Home > Honeywell > Controller > Honeywell Touchpoint 4 Manual

Honeywell Touchpoint 4 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Touchpoint 4 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							   Commissioning
    TP4MAN Issue 3 Apr 06 (MAN0631)60
    3-wire 4-20 mA Source
    This covers connection to gas detectors such as Sensepoint Plus/Pro.
    1 Set up the gas detector.
    Refer to the detector’s user manual for details describing how to set up the detector. 
    2 Check that all power and electrical connections to the controller, and electrical 
    connections to the gas detector are correct.
    For gas detector access see its user manual. For detector to controller wiring details see
    page 20.
    3Follow step 2 on page 57.
    4 For Sensepoint Plus/Pro check for a minimum voltage of 12 Vdc at the gas 
    detector.
    For detectors other than Sensepoint Plus/Pro refer to their operating instructions.
    5 Check that Touchpoint 4’s display shows the correct gas units and range for the 
    detector in use.
    If not follow the procedure on page 52 to change the gas units and range.
    6Follow step 5 on page 58, to step 16 on page 59. 
    						
    							   Maintenance
    TP4MAN Issue 3 Apr 06 (MAN0631)61
    WARNINGS
    Touchpoint 4 is designed for installation and use in indoor safe area 
    non-explosive atmospheres. Installation must be in accordance 
    with the recognized standards of the 
    appropriate authority in the country concerned.
    Before carrying out any work ensure local regulations and site procedures 
    are followed. 
    Access to the interior of the controller, when carrying out any work, 
    must only be conducted by trained personnel. Switch off and isolate 
    the power supply to the controller when access is required. 
    Take any necessary precautions to prevent false alarms.
    The detectors/sensors that the controller connects to may be used for gas 
    detection in hazardous atmospheres. Refer to the individual detector/sensor 
    instructions for their details. 
    This chapter details the following:
    • general maintenance
    • troubleshooting, see page 62
    • system configuration sheet, see page 63
    • system review check sheet, see page 64
    General Maintenance
    Honeywell Analytics recommend that the controller’s configuration and operation are checked
    annually using the two check sheets shown at the end of this section. 
    The System Configuration Sheet should be referenced during system checks and updated if
    any changes to the system configuration have been made as well as a calibration log. 
    The System Review Check Sheet contains a list of the minimum checks that should be made
    to ensure the proper and safe functioning of a system.
    The gas detectors connected to the controller should be checked by following the procedures
    detailed in their user guides. 
    Maintenance 
    						
    							   Maintenance
    TP4MAN Issue 3 Apr 06 (MAN0631)62
    Troubleshooting
    The following table details self-diagnostics/problem solving for Touchpoint 4.
    Configuration Fault
    ConditionSymptom Action
    Power Supply Faults — subject to selected settings 
    DC1 normal:
    Power LED (green) ON
    Battery icon OFFAC supply failed
    (
    						
    							   Maintenance
    TP4MAN Issue 3 Apr 06 (MAN0631)63
    System Configuration Check Sheet
    Controller location  Installed by  Date
    Configured by  Date
    Calibrated by Date
    Contact tel no
    Power supply  ......... AC volts  ......... DC volts
    Channel
    TypeSensePoint detector typeOther detector 
    type
     mV input  mA input
    Flam.Toxic Oxygen
    STDPlus Pro
    1...................................
    ...................................
    ..
    ...................................
    .
    ................................... 2
    3
    4
    Comments (Detail ancillary equipment such as audible/visual alarm indicators, battery back up systems etc.)
    Common Configuration
    Alarm 1 Alarm 2 Fault RS485 Baud rate
    E/D L/NL E/D L/NL E/D address
    Channel Configuration
    Channel Gas Range UnitsAlarm 1 Alarm 2 Fault
    Level* E/D L/NL Level* E/D L/NL E/D
    1
    2
    3
    4
    * For Oxygen state rising (R) or falling (F)   E/D Energized or De-Energized   L/NL Latching/Non-Latching
    Calibration Record
    ChannelActual 
    zero 
    readingZero 
    re-cal? 
    Y/N?New zero 
    readingActual 
    span 
    readingSpan 
    re-cal? 
    Y/N?Span gas 
    conc.New span 
    readingNext cal. 
    dueCarried 
    out byDate 
    						
