Home > Honeywell > Controller > Honeywell Touchpoint 1 Manual

Honeywell Touchpoint 1 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Touchpoint 1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							   User Settings
    TP1MAN Issue 4_03-10 (MAN0630)41
     
    Event History 
    This menu is for the review the last 10 time and date action records for alarms, faults and
    controller Power On/Off events. 
    1 Access the menu system and select the   menu option. 8 Press OK. 
    The display then shows a 10 second countdown. 
    When the countdown is complete the display shows GOOD if the
    span has succeeded. 
    If the span fails the display shows FA I L and returns to the
    beginning of the span menu.
    9 Press OK.
    The display returns to the menu selection screen. 
    10 Press Cancel.
    Returns controller to normal operation.
    Press Up or Down. The icon flashes.
    2 Press OK.
    The display shows a flashing A1 to 
    indicate Alarm 1 event history is initially 
    selected.
    3 Select from:
    • A1- Alarm 1 (default)
    •A2- Alarm 2
    • F- Fault 
    • On/Off- Power 
    Use the Up/Down buttons.
    4 Press OK to access the selected history.
    001 to 010 are shown on the display to indicate
    the position in the series of records.             
    For example if A1 is selected by pressing OK the screen displays its ON record initially.
    • ON — indicates time/date the alarm activated.
    By pressing Up/Down the OFF record is then displayed.
    • OFF — indicates the time/date when a latched alarm was accepted/reset, or the 
    time/date a non-latched alarm automatically reset. 
    010 indicates the last (10th) record.
    %v/v 
    						
    							   User Settings
    TP1MAN Issue 4_03-10 (MAN0630)42
    6 Press Cancel.
    Goes to the A1 history record.
    Choose further records from A2, F, or Power on/off. 
    7 When record viewing is complete press Cancel.
    The display returns to the menu selection screen. 
    8 Press Cancel.
    Returns controller to normal operation.
    Alarm Levels and Relay Action 
    Sets the alarm levels for Alarm 1 and Alarm 2 as well as how the alarm and fault relays operate.
    For oxygen, either a Rising (oxygen enrichment), or Falling (oxygen deficiency) alarm can be
    selected.
    .
    5 To view the other 9 records repeat the procedure.
    Note The time and date for each record is shown at the bottom of the display in a 
    sequence of three parts. Each part is displayed for 2 seconds.
    For example if the time for the record is 18 minutes past 12 oclock on July 27th, 2004
    then the display shows:
    • 2004 - year 2004 — first
    • 07 27 - 7th month, 27th day — second
    • 12:18 - 18 minutes past twelve — third
    The sequence then repeats.
    1 Access the menu system and select the   
    menu option.
    Press Up or Down. The icon flashes.
    2 Press OK.
    The current A1 (Alarm 1) setting is displayed.
    3 Use Up/Down to change the value.
    A1 alarm levels can be set between 0% and FS (full
    scale). The default setting is 20% of the full scale
    range. 
    4 Press OK to accept the change.
    If the gas units are %v/v and the gas being
    detected is oxygen then a rising alarm, UP, or a
    falling alarm, DOWN, can be set. Use Up/Down
    buttons to change the value.
    O2 only
    %v/v 
    						
    							   User Settings
    TP1MAN Issue 4_03-10 (MAN0630)43
    8 Press OK to accept the change.
    The display now changes to the current A2 Alarm 2 setting. 5 Press OK to accept the change.
    The display changes to the A1 relay action menu.
    The display shows either r 1-d (for relay 1 de-
    energized), or r 1-E (for relay 1 energized). 
    6 Use Up/Down to change the relay action. 
    7 Press OK to accept the change.
    The display changes to the relay latching or non-
    latching menu and shows either r 1-L (for Relay 1
    latching), or r 1-N (for Relay 1 non-latching). 
    Use Up/Down to change the relay action. 
    The diagram shows the effect of latching or non
    latching relays.
    Flashing  visual indicators 
    show alarm has occurred 
    and not pressedCancel 
    Alarm Point
    Alarm Relay
    Operation
    (Latching)
    Alarm Relay
    Operation
    (Non-Latching)
    Audible Alarm 
    Visual AlarmGas Reading                                   Press  button                Press  buttonCancel Cancel 
    Visual alarm not cleared 
    until gas alarm has 
    cleared and 
    pressed Cancel is Visual indicators stop f
    pressed 
    but gas still presentlashing 
    and go steady when Cancel 
    Audible alarm can be silenced with gas present If gas rises again then Audible Alarm re-activates                 
    						
