Honeywell Touchpoint 4 Manual
Have a look at the manual Honeywell Touchpoint 4 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)51 Power Source This menu programs Touchpoint 4 for the type of available power source(s). The controller can be set to any of three different power supply modes. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The display shows one of the following power modes: • dC-1 — AC only power supply • dC-2 — AC and DC power supplies • dC-3 — DC only power supply 3 Use Up/Down to select the required power configuration. Note If the system is powered by an AC supply, only dC-1 or dC-2 should be selected. If the system is powered by a DC supply, only dC-2 or dC-3 should be selected. 4 Press OK. The display returns to the menu selection screen. 5 Press Cancel. Returns controller to normal operation.
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)52 Channel Settings This table provides a summary of the individual channel configuration options. For detailed step- by-step instructions for each menu see the subsequent sections. / / / / / Units and RangeSelect Kppm, ppm, LEL or %V/VChange range valueFinished. Returns to Configuration Menu CalibrationSet Zero (C0). With zero gas at detector adjust value to zeroWait for 10s count down. If OK GOOD is displayed. If fail FA I L is displayed and return to set ZeroSet Span (CS). Apply cal. gas. When stable adjust value to cal. gas concentrationWait for 10s count down. If OK GOOD is displayed. If fail FA I L is displayed and return to set spanFinished. Returns to Configuration Menu Alarms/ Relays A1 alarm level. Change to new value.O 2 only - select rising (UP) or falling (DOWN) alarmA2 alarm level. Change to new value.O 2 only - select rising (UP) or falling (DOWN) alarmFinished. Returns to Configuration Menu AddressSelect Address (Add0, Add1, Add2, Add3, Add4) Finished. Returns to Configuration Menu / / / / / XX
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)53 Gas Units and Range WA R N I N G If the range is changed, the alarm set points also change. Verify desired set points per page 55. This menu is the first one displayed when the menu system is accessed. It sets the units of gas measurement and the range. 5 Press the Up or Down buttons to select a different range. Default units and ranges are shown in the following table. 6 When settings are complete press OK. Returns to the menu selection screen. 7 Press Cancel. Returns controller to normal operation. Caution If the range is changed, the alarm level will also be changed. Set desired alarm levels per page 55. 1 Press the Up and Down down buttons simultaneously. This accesses the menu system and displays the menu icon, which flashes. 2 Press OK. The current units and range are displayed. 3 Press Up or Down to select a different unit of gas measurement. See the subsequent table. 4 Press OK to accept the selected unit. The display now shows the current range. Unitkppm ppm %LEL %v/v Range1.0 - 999.9 1.0 - 999.9 or 10 - 999910 - 100 1.0 - 100
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)54 Zero and Span This menu is for calibrating the controller measurements to the connected gas detector. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The top left of the display reads CO to indicate the set zero menu mode. The gas reading displays the current real zero value. Note Ensure the sensor is in clean air before carrying out the next step. For oxygen apply nitrogen to the sensor at 0.3 l/min. 3 When the gas reading is stable adjust the reading to zero. Use the Up/Down buttons. Note Honeywell Analytics recommend the use of half full-scale gas for calibration purposes (contact a distributor for the supply of calibration gas). 4 Press OK when the reading is zero. The display now shows a 10 second countdown. When the countdown is complete the display shows GOOD if the zero has succeeded and then change to the span mode. If the zero fails the display shows FA I L and returns to the beginning of the set zero mode. After successfully setting the zero the display then changes to show CS in the top left to indicate the set span mode. For O 2 only — apply N2 at a flow rate of 0.3 l/m to perform a zero. Alternatively press Cancel to by-pass the zeroing and move directly to the span function. 5 Fit a flow adapter to the gas detector sensor. First remove any accessory fitted to the sensor, e.g. weather protection. 6 Apply calibration (span) gas to the detector at a flow rate of 0.3 l/min. The gas reading on the controller display shows the measured reading from the detector 7 When the gas reading is stable adjust the reading to the actual concentration of the calibration gas being applied to the detector. Use the Up/Down buttons. 8 Press OK. The display then shows a 10 second countdown. When the countdown is complete the display shows GOOD if the span has succeedd. If the span fails the display shows FA I L and returns to the beginning of the span menu. 9 When settings are complete, press Cancel. Returns controller to normal operation.
