Honeywell Touchpoint 4 Manual
Have a look at the manual Honeywell Touchpoint 4 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)60 3-wire 4-20 mA Source This covers connection to gas detectors such as Sensepoint Plus/Pro. 1 Set up the gas detector. Refer to the detector’s user manual for details describing how to set up the detector. 2 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 20. 3Follow step 2 on page 57. 4 For Sensepoint Plus/Pro check for a minimum voltage of 12 Vdc at the gas detector. For detectors other than Sensepoint Plus/Pro refer to their operating instructions. 5 Check that Touchpoint 4’s display shows the correct gas units and range for the detector in use. If not follow the procedure on page 52 to change the gas units and range. 6Follow step 5 on page 58, to step 16 on page 59.
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)61 WARNINGS Touchpoint 4 is designed for installation and use in indoor safe area non-explosive atmospheres. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned. Before carrying out any work ensure local regulations and site procedures are followed. Access to the interior of the controller, when carrying out any work, must only be conducted by trained personnel. Switch off and isolate the power supply to the controller when access is required. Take any necessary precautions to prevent false alarms. The detectors/sensors that the controller connects to may be used for gas detection in hazardous atmospheres. Refer to the individual detector/sensor instructions for their details. This chapter details the following: • general maintenance • troubleshooting, see page 62 • system configuration sheet, see page 63 • system review check sheet, see page 64 General Maintenance Honeywell Analytics recommend that the controller’s configuration and operation are checked annually using the two check sheets shown at the end of this section. The System Configuration Sheet should be referenced during system checks and updated if any changes to the system configuration have been made as well as a calibration log. The System Review Check Sheet contains a list of the minimum checks that should be made to ensure the proper and safe functioning of a system. The gas detectors connected to the controller should be checked by following the procedures detailed in their user guides. Maintenance
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)62 Troubleshooting The following table details self-diagnostics/problem solving for Touchpoint 4. Configuration Fault ConditionSymptom Action Power Supply Faults — subject to selected settings DC1 normal: Power LED (green) ON Battery icon OFFAC supply failed (
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)63 System Configuration Check Sheet Controller location Installed by Date Configured by Date Calibrated by Date Contact tel no Power supply ......... AC volts ......... DC volts Channel TypeSensePoint detector typeOther detector type mV input mA input Flam.Toxic Oxygen STDPlus Pro 1................................... ................................... .. ................................... . ................................... 2 3 4 Comments (Detail ancillary equipment such as audible/visual alarm indicators, battery back up systems etc.) Common Configuration Alarm 1 Alarm 2 Fault RS485 Baud rate E/D L/NL E/D L/NL E/D address Channel Configuration Channel Gas Range UnitsAlarm 1 Alarm 2 Fault Level* E/D L/NL Level* E/D L/NL E/D 1 2 3 4 * For Oxygen state rising (R) or falling (F) E/D Energized or De-Energized L/NL Latching/Non-Latching Calibration Record ChannelActual zero readingZero re-cal? Y/N?New zero readingActual span readingSpan re-cal? Y/N?Span gas conc.New span readingNext cal. dueCarried out byDate
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)64 System Review Check Sheet/Record Comments Company Name Application Details Contact Name Address Tel Mobile Fax (Brief application and system overview including ancillary devices)Email Customer reported problems/specific requests Checklist Control System Y N Comments Is control system mounted in a suitable place? Daily viewing, access for maintenance? Is protection suitable for location? Indoor/outdoor, enclosure IP /NEMA rating? Are there any visual signs of damage? Physical damage? Is suitable cable/wire used for all connections? Screened, SWA, CSA, or AWG? Have all cables/wire been terminated correctly? Use of crimps, terminals tightened? Have all earth/ground connections been made? Earth loops? Are all the display indicators working properly? LCDs, LEDs? Detectors Y N Comments Are the detectors located in a suitable place? Lighter/heavier than air gas? Breathing zone? Ventilation? Are the detectors correct for the application? Gas? Range? Type? Are recommended accessories fitted? Weather protection, collecting cone, filters? Are the detectors/filters clean? Not been painted, filters clean? Are the detectors securely mounted? Bracket, wall mount, pipe mount? Are all glands/conduit secure? Securely tightened, seals not perished? Have all cables/wires been terminated correctly? Use of crimps, terminals tightened? Are junction boxes/enclosures closed properly? Junction boxes, transmitter enclosures? Ancillary Devices Y N Comments Are connections to ancillary devices correct? Audio/Visual alarms? Signs? Valves? DCS? SCADA?