    							   User Settings
    TP1MAN Issue 4_03-10 (MAN0630)44
    9Alarm 2 settings are changed in the same way as for Alarm 1. 
    A2 alarm levels can be set between the A1 alarm level and the full scale range. 
    The default setting is 50% of the full scale range.
    10 Press OK to accept the changes. 
    The display now changes to the F Fault Relay settings. 
    11Fault Relay settings are changed in the same way as for the alarm relays. 
    12 Press OK.
    The display returns to the menu selection screen. 
    13 Press Cancel.
    Returns controller to normal operation.
    Time and Date 
    This menu sets the controller’s real-time clock. 
    1 Access the menu system and select the   menu option.
    Press Up or Down. The icon flashes.
    2 Press OK. 
    8 Press OK to accept the change.
    The display changes to a flashing display of the current time (hours).
    9 Use Up/Down to change the hours.
    Between 00 and 23. At the bottom of the display the current selected year flashes.
    3 Use Up/Down to change the year.
    Between 2002 and 2099. 
    4 Press the OK button to accept the change.
    The display changes to a flashing display of the current month
    setting.
    5 Use Up/Down to change the month.
    Between 1 and 12. 
    6 Press OK to accept the change.
    The display changes to a flashing display of the current day.
    7 Use Up/Down to change the day.
    Between 1 and 31.  
    						
    							   User Settings
    TP1MAN Issue 4_03-10 (MAN0630)45
    10 Press OK to accept the change.
    The display changes to a flashing display of the current time (minutes).
    11 Use Up/Down to change the minutes.
    Between 00 and 59.
    12 Press OK.
    The display returns to the menu selection screen. 
    13 Press Cancel.
    Returns controller to normal operation.
    Power Source 
    This menu programs Touchpoint 1 for the type of available power source(s). 
    The controller can be set to any of three different power supply modes.
    1 Access the menu system and select the   menu option.
    Press Up or Down. The icon flashes.
    2 Press OK.
    The display shows one of the following current selected power modes:
    • dC-1 — AC only power supply
    • dC-2 — AC and DC power supplies 
    • dC-3 — DC only power supply
    3 Use Up/Down to select the required power configuration. 
    Note  If the system is powered by an AC supply, only dC-1 or dC-2 should be selected.
    If the system is powered by a DC supply, only dC-2 or dC-3 should be selected. 
    4 Press OK.
    The display returns to the menu selection screen. 
    5 Press Cancel.
    Returns controller to normal operation.
    Default Configuration
    Touchpoint 1 is supplied from the factory with a standard default configuration. 
    The configuration is based on settings typically used in gas detection systems. 
    The two versions of Touchpoint 1 are factory configured as follows. 
    						
    							   User Settings
    TP1MAN Issue 4_03-10 (MAN0630)46
    mV input detector
    4-20 mA input detector 
    * User configurable alarm set point in the range 10% to 90% of full scale.
    Function Default Configuration
    Display range and units0-100% LEL
    mV Signal 3.5 mV Overrange
    Alarm Relay 1*Alarm level 1 — 20% LEL
    Latching, normally de-energized, energizes on alarm
    (Single Pole Change Over 240 Vac 3A max)
    Alarm Relay 2*Alarm level 2 — 40% LEL
    Latching, normally de-energized, energizes on alarm
    (Single Pole Change Over 240 Vac 3A max)
    Fault RelayNon-latching, normally energized, de-energizes on fault
    (Single Pole Change Over 240 Vac 3A max)
    Function Default Configuration
    Display range and units0-100% FS
    mA Signal0 - 1.5 mA Open circuit fault
    1.5 - 2.5 mA Inhibit
    2.5 - 3.2 mA Drift fault
    3.2 - 4.0 mA Deadband
    4.0 to 20.0 mA Normal operation
    22.0 mA Max. overrange
    Alarm Relay 1*Alarm level 1 — 20% of full scale
    Normally de-energized, energizes on alarm
    (Single Pole Change Over 240 Vac 3A max)
    Alarm Relay 2*Alarm level 2 — 40% of full scale 
    Normally de-energized, energizes on alarm
    (Single Pole Change Over 240 Vac 3A max)
    Fault RelayNon-latching, normally energized, de-energizes on fault
    (Single Pole change over 240 Vac 3A max) 
    						