    							   Maintenance
    TP4MAN Issue 3 Apr 06 (MAN0631)64
    System Review Check Sheet/Record
    Comments
    Company Name  Application Details 
    Contact Name
    Address
    Tel
    Mobile
    Fax
    (Brief application and system overview including ancillary devices)Email
    Customer reported problems/specific requests
    Checklist
    Control System Y N Comments
    Is control system mounted in a suitable place?
    Daily viewing, access for maintenance?
    Is protection suitable for location?
    Indoor/outdoor, enclosure IP /NEMA rating?
    Are there any visual signs of damage?
    Physical damage?
    Is suitable cable/wire used for all connections?
    Screened, SWA, CSA, or AWG?
    Have all cables/wire been terminated correctly?
    Use of crimps, terminals tightened?
    Have all earth/ground connections been made?
    Earth loops?
    Are all the display indicators working properly?
    LCDs, LEDs?
    Detectors Y N Comments
    Are the detectors located in a suitable place?
    Lighter/heavier than air gas? Breathing zone? Ventilation?
    Are the detectors correct for the application?
    Gas? Range? Type?
    Are recommended accessories fitted?
    Weather protection, collecting cone, filters?
    Are the detectors/filters clean?
    Not been painted, filters clean?
    Are the detectors securely mounted?
    Bracket, wall mount, pipe mount?
    Are all glands/conduit secure?
    Securely tightened, seals not perished?
    Have all cables/wires been terminated correctly?
    Use of crimps, terminals tightened?
    Are junction boxes/enclosures closed properly?
    Junction boxes, transmitter enclosures?
    Ancillary Devices Y N Comments
    Are connections to ancillary devices correct?
    Audio/Visual alarms? Signs? Valves? DCS? SCADA? 
    						
    							   Maintenance
    TP4MAN Issue 3 Apr 06 (MAN0631)65
    Are the devices suitable for the relay ratings?
    Correct switching power rating or driving other relays?
    Other General Comments
    Checks carried out by  Date Next check 
    						
    							   Parts
    TP4MAN Issue 3 Apr 06 (MAN0631)65
    This chapter lists part numbers for complete controllers, spare items and accessories.
    Touchpoint 4 Controllers
    Description Part No.
    4-Channel 
    4 x mA input, 0 x mV input  TPWM4440
    3 x mA input, 1 x mV input  TPWM4431
    2 x mA input, 2 x mV input  TPWM4422
    1 x mA input, 3 x mV input  TPWM4413
    0 x mA input, 4 x mV input  TPWM4404
    3-Channel 
    3 x mA input, 0 x mV input  TPWM4330
    2 x mA input, 1 x mV input  TPWM4321
    1 x mA input, 2 x mV input  TPWM4312
    0 x mA input, 3 x mV input  TPWM4303
    2-Channel 
    2 x mA input, 0 x mV input  TPWM4220
    1 x mA input, 1 x mV input  TPWM4211
    0 x mA input, 2 x mV input  TPWM4202
    1-Channel System
    1 x mA input, 0 x mV input  TPWM4110
    0 x mA input, 1 x mV input  TPWM4101
    Parts 
    						
    							   Parts
    TP4MAN Issue 3 Apr 06 (MAN0631)66
    Accessories
    Spares
    Caution Other 3rd party non-approved equipment may be used, but only at 
    the users own risk. 
    A range of approved 3rd party supplied equipment is available that has been tested to ensure
    their operation with the Zareba range of products. Contact a Honeywell Analytics distributor for
    details about the range.Description Part No.
    mA expansion kit
    (includes mA input module, display module, IDC lead, interconnect 
    cable and fixings)TP4MAEK 
    mV expansion kit
    (includes mV input module, display module, IDC lead, interconnect 
    cable and fixings)TP4MVEK 
    Description Part No.
    Instruction manual  TP4MAN
    Wall mounting bracket TP4WMB 
    Replacement input module for common module  TP4CMIM 
    Replacement display module for common module  TP4CMDM 
    Replacement mV input module  TP4MVIM 
    Replacement mA input module  TP4MAIM 
    Replacement mV display module  TP4MVDM 
    Replacement mA display module  TP4MADM 
    IDC lead (display to input module)  TP4IDC 
    Interconnect cable (input module to input module)  TP4INT 
    Terminal screw and U clamp (bag of 20)  SPPPMTS  
    						
