Page 1
1 SERVICE INFORMATION 3 2 FEATURES 4 3 SPECIFICATION (HEAT PUMP TYPE ) 10 4 SPECIFICATION (COOLING ONLY TYPE ) 11 5 TECHNICAL DRAWING 12 6 CIRCUITDIAGRAM 14 7 OPERATING INSTRUCTION 26 8 REFRIGERATION CYCLE 28 9 OPERATIO N RANGE 29 10 PIPE LENGTH 30 © 2002 Matsushita Industrial Corporation. Sdn. Bhd. (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law. CS-W50BB4P CU-V50BBP8 CS-W50BB4P CU-W50BBP8 11 OPERATING CHARACTERISTIC 32 12 FAN...
Page 2
20 TEST OPERATIO N AND SELF DIAGNOSIS 47 21 SETTING OF SAVEENERGY AND THERMISTOR SWITCH 51 22 GROUP CONTROL 52 23 TROUBLESHOOTING 53 24 EMERGENCY OPERATIO N 58 25 CONTROL 59 26 WIRED REMOTE CONTROLINSTALLA TION MANUAL 70 27 WIRELESS REMOTE CONTROLINSTALLA TION MANUAL 75 28 INSTALLA TION (INDOOR UNIT) 82 29 INSTALLA TION (OUTDOOR UNIT) 91 30 REPLACEMENT PARTS 103 2
Page 3
1 SERVICE INFORMATION Caution: OPb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C). OPb free solder will tend to splash when heated too high (about 1100° F/600°C). Notice of Address setting for NEW Cassette / NEW Outdoor Unit. The new Casse tte / new Outdoor models are possible to have...
Page 4
2.1. Variety of excellent features • • • • Compact design Compact design 290 mm height, 840 mm width and 840 mm depth. • • • • Automatic restart function When theelectric power resumes after a power failure, the unit will automatically restarts the operation in the pre- failure mode. • • • • Auto fan mode (indoor unit) Auto fan mode is added beside s HI, ME and LO. It automatically adjusts the fan speed according to the indoor temperature. • • • • Dry mode function Dry...
Page 5
2.2.1. Product features • • • • Low-noise design improves comfort in surrounding areas 1. The noise-suppressing winglet fan is a result of new research into vane design theory. The unique curved shape suppresses the generation of vortexes, thus reducing air flow noise. 2. The adoption of double -orifice rings reduces air passage resistance. 3. Strengthening of the noise insulation materials in the compressor and the sealing-in of mechanical noise allows vibration noise to be greatly enclosed...
Page 6
2.4. A brand-new control method using the latest in technology • • • • Easier power supply wiring connection Power supply wiring and other wiring tasks can be carried out more easily. − − − − Twin non-polar wires used to connect indoor and outdoor units. − − − − Adoption of connection error prevention circuits for drive wires and signal wires. If a connection error is made, the relay does not operate and current does not flow to the circuit boards. • • • • Twin and...
Page 7
2.8. New refrigerant Series [R407C] pipe installation 2.8.1. Procedure • • • • The new refrigerant (R407C) has a different composition to the previously-used refrigerant (R22), so some contents and method of pipe installa tion and charging work are different from before. Care should be taken whencarrying out this work. 2.8.2. Installation and precautions 2.8.2.1. Before installation 1. Determine the installa tion division. 2. Check the refrigerant to be used. • • • • Check that the...
Page 8
• • • • Do not work for refrigerant piping on outdoo r on rainy days. • • • • Seal by brazing. • • • • Be sure to use only a non-oxidizing brazing material. (Use nitrogen. Anti-oxidants cannot be used.) • • • • W hen brazing pipes together, or when brazing copper pipes and copper joints, use a brazing material (Bcup-3) which does not require flux. • • • • Flare processing and ester oil. • • • • Sealing can be improved by applyin g ester oil or...
Page 10
3 SPECIFICATION (HEAT PUMP TYPE ) CS-W50B B4P / CU-W50B BP8 ITEM / MODELIndoor UnitOutdoor unit Main BodyCS-W50BB4PCU-W50BBP8 PanelCZ-BT01P RemoteCZ-RD51P (Wired) ControlCZ-RL51P (Wireless) Cooling CapacitykW14.0 BTU/h47,700 Heating CapacitykW16.0 BTU/h54,600 Refrigerant Charge-lessm30 Standard Air Volume for High Speedm3/min31 cfm1095 Outside Dimension (H x W x D)mm290 x 840 x 8401220 x 1100 x 320 inch11-7/16 x 33-1/24 x 33-1/2448-1/24 x 43-5/16 x 12-19/32 Net Weightkg33115 lbs73254 Piping...