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)55 Alarm Levels and Relay Action Sets the alarm levels for Alarm 1 and Alarm 2 as well as how the alarm relays operate. For oxygen either a Rising (oxygen enrichment) or Falling (oxygen deficiency) alarm can be selected. The display changes to the relay latching or non-latching menu and shows either r 1-L (for relay 1 latching), or r 1-N (for relay 1 non-latching). Use Up/Down to change the relay action. The diagram on page 47 shows the effect of latching or non-latching relays. 8 Press OK to accept the change. The display now changes to the current A2 Alarm 2 setting. 9Alarm 2 settings are changed in the same way as for Alarm 1. A2 alarm levels can be set between the A1 alarm level and the full scale range. The default setting is 50% of the full scale range. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The current A1 (alarm 1) setting is displayed. 3 Use Up/Down to change the value. A1 alarm levels can be set between 0% and the FS (full-scale) range. The default setting is 25% of the full-scale range. 4 Press OK to accept the change. O2 only If the gas units are %V/V and the gas being detected is oxygen then a rising alarm UP or a falling alarm DOWN, can be selected. Use Up/Down to change the value. 5 Press OK to accept the change. The display changes to the A1 relay action menu. The display shows either r 1-d (for Relay 1 de- energized), or r 1-E (for Relay 1 energized). 6 Use Up/Down to change the relay action. 7 Press OK to accept the change. UP
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)56 10 When settings are complete press OK. Returns to the menu selection screen. 11 Press Cancel. Returns controller to normal operation. Channel Address This option sets the channel’s address. By default the four channels are set to Add1, Add2, Add3 and Add4 (from left to right). Common Module Default Configuration Channel Module Default Configuration Touchpoint 4 is supplied from the factory with standard default channel configurations. The configuration is based on settings typically used in gas detection systems. The two channel versions are factory configured as follows. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The display shows the channel address. 3 Use Up/Down to change the channel address. From Add0, Add1, Add2, Add3 or Add4. Note Setting the address of a channel to Add0 disables the channel. 4 Press the OK button to accept the change. 5 Press Cancel to return to normal operation. Function Default Configuration Address001 Baud Rate9600 Alarm Relay 1 (A1)Latching, normally de-energized, energizes on any A1 alarm Alarm Relay 2 (A2)Latching, normally de-energized, energizes on any A2 alarm Fault Relay (F)Non-latching, normally energized, de-energizes on fault/power loss
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)57 mV input detector 4-20 mA input detector Function Default Configuration Display range and units0-100% LEL mV Signal 3.5 mV Overrange Alarm Relay 1Alarm level 1 — 20% LEL Latching, normally de-energized, energizes on alarm (Single Pole Change Over 240 Vac 3A max) Alarm Relay 2Alarm level 2 — 40% LEL Latching, normally de-energized, energizes on alarm (Single Pole Change Over 240 Vac 3A max) Fault RelayNon-latching, normally energized, de-energizes on fault (Single Pole Change Over 240 Vac 3A max) Function Default Configuration Display range and units0-100% FS mA Signal0 - 1.5 mA Open circuit fault 1.5 - 2.5 mA Inhibit 2.5 - 3.2 mA Drift fault 3.2 - 4.0 mA Deadband 4.0 to 20.0 mA Normal operation 22.0 mA Max. overrange Alarm Relay 1Alarm level 1 — 20% of full scale Normally de-energized, energizes on alarm (Single Pole Change Over 240 Vac 3A max) Alarm Relay 2Alarm level 2 — 40% of full scale Normally de-energized, energizes on alarm (Single Pole Change Over 240 Vac 3A max) Fault RelayNon-latching, normally energized, de-energizes on fault (Single Pole change over 240 Vac 3A max)