    							   Specifications
    TP4MAN Issue 3 Apr 06 (MAN0631)67
    General
    Environmental
    UseWall mounted 1 to 4 channel control panel for the local annunciation of gas 
    hazards as detected by the Zareba Sensepoint range of gas detectors. 
    Suitable for use as an indoor stand-alone, self-contained installation or as 
    part of a larger distributed control system
    User Interface
    OperationSingle Test/Accept/Reset push button for normal operational use. Three 
    further hidden push buttons per module for configuration via intuitive menu 
    system
    Backlit displaySystem and channel status including, measuring range, units of measure, 
    digital gas reading, bar graph display 0-100% full scale, system status 
    indicators including alarm set point, alarm activated and power health
    Other 
    indicatorsUltra-bright LEDs: alarm (red), power (green), fault (amber)
    Audible alarm85 dBA at 1m / 90 dBA at 1 foot, user hush facility, re-activated on new event
    TerminationsAccessed via hinged front cover (latch to hold open as required). 
    All cable/conduit entry via pre-formed knockouts at bottom of controller. 
    Screw terminals suitable for 0.5 mm
    2 (20 AWG) to 2.5 mm2 (14 AWG). 
    Crimped connection recommended.Do not over tighten the terminals. 
    The recommended maximum toque for the terminal block is 12 lb in. 
    IP rating Indoor use, IP 44 in accordance with EN60529:1992
    Weight 6 Kg/13.2 lb (approx.)
    Operating 
    Temp Range-10
    oC to +40oC / 14oF to 104oF
    Operating 
    Humidity Range10 to 90% RH (non condensing)
    Operating 
    Pressure Range 90-110 kPa
    Storage -40
    oC to +80oC / -40oF to +176oF, 20 to 80% RH (non condensing)
    Specifications 
    						
    							   Specifications
    TP4MAN Issue 3 Apr 06 (MAN0631)68
    Common Module
    Channel Module
    Supply85-265 Vac, 50/60 Hz, auto-sensing 19-30 Vdc, maximum power 160Wac 
    and/or 63Wdc
    Communications RS485, user configurable address and baud rate (1200, 2400, 4800, 9600, 
    19200)
    Other Remote accept/reset push button, normally open, momentary close 
    to activate 
    RelaysCommon Alarm 1 (A1)  Common Alarm 2 (A2)  System Fault (F)
    RatingSPCO / 3 A, 240 Vac (non inductive load)
    Default SettingLatching
    Normally de-energized
    Energize on any A1 
    alarmLatching
    Normally de-energized
    Energize on any A2 alarm
    Latching
    Normally energized
    De-energize on any 
    fault/power loss
    User 
    Configurable 
    OptionsLatching/non-latching, Energized/de-energized 
    Number of 
    Inputs Up to four channel modules may be fitted to any system. mV and mA types 
    available
    Input modules to match the following types of connected detector
    Detector Type 3-wire mV bridge 2 wire, 4-20 mA, 
    loop powered3-wire, 4-20 mA, 
    source output
    Example Sensepoint Flammable Sensepoint Toxic 
    and Oxygen Sensepoint Plus or 
    Sensepoint Pro
    Detector 
    Supply mV Bridge Input Module
    Constant current supply: 200 mA
    Self regulating supply voltage 
    subject to cable resistance 
    Max. loop resistance: 18 Ohms 
    mA Input Module 
    Maximum detector current supply: 500 mA, 
    Minimum guaranteed supply voltage from 
    the controller: 19 Vdc
    Input impedance: 100 Ohms 
    						
    All Honeywell manuals Comments (0)