • •  • 
    If you make the DIP switch settings after the power has
    been turned on, carry out twin/triple automatic address
    resetting.
     
        • 
    • •  • 
    Be sure to set DIP switch 1-8 to ON when setting twin/triple
    addresses. If DIP switch 1-1 is set to ON without setting 1-
    8 to ON, group addresses will be set instead, and the
    remote control open circuit error code (F26) will be
    display ed.
    19.1.4. Automatic address resetting for
    twin/triple systems
    Function: 
        • 
    • •  • 
    This reset the current twin/triple
    addresses which have been set
    automatically , and result in the
    reoccurance of automatic twin/triple
    address settings.
    Procedure: Press the ADDRESS RESET button SW3
    (push button switch) on the outdoor unit
    circuit board continuously until LEDs 2 to
    8 on the outdoo r unit circuit board are all
    illuminated (takes approximately 3.5
    seconds).
    Operations: The outdoor unit will reset the addresses
    for the indoor units which it is connected
    to, and will send an instruction to carry
    out automatic address setting again. If
    the indoor unit DIP switch have not been
    manua lly set for twin/triple address
    setting, the indoor units receive this
    command and clear their existing settings
    and carry out automatic address setting.
    If an indoor unit has had its address set by the DIP switch (DIP switch
    1-8 is ON), or if the remote control unit is connected to one of the
    indoor unit, then the addresses for those indoor units cannot be reset.
    43 
    						
    							 
        • 
    • •  • 
    The indoor units will not run for approximately 1 minute
    while automatic twin/triple address resetting is being carried
    out.
    Note: 
        • 
    • •  • 
    Do not turn off the power supply for at least 1 minute after
    automatic twin/triple address resetting has been carried out.
    19.2. Piping connections
     
        • 
    • •  • 
    The following table shows the pipe diameters for a twin-type system.
    Outdoor unit main pipe diameter (mm)Indoor unit combinations
    3HPIndoor unit capacity (HP)1.51.5
    Liquid side:ø 9.52Branch pipe
    diameterLiquid sideø 6.35ø 6.35
    Gas side:ø 15.88Gas sideø 12.7ø 12.7
    4HPIndoor unit capacity (HP)2.02.01.52.5
    Liquid side:ø 9.52Branch pipe
    diameterLiquid sideø 6.35ø 6.35ø 6.35ø 6.35
    Gas side:ø 19.05Gas sideø 12.7ø 12.7ø 12.7ø 15.88
    5HPIndoor unit capacity (HP)2.52.52.03.0
    Liquid side:ø 9.52Branch pipe
    diameterLiquid sideø 6.35ø 6.35ø 6.35ø 9.52
    Gas side:ø 19.05Gas sideø 15.88ø 15.88ø 12.7ø 15.88
    6HPIndoor unit capacity (HP)3.03.02.04.0
    Liquid side:ø 9.52Branch pipe
    diameterLiquid sideø 9.52ø 9.52ø 6.35ø 9.52
    Gas side:ø 19.05Gas sideø 15.88ø 15.88ø 12.7ø 19.05
     
        • 
    • •  • 
    The following table shows the pipe diameters for a triple-type system.
    Outdoor unit main pipe diameter (mm)Indoor unit combinations
    6HPIndoor unit capacity (HP)2.02.02.01.51.53.0
    Liquid side:ø 9.52Branch pipe
    diameterLiquid sideø 6.35ø 6.35ø 6.35ø 6.35ø 6.35ø 9.52
    Gas side:ø 19.05Gas sideø 12.7ø 12.7ø 12.7ø 12.7ø 12.7ø 15.88
     
        • 
    • •  • 
    The following table shows the equivalent pipe lengths and height differences for twin- and triple-type systems.
    Equivalent lengthL + la + lb + lcWithin 50 m
    Branch pipe diameterla, lb, (lc)Within 15 m
    Branch pipe differencela - lb, lb - (lc), la - (lc)Within 10 m
    Height differenceH1Within 30 mHeight difference between indoor unitsH2Within 1 m
     1. Use the main pipe to gain any rise or fall required for the pipes.
     2. The numbe r of bends should be 8 or less in a single system (L + la, L + lb, L + lc), and 15 or less overall.
     3. Branch pipes should be position horizon tally.
     