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)57 WARNINGS Touchpoint 4 is designed for installation and use in indoor safe area non-explosive atmospheres. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned. Before carrying out any work ensure local regulations and site procedures are followed. Access to the interior of the controller, when carrying out any work, must only be conducted by trained personnel. Switch off and isolate the power supply to the controller when access is required. Take any necessary precautions to prevent false alarms. Caution Calibration of the gas detector and the controller is mandatory during commissioning to ensure their proper functioning. The controller with attached gas detectors should be commissioned in the following order: • first set the general controller configuration, see page 45 • set up any gas detectors that require local commissioning, e.g. Sensepoint Pro — this has its own display and user interface • set the configuration of the channels fitted to the controller, see page 51 • further commission the channels to match the types of gas detector attached to the controller following the procedures described in this chapter The chapter describes how to put the two versions of each channel module into service with the following types of gas detectors: • 3-wire mV bridge • 2-wire 4-20 mA sink, see page 59 • 3-wire 4-20 mA source, see page 60 Note On the subsequent diagrams, = LED ON, = LED OFF 3-wire mV Bridge This description covers connection to gas detectors such as Sensepoint Flammable. Carry out the following procedure. 1 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector details see its user manual. For detector to controller wiring details see page 21. 2 Apply power to the controller and check basic channel information is displayed. See page 29. To skip the channel warm up sequence press and hold the Cancel button on the Channel Module for 3 seconds. ALARM POWER FAULT Commissioning
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)58 10 Fit a flow adapter to the gas detector sensor. First remove any accessory fitted to the sensor, e.g. weather protection. 11 Apply calibration (span) gas to the detector. Adjust the gas flow rate to 0.3 l/min. Note Honeywell Analytics recommend the use of half full-scale gas for calibration purposes (contact a distributor for the supply of calibration gas). The controller now displays the actual gas measurement at the gas detector. 3 Check for a minimum voltage of 2.9 Vdc at the detector. If incorrect check for constant current supply of 200 mA +/-2 mA. For detectors other than Sensepoint Flammable refer to their operating instructions. 4 Close the detector enclosure. For gas detector details see its user manual. 5 Press the Up/Down buttons on the controller simultaneously. This enters configuration mode and the Set Gas Units and Range menu icon is displayed and flashes. 6 Select the Calibration Menu icon Use the Up/Down buttons. 7 Press the OK button. The top left of the display reads C0 indicating the set zero menu mode. The display shows the current gas reading real zero value. Ensure the sensor is in clean air. 8 When the gas reading is stable, adjust the reading to zero. Use the Up/Down buttons. 9 Press OK. The display shows a 10 second countdown. When the countdown finishes the display shows GOOD if set zero has succeeded. The display then changes to the set span menu mode indicated by CS in the top left of the display. If set zero fails the display shows FA I L and returns to the start of the set zero mode. ALARM POWER FAULT ALARM POWER FAULT
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)59 2-Wire 4-20 mA Sink This describes connection to gas detectors such as Sensepoint Toxic. 1 Set up the gas detector. Refer to the detector’s user manual for details describing how to set up the detector. 2 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 21. 3Follow step 2 on page 57. 4 Check for a minimum voltage of 16 Vdc at the gas detector. For detectors other than Sensepoint Toxic/Oxygen refer to their operating instructions. 5 Check that the Touchpoint 4 display shows the correct gas units and range for the detector in use. If not follow the procedure on page 52 to change the gas units and range. 6Follow step 5 on page 58, to step 16 on page 59. 12 When the gas reading is stable adjust the reading to the actual concentration of the calibration gas applied to the sensor. Use the Up/Down buttons. 13 Press the OK button. The display shows a 10 second countdown. If the set span succeeds the display shows GOOD. If the set span fails the display shows FAIL and returns to the beginning of the set span mode. After successfully setting the span the display returns to the menu selection mode. 14 Switch off the calibration test gas and remove the flow adapter from the detector. 15 Refit any accessory to the detector. 16 Return Touchpoint 4 to normal operation. Press the Cancel button. Alternatively select a different menu option. ALARM POWER FAULT