Installation TP4MAN Issue 3 Apr 06 (MAN0631)21 The next diagram shows the 3-wire detector power/signal terminal block layout with terminal identifiers. The table lists the detector power/signal terminals and their functions and specification. Zareba Sensepoint Gas Detector Connections Touchpoint 4 is specifically designed for use with the Zareba Sensepoint range of gas detectors. The subsequent diagrams show connection details for these units. For further information about Zareba Sensepoint...
Page 26
Installation TP4MAN Issue 3 Apr 06 (MAN0631)26 Generic Gas Detector Connections The following diagrams show generic installation connections for other gas detectors. 3-Wire mV Detector 3-Wire 4-20 mA Detector 1 2 31 2 3 +ve Signal+ve Signal -ve -ve 1 2 33Detector Controller
Page 27
Installation TP4MAN Issue 3 Apr 06 (MAN0631)27 2-Wire 4-20 mA Detector Maximum Cable Lengths To calculate the maximum cable run length from power source to the detector refer to the following example diagram and formula. Rloop = (Vcontroller — Vdetector min) / Idetector Maximum cable run length = Rloop / cable per metre resistance where: R loop = maximum working cable run resistance V controller = maximum available supply voltage at controller V detector min = minimum voltage at which the...
Page 28
Installation TP4MAN Issue 3 Apr 06 (MAN0631)28 Vsupply Vsensor Imax 0 V Signal Cable run ControllerDetector R l
Page 29
Operation TP4MAN Issue 3 Apr 06 (MAN0631)29 WARNINGS Access to the interior of the controller, when carrying out any work, must only be conducted by trained personnel. Switch off and isolate the power supply to the controller when access is required. Take any necessary precautions to prevent false alarms. Once powered and connected properly with the gas detector(s), Touchpoint 4 displays gas concentration, alarm, fault and status information on each Channel Module, and shows channel and system...
Page 30
Operation TP4MAN Issue 3 Apr 06 (MAN0631)30 Information on the Displays At switch on: • all display icons/text/numbers/symbols on the Common Module are lit • all LEDs on the Common Module are lit • the alarm buzzer sounds for 1.0 seconds. This sequence repeats twice and is the controller’s self-test procedure. The Common Module display then shows: • local time and date • power LED indicator lit The Common Module then tries to communicate with any connected individual Channel Module to...