Page 61
(When float switch is continuously off) 25.3. Freezing prevention control 1. Operation During cooling mode operation, after 9 minutes have passed since the compressor turned on, the outdoor unit will stop its operation when the temperature detected by the indoor unit pipe temperature sensor is 2°C or lower. The indoor unit continues operating at the fan speed set by the remote control. (The remote controldisplay does not change.) 2. Cancelling This control is cancelled when the temperature detected...
Page 62
25.4. Heating mode operation time chart (Heat pump type) (*2) Outdoor unit fan control during heating mode operation When the compressor is on during heating mode operation (except during defrosting and when the liquid bypass valve is on), the outdoor unit fan is controlled by means of input (CN2) indicating whether the contact of the heating pressure switch on the outdoor unit circuit board is open or closed. (At the start of heating mode operation, the fan operates at HI speed.) 62
Page 63
25.5. Hot starting 1. Whenheating mode operation starts a. Start Hot start control commences when heating mode operation starts. b. Operation “PREHEAT” appears on the remote controldisplay . (Other display s remain unchanged.) The indoor unit fan stops. In additio n, during hot starting, the louvre stays at the horizon tal position (angle 0°). c. Cancelling Hot starting will be cancelled when the compressor is turned on or the indoor unit pipe temperature sensor is 18°C or higher or after 1 minute of...
Page 64
2. Whendefrosting is completed a. Start Hot start control commences when defrosting is completed. b. Operation “PREHEAT” appears on the remote controldisplay . (Other display s remain unchanged) The indoor unit fan stops. In additio n, during hot starting, the louvre stays at the horizon tal position (angle 0°C). c. Cancelling Hot starting will be cancelled when the temperature detected by the indoor unit pipe temperature sensor is 18°C or higher, or after a maximum 1 minute has passed since...
Page 65
25.7. Excess heat dissipation for indoor unit The indoor unit fan continue its operation for 30 seconds after heating mode operation turns off in order to dissipa te excess heat. 1. Whenheating mode operation has stopped (LOWspeed for 30 seconds) 2. Whenoperation is set to a mode other than heating by means of the OPERATION button 3. If operation starts again during the 30 seconds mentioned at (1) (The fan operates at LOW speed for the remainder of the 30 seconds and then hot start commences.) 25.8....
Page 66
2. Operation a. During defrosting, the outdoor unit turns on the compressor and turns off the outdoor unit fan and the reversing valve. b. The indoor unit fan operates at LOW speed for 30 seconds upon defrosting starts, After this, the indoor unit fan turns off until defrosting is completed. (During defrosting, the louvre of the indoor unit stays at horizon tal position). 25.9. Indoor thermostat characteristics 1. Thermostat characteristics during cooling and heating modes. Operation modeSetting...
Page 67
b. Thermostat characteristic when switching between cooling and heating mode operation Switching between cooling mode and heating mode operation is carried out as shown in the table below. However, during automatic changeover operation, the operation will not change within 10 minutes after the thermostat has switched off, either cooling mode or heating mode. (The 10 minutes timer will be cancelled when operation is changed to other modes (manually) or when operation stops and the thermostat turns on.)...
Page 68
25.10. Indoor unit fan control 1. Fixing at LO, MED or HI When LO, MED or HI isset, the relay switches and operation is carried out at that setting. 2. Automatic fan speed When set toAUTO, the indoor unit fan operation changes as shown in the table below. (Indoor temperature) - (Setting temperature) (Units: K) Mode / Fan SpeedHIMEDLO Cooling+3 or higher+1.5 ~ 3Less than +1.5 Heating-3 or lower-1.6 ~ - 3More than -1.5 FanMED irrespective of temperature 25.11. Forced operation during restart The...
Page 69
2. During initial operation When the OFF/ON button is pressed to start the operation, the louvre moves through one full cycle, and then swings automatically (if AUTO has been set using the remote control) or moves to the setting angle (ifMANUAL has been set using the remote control). 3. Whenoperation stops When the OFF/ON button is pressed to stop the operation, the louvre moves through one full cycle, and then stops in the down position, regardless of the remote control setting. 4. When thermostat is...