7 OPERATING INSTRUCTION
7.1. Wired Remote Control (OPTIONAL PARTS)
NOTES:
 
    • 
• •  • 
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
 
    • 
• •  • 
The illustration above is for explan atory purposes only. The appearance will be different during actual operation.
 
    • 
• •  • 
Do not operate the remote control with wet hands. Otherwise, electric shock or malfun ction may occur.
 
    • 
• •  • 
Do not press the...

Page 26

7.2. Wireless Remote Control (OPTIONAL PARTS)
NOTES:
 
    • 
• •  • 
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
 
    • 
• •  • 
The illustration above is for explan atory purpose only. The appearance will be different during actual operation.
 
    • 
• •  • 
If using the wireless remote control in conjunction with the wired remote control, the settings made from the wireless remote
control will appear on the wired...

Page 27

8 REFRIGERATION CYCLE
CS-W50BTP/CU -W50BBP8
CS-W50BTP/CU -V50BB P8
27 

Page 28

9 OPERATION RANGE
Power Supply
The applica ble voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanc ed within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of
the rated voltage.
Power Supply
MODELUnit Main PowerApplicable Voltage
CU-Phase, VoltsHzMaxMin
V50BBP83N~38050418342
W50BBP83N~40050440360
3N~41550457374
Indoor and Outdoor Temperature
 
    • 
• •  • 
Cooling only type...

Page 29

10 PIPE LENGTH
Q
QQ Q
CORRECTION OF COOLINGCAPACITY ANDHEATINGCAPACITIES
Correction of cooling and heating capacities according to the connecting pipe length.
The data of cooling capacities (marked on the name plate) are based on 7.5 meters connecting pipe and horizon tal installa tion.
For other pipe length of other installa tion multiply by the following correction factor to determine the revised cooling capacity.
29 

Page 30

Attention Q
QQ Q
REFRIGERANT ADDITIONAL CHARGE
 1. Piping installation by standard piping
 
    • 
• •  • 
At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m.
(Refer to the following table)
But when the piping length exceed s 30m, additio nal charge is required according to the following table.
Example:
CU-V50BB P8
In case of 50m long pipe (one way), the amoun t of refrigerant to be replenished is: (50 - 30) x 50 = 1,000g
Q...