Maintenance TP4MAN Issue 3 Apr 06 (MAN0631)65 Are the devices suitable for the relay ratings? Correct switching power rating or driving other relays? Other General Comments Checks carried out by Date Next check
Parts TP4MAN Issue 3 Apr 06 (MAN0631)65 This chapter lists part numbers for complete controllers, spare items and accessories. Touchpoint 4 Controllers Description Part No. 4-Channel 4 x mA input, 0 x mV input TPWM4440 3 x mA input, 1 x mV input TPWM4431 2 x mA input, 2 x mV input TPWM4422 1 x mA input, 3 x mV input TPWM4413 0 x mA input, 4 x mV input TPWM4404 3-Channel 3 x mA input, 0 x mV input TPWM4330 2 x mA input, 1 x mV input TPWM4321 1 x mA input, 2 x mV input TPWM4312 0 x mA input, 3 x mV input TPWM4303 2-Channel 2 x mA input, 0 x mV input TPWM4220 1 x mA input, 1 x mV input TPWM4211 0 x mA input, 2 x mV input TPWM4202 1-Channel System 1 x mA input, 0 x mV input TPWM4110 0 x mA input, 1 x mV input TPWM4101 Parts
Parts TP4MAN Issue 3 Apr 06 (MAN0631)66 Accessories Spares Caution Other 3rd party non-approved equipment may be used, but only at the users own risk. A range of approved 3rd party supplied equipment is available that has been tested to ensure their operation with the Zareba range of products. Contact a Honeywell Analytics distributor for details about the range.Description Part No. mA expansion kit (includes mA input module, display module, IDC lead, interconnect cable and fixings)TP4MAEK mV expansion kit (includes mV input module, display module, IDC lead, interconnect cable and fixings)TP4MVEK Description Part No. Instruction manual TP4MAN Wall mounting bracket TP4WMB Replacement input module for common module TP4CMIM Replacement display module for common module TP4CMDM Replacement mV input module TP4MVIM Replacement mA input module TP4MAIM Replacement mV display module TP4MVDM Replacement mA display module TP4MADM IDC lead (display to input module) TP4IDC Interconnect cable (input module to input module) TP4INT Terminal screw and U clamp (bag of 20) SPPPMTS
Specifications TP4MAN Issue 3 Apr 06 (MAN0631)67 General Environmental UseWall mounted 1 to 4 channel control panel for the local annunciation of gas hazards as detected by the Zareba Sensepoint range of gas detectors. Suitable for use as an indoor stand-alone, self-contained installation or as part of a larger distributed control system User Interface OperationSingle Test/Accept/Reset push button for normal operational use. Three further hidden push buttons per module for configuration via intuitive menu system Backlit displaySystem and channel status including, measuring range, units of measure, digital gas reading, bar graph display 0-100% full scale, system status indicators including alarm set point, alarm activated and power health Other indicatorsUltra-bright LEDs: alarm (red), power (green), fault (amber) Audible alarm85 dBA at 1m / 90 dBA at 1 foot, user hush facility, re-activated on new event TerminationsAccessed via hinged front cover (latch to hold open as required). All cable/conduit entry via pre-formed knockouts at bottom of controller. Screw terminals suitable for 0.5 mm 2 (20 AWG) to 2.5 mm2 (14 AWG). Crimped connection recommended.Do not over tighten the terminals. The recommended maximum toque for the terminal block is 12 lb in. IP rating Indoor use, IP 44 in accordance with EN60529:1992 Weight 6 Kg/13.2 lb (approx.) Operating Temp Range-10 oC to +40oC / 14oF to 104oF Operating Humidity Range10 to 90% RH (non condensing) Operating Pressure Range 90-110 kPa Storage -40 oC to +80oC / -40oF to +176oF, 20 to 80% RH (non condensing) Specifications
Specifications TP4MAN Issue 3 Apr 06 (MAN0631)68 Common Module Channel Module Supply85-265 Vac, 50/60 Hz, auto-sensing 19-30 Vdc, maximum power 160Wac and/or 63Wdc Communications RS485, user configurable address and baud rate (1200, 2400, 4800, 9600, 19200) Other Remote accept/reset push button, normally open, momentary close to activate RelaysCommon Alarm 1 (A1) Common Alarm 2 (A2) System Fault (F) RatingSPCO / 3 A, 240 Vac (non inductive load) Default SettingLatching Normally de-energized Energize on any A1 alarmLatching Normally de-energized Energize on any A2 alarm Latching Normally energized De-energize on any fault/power loss User Configurable OptionsLatching/non-latching, Energized/de-energized Number of Inputs Up to four channel modules may be fitted to any system. mV and mA types available Input modules to match the following types of connected detector Detector Type 3-wire mV bridge 2 wire, 4-20 mA, loop powered3-wire, 4-20 mA, source output Example Sensepoint Flammable Sensepoint Toxic and Oxygen Sensepoint Plus or Sensepoint Pro Detector Supply mV Bridge Input Module Constant current supply: 200 mA Self regulating supply voltage subject to cable resistance Max. loop resistance: 18 Ohms mA Input Module Maximum detector current supply: 500 mA, Minimum guaranteed supply voltage from the controller: 19 Vdc Input impedance: 100 Ohms