21.1. Energy save setting • • • • Upper and lower limit can be set for the setting temperature during cooling and heating operation. (The factory shipment setting has an upper limit of 31°C and a lower limit of 16°C.) 1. While operation is stopped, press theTEMP UP and TEMP DOWNbuttons simultaneousl y. 2. To set an upper limit Press the OPERATION button until HEAT is display ed. ↓ Press the TEMP UP or TEMPDOWNbutton to set the temperature. ↓ Press the SET button to complete the upper limit...
Page 52
Setting group for 1 remote control unit • • • • W hen using a remote control thermostat, the thermostat setting is used for all indoor units in the group. • • • • During group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units and cooling-only units.) • • • • Do not mix manua l settings and automatic settings. (Manual settings take priority.) • • • • The master unit and slave units can be centralized controlled during group...
Page 53
If test operation does not proceed correctly Carry out test operation after approximately 12 hours have passed since the power was turned on (crankcase heater is energized). If operation is started by using the remote control within 1 minute of turning on the power, the outdoor unit settings will not be made correctly and correct operation will not be possible. If the following symptoms occur after turning on the power, check the wiring connections once more. • • • • For standard installation...
Page 54
1. The main power is turned on while the transmission wires between the indoor unit(s) are not connected (open circuit at section A) Symptom: Nothing abnormal appears on the remote control display . If operation is started in this condition, the combination of the 50BB outdoo r unit and the 14BB4 indoor unit (master unit) will result in abnormal operation. ↓ If operation continues, an abnormality will occur on the refrigeration cycle and operation will stop. − − − − Remote control... “CHECK”...
Page 55
1. The main power is turned on while the transmission wires between the indoor unit and the outdoor unit are not connected (open circuit at section A) Symptom: Operation of indoor unit No. 1 and indoor unit No. 3 is possible. However, “CHECK” flashes in the remote controldisplay for 3-5 minutes after the main power is turned on. − − − − Remote control... “CHECK” flashes − − − − Indoor unit No. 2... LED2 on the printed circuit board flashes (both master and slave units) − − − −...
Page 56
1. Automatic address setting (don’t need to set dip-switch) If the wiring is connected properly as above example, the address is set automatically by the main powersupply . An indoor unit with remote control will be set as the master. If the power source is installe d to indoor units and outdoo r units separately, turn on the switch by following the procedure: outdoor unit, then indoor unit with control, and finally other indoor units. When theslave units do not operate (when address cannot be set) 1....
Page 57
Reset the address by following the procedure: a. Make sure that dip-switches No. 1 to 4 and No. 8 are OFF, stop the operation. b. Simultaneously, push buttons “AIR SWING AUTO”, “OPERATION ” and “A/C No.”. The address will be reset and new address will be set. Important:The address for the Twin/Triple control cannot be reset, using the above mentioned procedure. 2. Manua l address setting (by dip-switchDSW1) Whensetting the address manua lly, set the dip-switch of the PC board of the indoor unit as...
Page 58
Emergencyoperation • • • • Emergency operation of outdoor unit Emergency operation can be carried out by setting the DSW1 switch on the printed circuit board of the outdoor unit to the EMERGENCY position. However, emergency operation is only carried out when an abnormality is detected by the indoor/outdoor temperature thermistors. The resistance values of each thermistor are measured as shown in the table below to determine if there is an abnormality. Thermistor resistance table Temperatu...
Page 59
25 CONTROL Description of basic Functions 25.1. Cooling mode operation time chart (*1) Outdoor unit fan start control during cooling At the start of cooling mode and drying mode operation, the outdoo r unit heat exchan ger outlet temperature is detected in order to set the fan speed. Operation is carried out at the fan speed detected for 30 seconds. After 30 seconds, the heat exchan ger outlet temperature is detected and the outdoo r unit fan speed is changed automatically . (*2) Cooling low outdoor...
Page 60
25.2. Drain pump control 1. Basic operation During cooling mode, dry mode or defrost mode operation, the drain pump turns on when the compressor turns on. (The drain pump turns on during freezing prevention control.) • • • • W hen the compressor turns off, the drain pump will still continue its operation for 6 more minutes. • • • • If the drain pump is running when operation stops or when the operating mode is changed, the drain pump will still continue its operation for 6 more...