        • 
    • •  • 
    The branch pipe shoud be horizon tal to or perpendicular to the indoor unit.
    44 
    						
    							19.3. Refrigerant charging
     
        • 
    • •  • 
    For twin and triple-type systems
    The pipe length is the total of the branch pipe (L) and the junction pipes (la→
    lb→
    lc in order from the thickest diameter). At
    the point where the pipe length exceed s 30 m, determine the amoun t of refrigerant for the remaining liquid-side pipe diameters
    and pipe lengths from the following table in order to charge the system.
    45 
    						
    							20 WIRING MISTAKE PREVENTION
    Improved quality of installation work through adoption of an “Connection error prevention” circuitwhichpreven ts wiring
    mistakes
    Conne ction errors with the control wires and the power supply wires will not only contribute to burning-out of the control circuit
    board, but can also cause large-scale working losses and affect reliability. If a circuit board with a “Connection error prevention”
    circuit is used, the relay will not operate if the wires have been connected incorrectly, so that current will not flow to the control
    circuit board. This is designed principally toconpensate human error during installa tion.
    Prevention of connection errors
    These units are equipped with connection error prevention circuits. If the units do not operate, it is possible that the connection error
    prevention circuits have been operated. In such cases, check that the power supply wires (connected to terminals 1
    and 2and
    the control wires (connected to terminals 3
    and 4) are connected correctly. If they are connected incorrectly, connectthem
    correctly. Normal operation should thencommence.
     
        • 
    • •  • 
    Do not short the remote control wires to each other. (The protection circuit will be activated and the units will not operate.) Once
    the cause of the short is eliminated, normal operation will then be possible.
    NOTE:
     
        • 
    • •  • 
    W ait one minute after turning on the indoor unit power supply before operating theremote control.
     
        • 
    • •  • 
    If nothing at all appears in the remote control LCD, check the powersupply for the indoor unit.
    Refer to “TROUBLESH OOTING” chapter.
    NOTE:
    Do not allow any of the following connection, as such connection may damage the printed circuit board.
     
        • 
    • •  • 
    Do not connect anythin g except a relay to the timer input or fan speed output (connector CNT1 on printed circuit board).
     
        • 
    • •  • 
    Do not connect U-NET transmission wires to terminals 3 and 4 of the indoor and outdoor units. (*1)
     
        • 
    • •  • 
    Do not connect U-NET transmission wires to terminals A and B of the remote control.
    (1*) U-NET transmission wires are the communication wires used for the central control.
    47 
    						
    							21.1. Test operation
     
        • 
    • •  • 
    Always use a properly-insu lated tool to operate the switch
    on the circuit board. (Do not use your finger or any metallic
    object).
     
        • 
    • •  • 
    Never turn on the power supply until all installa tion work has
    been completed.
     
        • 
    • •  • 
    Turn on the circuit breaker before test operation extends
    past 12 hours.
    (The crankcase heater will be energized, which will warm
    the compressor and prevent liquid compression.)
     
        • 
    • •  • 
    For three-phase models, check that the phase is not
    reversed.
    (If the phase is reversed, the LED on the printed circuit
    board will flash.)
     
        • 
    • •  • 
    Check that the voltage is 198 V or higher when starting the
    unit. (The unit will not operate if the voltage is less than
    198V.)
     
        • 
    • •  • 
    Carry out test operation for 5 minutes or more, using the
    remote control or the switch on the outdoor unit printed
    circuit board.
     
        • 
    • •  • 
    Always carry out cooling operation first during test
    operation, even during the warm season.
    (If heating is carried out first, problems with operation of the
    compressor will result.)
    21.2. Test operation from the
    outdoor unit
    During outdoor unit emergency operation or test operation, the
    LEDs on the printed circuit board will flash.
    To cancel test operation, press the TEST RUN button once
    more while test operation is being carried out.
    (Test operation will stop automatically after 30 minutes have
    passed.)
    21.3. Test operation using the wired
    remote control
     1. Check that “COOL” is display ed on the operation mode
    display , and then press the OFF/ON button to start test
    operation.
     2. Within 1 minute of pressing the OFF/ON button, press the
    TEST RUN button.
     3. The pipe temperature (gas pipe) will then be display ed in
    the temperature setting display of theremote control.
     
