    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                 51
    This chapter lists part nu mbers for complete units  and spare/replacement items.
    Touchpoint 1 Controllers
    Spares
    Description Part No.
    mV Input TPWM1101
    mA Input TPWM1110
    Description Part No.
    Instruction manual TP1MAN
    Wall mounting bracket TP1WMB
    mV input module TP1MVIM
    mA input module TP1MAIM
    mV display module TP1MVDM
    mA display module TP1MADM
    IDC lead (display to  input module) TP1IDC
    Terminal screw and U  clamp (bag of 20) SPPPMTS
    Parts 
    						
    							   Specifications
    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                52
    General
    Environmental
    Use Wall mounted single 
    channel control panel for the  local annunciation of gas 
    hazards as detected by the Honeywell Analytics r ange of Sensepoint gas 
    detectors. Suitable for small scale, i ndoor installations requiring a self 
    contained gas detection and control system
    User interface
    Operation Single Test/Accept/Reset push-butt
    on for normal operational use. Three 
    further hidden push buttons for configuration via in tuitive menu system
    Backlit 
    display Channel status including 
    measuring range, units of  measure, digital gas 
    reading, bar graph displays 0-100% full  scale, status indicators including 
    alarm set point, alarm acti vated, and power health
    Other 
    Indicators Ultra-bright LEDs: alarm (red), 
    power (green), fault (amber)
    Audible Alarm 85 dBA at 1 m / 90 dBA at 1  foot, user hush facility, re-activated on new event
    Te r m i n a t i o n s Accessed via hinged front cover (latch 
    to hold open as required). All cable/
    conduit entry via pre-formed knockouts in  gland plate at bottom of controller.
    Screw terminals suitable  for use with 0.5 mm
    2 (20 AWG) to 2.5 mm2 (14 AWG)
    wires. Crimped connection re commended. Take care not to over tighten screw
    terminals. The recommended torque sett ing for the terminals is 12 lb in.
    IP Rating  Indoor use, IP44 in  accordance with EN60529:1992
    Weight  2.5 kg / 5.5 lb (approx.)
    Operating 
    Temp Range  -10°C to +40°C / 14°F to 104°F continuous (up to +50°C/122°F intermittent)
    Operating 
    Humidity 
    Range  10 to 90% RH (non condensing)
    Operating 
    Pressure 
    Range  90-110 kPa
    Storage  -40
    oC to +80oC / -40oF to +176oF, 20 to 80% RH (non condensing) 
    EMC EN50270
    Specifications 
    						
    							   Specifications
    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                  53
    Inputs
    Outputs
    Supply  Auto-sensing 85-265 Vac, 50/60 Hz , 30 W and/or 18-32 Vdc, 15 W
    Detector Type 3 wire mV bridge 2 wire, 4-20 mA, 
    loop powered3 wire, 4-20 mA, 
    source output
    Example Sensepoint Flammable Sensepoint Toxic 
    and OxygenSensepoint Plus 
    and Sensepoint Pro 
    Detector 
    Supply mV Bridge Input Module 
    Constant current supply: 200 mA 
    Self regulating supply voltage 
    subject to cable resistance 
    Maximum loop resistance: 18 ohms
    mA Input Module
    Maximum detector current supply: 500 mA
    Minimum guaranteed supply voltage 
    from the controller: 18 Vdc
    input impedance: 100 ohms
    Relays  Alarm 1 (A1)  Al arm 2 (A2) Fault (F)
    Rating  SPCO/3 A, 240 Vac (non inductive load)
    Default 
    Settings Latching
    Non- Latching
    De-energized Energized 
    Energize on alarm  De-energize on fault or 
    loss of power
    Factory setting 20% FS Factory setting 40% FS
    User 
    Configurable 
    Options  Latching/non-latching 
    Energized/de-energized 
    Rising/falling (oxygen only)  Trip point 10-90% FS  
    						
    							   Warranty
    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                   54
    Warranty
    All products are designed and manufactured to the  latest internationally recognized standards by
    Honeywell Analytics under a Qual ity Management system that is certified to ISO 9001. As such
    Honeywell Analytics warrants  its products against defective  parts and workmanship and will
    repair or (at its option) replace any instruments which are or  may become defective under proper
    use within 12 months from  date of commissioning by an  approved Honeywell Analytics
    representative or 18 months from  date of shipment from Honeywell Analytics, whichever is the
    sooner. This warranty d oes not cover disposable  batteries or damage caused by accident,
    abuse, abnormal operating conditi ons or poisoning of sensor. 
    Defective goods must be returned to Honeywell  Analytics premises accompanied by a detailed
    description of any issue. Where  return of goods is not practicable Honeywell Analytics reserves
    the right to charge for any site  attendance where any fault is  not found with the equipment.
    Honeywell Analytics shall not be liable for any loss or dama ge whatsoever or howsoever
    occasioned which may be a  direct or indirect result of the use or operati on of the Contract Goods
    by the Buyer or any Party.
    This warranty covers instrument and parts sold  to the Buyer only by authorized distributors,
    dealers and representatives as appointed by Honeywell Analytics. The warranties set out in this
    clause are not pro rata, i.e. the  initial warranty period is not extended by virtue of any works
    carried out there under. 
    						
    							Issue 4 03/2010 H_MAN0630_TP1MAN_EMEAIECO_HAA100021© 2010 Honeywell Analytics11079
    Contact Honeywell Analytics:  
    Find out mor e
    www .honeywellanalytics.com
    Eur ope, Middle East, Africa, India
    Life Safety Distribution AG
    Weiherallee 11a
    CH-8610 Uster
    Switzerland
    Tel: +41 (0)44 943 4300
    Fax: +41 (0)44 943 4398
    [email protected]
    Americas
    Honeywell Analytics Inc. 
    405 Barclay Blvd.
    Lincolnshire, IL 60069
    USA
    Tel: +1 847 955 8200 
    Toll free: +1 800 538 0363 
    Fax: +1 847 955 8210
    [email protected]
    www .honeywell.com
    Technical Services
    EMEAI: 
    [email protected]
    US:        [email protected]
    AP:        [email protected]
    Asia Pacific 
    Honeywell Analytics Asia Pacific 
    #508, Kolon Science Valley (I) 
    187-10 Guro-Dong, Guro-Gu 
    Seoul, 152-050 
    Korea 
    Tel: +82 (0)2 2025 0300
    Fax: +82 (0)2 2025 0329
    [email protected]
    Please Note:While every effort has been made to ensure accuracy in this publication, no responsibility can be accepted for errors or omissions. Data may change, as well as legislation, and you are strongly advised to obtain copies of the most recently issued regulations, standards, and guidelines. This publication is not intended to form the basis of a contract. 
    						