    							   Maintenance
    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                   47
    WARNINGS
    Touchpoint 1 is designed for installation and use in indoor safe area  non-explosive atmospheres. Instal lation must be in accordance 
    with the recognized standards of the 
    appropriate authority in  the country concerned.
    Before carrying out any work ensure  local regulations and site procedures 
    are followed. 
    Access to the interior of the  controller, when carrying out any work, must only be 
    conducted by trained personnel. Switch  off and isolate the power supply 
    to the controller, or obtain a hot work  permit, when access is required. Take any 
    necessary precautions to  prevent false alarms.
    The detectors/sensors that the controll er connects to may be used for gas 
    detection in hazardous atmospheres. Re fer to the individual detector/sensor 
    instructions for their details. 
    This chapter tells about the following: • general maintenance
    • troubleshooting , see page 39
    • system configuration sheet , see page 40
    • system review check sheet , see page 41
    General Maintenance
    Honeywell Analytics recommend that  the controller’s configuration and operation are checked
    annually using the two check sheets show n at the end of this section. 
    The  System Configuration Sheet  should be referenced during system checks and updated if
    any changes to the system conf iguration have been made as we ll as a calibration log. 
    The  System Review Check Sheet  contains a list of the minimum checks that should be made
    to ensure the proper and safe  functioning of a system.
    The gas detectors connect ed to the controller should be checked by following the procedures
    detailed in their user guides. 
    Maintenance 
    						
    							   Maintenance
    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                48
    Troubleshooting
    The following table details self  diagnostics/problem solving for  Touchpoint 1.
    Configuration Fault ConditionSymptom Action
    Power Supply Faults — subj ect to selected settings 
    DC1 normal:
    Power LED (green)  ON
    Battery icon OFF AC supply failed
    (
    						
    							   Maintenance
    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                  49
    System Configuration Check Sheet
    Controller location  Installed by Date
    Configured by  Date
    Calibrated by Date
    Contact tel no
    Power supply   ......... AC volts  ......... DC volts
    Channel
    TypeSensePoint detector typeOther detector  type
     mV input  mA input Flam.Toxic Oxygen
    STD PlusPro
    1 ..............................
    Comments  (Detail ancillary equipment such as audible/visu al alarm indicators, battery back up systems etc. )
    Channel Configuration Channel Gas Range Units Alarm 1
    Alarm 2Fault
    Level* E/D L/NL Level* E/D L/NL E/D
    1 * For Oxygen state rising (R) or fall ing (F)   E/D Energized or De-Energized   L/NL Latching/Non-Latching
    Calibration Record
    Actual zero reading Zero 
    re-cal? 
    Y/N? New zero 
    reading Actual 
    span 
    reading Span 
    re-cal? 
    Y/N? Span gas 
    conc. New span 
    reading Next cal. 
    due Carried 
    out by Date
    Comments 
    						
    							   Maintenance
    TP1MAN Issue 4_03-10 (MAN0630)
                                                                            \
                                                  50
    System Review Check Sheet/Record
    Company Name  Application Details 
    Contact Name
    Address
    Tel
    Mobile
    Fax
    (Brief application and system overview including ancillary devices)Email
    Customer reported problems/specific requests
    Checklist
    Control System Y N Comments
    Is control system mounted in a suitable place?
    Daily viewing, access for maintenance?
    Is protection suitable for location?
    Indoor/outdoor, enclosure IP /NEMA rating?
    Are there any visual signs of damage?
    Physical damage?
    Is suitable cable/wire used for all connections?
    Screened, SWA, CSA, or AWG?
    Have all cables/wire been terminated correctly?
    Use of crimps, terminals tightened?
    Have all earth/ground connections been made?
    Earth loops?
    Are all the display indi cators working properly?
    LCDs, LEDs?
    Detectors Y N Comments
    Are the detectors located  in a suitable place?
    Lighter/heavier than air gas?  Breathing zone? Ventilation?
    Are the detectors correct for the application?
    Gas? Range? Type?
    Are recommended accessories fitted?
    Weather protection, collecting cone, filters?
    Are the detectors/filters clean?
    Not been painted, filters clean?
    Are the detectors securely mounted?
    Bracket, wall mount, pipe mount?
    Are all glands/conduit secure?
    Securely tightened, seals not perished?
    Have all cables/wires been terminated correctly?
    Use of crimps, terminals tightened?
    Are junction boxes/encl osures closed properly?
    Junction boxes, transmitter enclosures?
    Ancillary Devices Y N Comments
    Are connections to anci llary devices correct?
    Audio/Visual alarms? Signs? Valves? DCS? SCADA?
    Are the devices suitable  for the relay ratings?
    Correct switching power rating or driving other relays ?
    Other General Comments
    Checks carried out by  Date Next check 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Touchpoint 1 Manual