        • 
    • •  • 
    During group control, the numbe r appearing in the timer
    display will change each time the air conditioner No.
    button is pressed, and the pipe temperature for the
    indoor unit correspondin g to the numbe r display ed will
    appear in the temperature setting display .
     4. Check that the temperature in the pipe temperature display
    starts dropping after operation has been continuing for
    some time.
    21 TEST OPERATION AND SELF DIAGNOSIS
    48 
    						
    							21.4. Test operation using the
    wireless remote control
     1. Within 1 minute of pressing the OFF/ON button, press to
    cooling operation and then press the TEST RUN button.
     
        • 
    • •  • 
    If more than 1 minute passes, test operation cannot be
    started. In this case, press the OFF/ON button once
    more to repeat the operation.
     
        • 
    • •  • 
    Use the OPERATION button to change the operation.
    The current operation mode will appear in the operation
    mode display .
     2. Whentest operation starts, “TEST RUN” will appear in the
    timerdisplay of the LCD, and operation will be carried out in
    accordance with the operation mode display (COOL or
    HEAT) appearing at that time.
    However, the numbe r in the temperature setting display will
    not change.
    (Cancelling test operation)
     
        • 
    • •  • 
    Press the OFF/ON button, the TEMP (UP/DOWN) button,
    the OPERATION button, the FAN SPEED button or the
    TEST RUN button to cancel test operation.
    21.5. Self-diagnosis function
     
        • 
    • •  • 
    The wired remote controldisplay and the self-diagnosis
    LEDs (red) on the outdoor unit printed circuit board indicate
    where the abnormality has occurred.
     
        • 
    • •  • 
    Recallin g the error display .
    
     
        − 
    − −  − 
    The air conditioner No. “01” appears during normal
    installa tion and use.Whenusing group control, a
    different numbe r may appear. The air conditioner No.
    can be display ed by pressing the air conditioner No.
    button.
    When an abnormality occurs at this unit, “CHECK” flashes
    in the display .
    Press the CHECK button while the display is flashing.
    The timerdisplay will change and an error codefrom F15 to
    F49 will appear in place of the time. (The temperature
    setting display will also change to show the air conditioner
    No.)
    Press the TIMER SELECT/SET button while the error is
    displayed.
    The F15 - F49 display will change to the detail display .
     
        • 
    • •  • 
    After checking the error display and the detail display , refer
    to the self-diagnosis error code table on the following page
    and check the location of the problem.
     
        • 
    • •  • 
    If the problem is repaired and operation returns to normal,
    the CHECK display on theremote control will be eliminated,
    but the self-diagnosis LED will remain illuminated until the
    operation starts again.
    49 
    						
    							How to display the past error message
    If the “CHECK” display on the wiredremote control is not
    flashing, press the CHECK button continuously for 5 seconds
    or more to display the problem details for the last problem or
    the problem before that. You can then switch between the
    display s for the previous problem and the problem before that
    by pressing the TIMERFORWARD orBACK buttons.
    (Last problem display : 1F15 - 1F49
    Second-last problem display : 2F15 - 2F49)
    Press the CHECK button once more to return to the normal
    display .An error code from 1F15 to 1F49 will bedisplay ed.
    (The temperature setting display will also change to show the
    air conditioner No.)
    If the TIMER SELEC T/SET button is pressed while the error
    code from 1F15 to 1F49 is beingdisplay ed, the display screen
    will change to show the details of the last problem display .
    (If 2F15 to 2F49 is being display ed, the details of the second-
    last problem display will appear.)
    50 
    						
    All Panasonic manuals Comments (0)

    Related Manuals for Panasonic Cs W50btp Cu W50bbp8 Cu V50bbp8 Repair Manual