Honeywell Touchpoint 4 Manual
Here you can view all the pages of manual Honeywell Touchpoint 4 Manual. The Honeywell manuals for Controller are available online for free. You can easily download all the documents as PDF.
Page 51
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)51 Power Source This menu programs Touchpoint 4 for the type of available power source(s). The controller can be set to any of three different power supply modes. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The display shows one of the following power modes: • dC-1 — AC only power supply • dC-2 — AC and DC power supplies • dC-3 — DC only power supply 3 Use Up/Down to select the required power...
Page 52
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)52 Channel Settings This table provides a summary of the individual channel configuration options. For detailed step- by-step instructions for each menu see the subsequent sections. / / / / / Units and RangeSelect Kppm, ppm, LEL or %V/VChange range valueFinished. Returns to Configuration Menu CalibrationSet Zero (C0). With zero gas at detector adjust value to zeroWait for 10s count down. If OK GOOD is displayed. If fail FA I L is...
Page 53
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)53 Gas Units and Range WA R N I N G If the range is changed, the alarm set points also change. Verify desired set points per page 55. This menu is the first one displayed when the menu system is accessed. It sets the units of gas measurement and the range. 5 Press the Up or Down buttons to select a different range. Default units and ranges are shown in the following table. 6 When settings are complete press OK. Returns to the menu selection screen. 7...
Page 54
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)54 Zero and Span This menu is for calibrating the controller measurements to the connected gas detector. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The top left of the display reads CO to indicate the set zero menu mode. The gas reading displays the current real zero value. Note Ensure the sensor is in clean air before carrying out the next step. For oxygen apply nitrogen to the sensor at 0.3...
Page 55
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)55 Alarm Levels and Relay Action Sets the alarm levels for Alarm 1 and Alarm 2 as well as how the alarm relays operate. For oxygen either a Rising (oxygen enrichment) or Falling (oxygen deficiency) alarm can be selected. The display changes to the relay latching or non-latching menu and shows either r 1-L (for relay 1 latching), or r 1-N (for relay 1 non-latching). Use Up/Down to change the relay action. The diagram on page 47 shows the effect of...
Page 56
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)56 10 When settings are complete press OK. Returns to the menu selection screen. 11 Press Cancel. Returns controller to normal operation. Channel Address This option sets the channel’s address. By default the four channels are set to Add1, Add2, Add3 and Add4 (from left to right). Common Module Default Configuration Channel Module Default Configuration Touchpoint 4 is supplied from the factory with standard default channel configurations. The...
Page 57
User Settings TP4MAN Issue 3 Apr 06 (MAN0631)57 mV input detector 4-20 mA input detector Function Default Configuration Display range and units0-100% LEL mV Signal 3.5 mV Overrange Alarm Relay 1Alarm level 1 — 20% LEL Latching, normally de-energized, energizes on alarm (Single Pole Change Over 240 Vac 3A max) Alarm Relay 2Alarm level 2 — 40% LEL Latching, normally de-energized, energizes on alarm (Single Pole Change Over 240 Vac 3A max) Fault RelayNon-latching, normally energized, de-energizes on...
Page 58
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)57 WARNINGS Touchpoint 4 is designed for installation and use in indoor safe area non-explosive atmospheres. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned. Before carrying out any work ensure local regulations and site procedures are followed. Access to the interior of the controller, when carrying out any work, must only be conducted by trained personnel. Switch off and isolate...
Page 59
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)58 10 Fit a flow adapter to the gas detector sensor. First remove any accessory fitted to the sensor, e.g. weather protection. 11 Apply calibration (span) gas to the detector. Adjust the gas flow rate to 0.3 l/min. Note Honeywell Analytics recommend the use of half full-scale gas for calibration purposes (contact a distributor for the supply of calibration gas). The controller now displays the actual gas measurement at the gas detector. 3 Check for a...
Page 60
Commissioning TP4MAN Issue 3 Apr 06 (MAN0631)59 2-Wire 4-20 mA Sink This describes connection to gas detectors such as Sensepoint Toxic. 1 Set up the gas detector. Refer to the detector’s user manual for details describing how to set up the detector. 2 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 21. 3Follow step 2 on page...