Page 61
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)60 3-wire 4-20 mA Source This covers connection to gas detectors such as Sensepoint Plus/Pro. 1 Set up the gas detector. Refer to the detector’s user manual for details describing how to set up the detector. 2 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 20. 3Follow step 2 on page...
Page 62
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)61 WARNINGS Touchpoint 4 is designed for installation and use in indoor safe area non-explosive atmospheres. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned. Before carrying out any work ensure local regulations and site procedures are followed. Access to the interior of the controller, when carrying out any work, must only be conducted by trained personnel. Switch off and isolate...
Page 63
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)62 Troubleshooting The following table details self-diagnostics/problem solving for Touchpoint 4. Configuration Fault ConditionSymptom Action Power Supply Faults — subject to selected settings DC1 normal: Power LED (green) ON Battery icon OFFAC supply failed (
Page 64
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)63 System Configuration Check Sheet Controller location Installed by Date Configured by Date Calibrated by Date Contact tel no Power supply ......... AC volts ......... DC volts Channel TypeSensePoint detector typeOther detector type mV input mA input Flam.Toxic Oxygen STDPlus Pro 1................................... ................................... .. ................................... . ................................... 2 3 4 Comments (Detail...
Page 65
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)64 System Review Check Sheet/Record Comments Company Name Application Details Contact Name Address Tel Mobile Fax (Brief application and system overview including ancillary devices)Email Customer reported problems/specific requests Checklist Control System Y N Comments Is control system mounted in a suitable place? Daily viewing, access for maintenance? Is protection suitable for location? Indoor/outdoor, enclosure IP /NEMA rating? Are there any visual...
Page 66
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)65 Are the devices suitable for the relay ratings? Correct switching power rating or driving other relays? Other General Comments Checks carried out by Date Next check
Page 67
Parts TP4MAN Issue 3 Apr 06 (MAN0631)65 This chapter lists part numbers for complete controllers, spare items and accessories. Touchpoint 4 Controllers Description Part No. 4-Channel 4 x mA input, 0 x mV input TPWM4440 3 x mA input, 1 x mV input TPWM4431 2 x mA input, 2 x mV input TPWM4422 1 x mA input, 3 x mV input TPWM4413 0 x mA input, 4 x mV input TPWM4404 3-Channel 3 x mA input, 0 x mV input TPWM4330 2 x mA input, 1 x mV input TPWM4321 1 x mA input, 2 x mV input TPWM4312 0 x mA input, 3...
Page 68
Parts TP4MAN Issue 3 Apr 06 (MAN0631)66 Accessories Spares Caution Other 3rd party non-approved equipment may be used, but only at the users own risk. A range of approved 3rd party supplied equipment is available that has been tested to ensure their operation with the Zareba range of products. Contact a Honeywell Analytics distributor for details about the range.Description Part No. mA expansion kit (includes mA input module, display module, IDC lead, interconnect cable and fixings)TP4MAEK mV...
Page 69
Specifications TP4MAN Issue 3 Apr 06 (MAN0631)67 General Environmental UseWall mounted 1 to 4 channel control panel for the local annunciation of gas hazards as detected by the Zareba Sensepoint range of gas detectors. Suitable for use as an indoor stand-alone, self-contained installation or as part of a larger distributed control system User Interface OperationSingle Test/Accept/Reset push button for normal operational use. Three further hidden push buttons per module for configuration via...
Page 70
Specifications TP4MAN Issue 3 Apr 06 (MAN0631)68 Common Module Channel Module Supply85-265 Vac, 50/60 Hz, auto-sensing 19-30 Vdc, maximum power 160Wac and/or 63Wdc Communications RS485, user configurable address and baud rate (1200, 2400, 4800, 9600, 19200) Other Remote accept/reset push button, normally open, momentary close to activate RelaysCommon Alarm 1 (A1) Common Alarm 2 (A2) System Fault (F) RatingSPCO / 3 A, 240 Vac (non inductive load) Default SettingLatching Normally de-energized...