7 OPERATING INSTRUCTION
7.1. Wired Remote Control (OPTIONAL PARTS)
NOTES:
 
    • 
• •  • 
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
 
    • 
• •  • 
The illustration above is for explan atory purposes only. The appearance will be different during actual operation.
 
    • 
• •  • 
Do not operate the remote control with wet hands. Otherwise, electric shock or malfun ction may occur.
 
    • 
• •  • 
Do not press the...

Page 27

7.2. Wireless Remote Control (OPTIONAL PARTS)
NOTES:
 
    • 
• •  • 
Ensure that the correct button is pressed as simultaneous pressing of the multiple buttons will not make the setting correct.
 
    • 
• •  • 
The illustration above is for explan atory purpose only. The appearance will be different during actual operation.
 
    • 
• •  • 
If using the wireless remote control in conjunction with the wired remote control, the settings made from the wireless remote
control will appear on the wired...

Page 28

8 REFRIGERATION CYCLE
8.1. Heating Model
CS-W50BB4P / CU-W50BBP8
8.2. Cooling Only Model
CS-W50BB4P / CU-V50BB P8
28 

Page 29

9 OPERATION RANGE
Power Supply
The applica ble voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanc ed within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of
the rated voltage.
Power Supply
MODELUnit Main PowerApplicable Voltage
CU-Phase, VoltsHzMaxMin
W/V50BBP83N~38050418342
3N~40050440360
3N~41550457374
Indoor and Outdoor Temperature
 
    • 
• •  • 
Cooling only type
Model...

Page 30

10 PIPE LENGTH
Q
QQ Q
CORRECTION OF COOLINGCAPACITY ANDHEATINGCAPACITIES
Correction of cooling and heating capacities according to the connecting pipe length.
The data of cooling capacities (marked on the name plate) are based on 7.5 meters connecting pipe and horizon tal installa tion.
For other pipe length of other installa tion multiply by the following correction factor to determine the revised cooling capacity.
Q
QQ Q
REFRIGERANT ADDITIONAL CHARGE
 
    • 
• •  • 
The piping length exceeds 30...