Honeywell Touchpoint 1 Manual
Have a look at the manual Honeywell Touchpoint 1 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Operation TP1MAN Issue 4_03-10 (MAN0630)31 Control Buttons The control buttons are located beneath an access panel underneath the display screen. They are used to cancel alarms and access/navigate the menu system. To access the buttons carry out the following procedure: 1 Access the controller interior. See page 12. Note The Control Buttons Access Panel cannot be opened until access is made. 2 Push down on the finger grip located at the bottom of the Control Buttons Access panel. See the subsequent diagram and the diagram on page 12. 3 Slide the panel down to release it. The panel springs upward and is held in the open position. This provides access to the buttons. The four control buttons provide the following functions: The results of these actions are shown on the display. Button Function In Text Navigates up through menus and lists and is used to select (highlight) a menu option. Also used to increment values, e.g. range.Up Navigates down through menus and lists and is used to select (highlight) a menu option. Also used to decrement values.Down Enters a menu function. Saves a user settingOK Exits/cancels the current screen/option and returns to the previous screen/option. Acknowledges alarm/fault. With no gas event reported, press the button once to put the controller through a self-test routine, see page 26.Cancel Control Buttons Access Panel (removed for clarity) Up Button OK Button Down Button Cancel Button X
Operation TP1MAN Issue 4_03-10 (MAN0630)32 Menus Touchpoint 1 has 6 menus for configuring/controlling the unit. They are represented on the display by the icons shown in the following table lists them and explains what they are for. Using Menus The controller uses a menu system for configuration/control that is displayed/navigated in the following ways. Displaying Menus „Press the and — Up and Down — control buttons at the same time. 000 is displayed in the gas reading position and the Gas Units/Range menu icon flashes. Navigating Menus 1 Press either the or — Up or Down — control buttons. This steps through the menu choices. The associated icon flashes. 2 Press the — OK — control button to enter the selected menu. Accepting Menu Choices „Press the — OK — control button. This accepts the selection/value, or change, and moves to the next step. Menu Description Function More information Gas units/range settings Change gas units (%v/v, %LEL, kppm, ppm) and rangeSee page 38 Set zero and span Calibrate the detector zero and span. See page 40 View Event HistoryCheck the time/date of each alarm and power on/offSee page 41 Set alarm levels and relay actionsChange the gas levels at which alarms occur. Set relays to: latching or non-latching, energized or de-energized, O 2 only — also rising or fallingSee page 42 Set time and dateSet the real-time clock on the controllerSee page 44 Choose power source Set power source to AC, DC or both See page 45
Operation TP1MAN Issue 4_03-10 (MAN0630)33 Cancelling Operations/Choices To cancel operations/choices: „Press the — Cancel — button. This returns to the previous menu level, setting, etc. Pressing Cancel again returns to normal operation. Note The system automatically returns to normal operation if no buttons are pressed for more than 30 minutes. For details of the Common Module menu see page 37. For details of the Channel Module menu see page 43. To change user settings/configuration using the menus and control buttons see page 38. Alarms When any detector event occurs, e.g. Alarm 1, Alarm 2 or Fault, the following occurs: • the status icon for the event flashes, e.g. — for Alarm 1 • the LED for the type of event flashes, e.g. — ALARM • the audible alarm sounds To acknowledge/accept any alarm press the Cancel button. This silences the audible alarm and at the same time the related icon and LED on the display change from flashing to steady. For detailed operation of audible and visual alarms under latching/non latching relay configuration refer to page page 42. Pressing the Cancel button when there are no alarms/faults tests the display and visual indicators, without operating the alarm relays. X
Commissioning TP1MAN Issue 4_03-10 (MAN0630)34 WARNINGS Touchpoint 1 is designed for installation and use in indoor safe area non-explosive atmospheres. Installation must be in accordance with the recognized standards of the appropriate authority in the country concerned. Before carrying out any work ensure local regulations and site procedures are followed. Access to the interior of the controller, when carrying out any work, must only be conducted by trained personnel. Switch off and isolate the power supply to the controller, or obtain a hot work permit, when access is required. Take any necessary precautions to prevent false alarms. Caution Calibration of the gas detector and the controller is mandatory during commissioning to ensure their proper functioning. This chapter describes how to put the two versions of Touchpoint 1 into service with the following different types of gas detectors: • 3-wire mV bridge, see page 34 • 2-wire 4-20 mA sink, see page 36 • 3-wire 4-20 mA source, see page 37 After powering up the Touchpoint 1 for the first time, the controller uses the default factory settings. To customize these settings for new requirements see page 38. Note On the subsequent diagrams, = LED ON, = LED OFF 3-wire mV Bridge This procedure covers connection to gas detectors such as Sensepoint Flammable. Carry out the following procedure 1 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 18. ALARMPOWER FAULT Commissioning
Commissioning TP1MAN Issue 4_03-10 (MAN0630)35 2 Apply power to the controller and switch it on. See page 25. To skip the warm up sequence press the Cancel button for 3 seconds. 3 Check for a minimum voltage of 2.9 Vdc at the detector. If incorrect check for constant current supply of 200 mA +/-2 mA. For detectors other than Sensepoint Flammable refer to their operating instructions. . 4 Close the detector enclosure. For gas detector details see its user manual. 5 Press the Up/Down buttons on the controller simultaneously. This enters the configuration mode and the Set Gas Units and Range menu icon is displayed and flashes. 6 Select the Calibration Menu icon Use the Up/Down buttons. 7 Press the OK button. The top left of the display reads C0 indicating the set zero menu mode.The display shows the gas reading current real zero value. Ensure the sensor is in clean air. 8 Adjust the reading to zero. Use the Up/Down buttons. 9 Press OK. The display shows a 10 second countdown. When the countdown finishes the display shows GOOD if set zero has succeeded. The display then changes to the set span menu mode indicated by CS in the top left of the display. If set zero fails the display shows FA I L and returns to the start of the set zero mode. 10 Fit a flow adapter to the gas detector sensor. First remove any accessory fitted to the sensor, e.g. weather protection. 11 Apply calibration (span) gas to the detector. Adjust the gas flow rate to 0.3 l/min. ALARM POWER FAULT ALARM POWER FAULT
Commissioning TP1MAN Issue 4_03-10 (MAN0630)36 Note Honeywell Analytics recommend the use of half full-scale gas for calibration purposes (contact a distributor for the supply of calibration gas). The controller now displays the actual gas measurement at the gas detector. 12 Adjust the reading to the actual concentration of the calibration gas applied to the sensor. Use the Up/Down buttons. 2-wire 4-20 mA Sink This describes connection to gas detectors such as Sensepoint Toxic. 1 Set up the gas detector. Refer to the detector’s user manual for details describing how to set up the detector. 2 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 19. 3Follow step 2 on page 35. 4 Check for a minimum voltage of 16 Vdc at the gas detector. For detectors other than Sensepoint Toxic/Oxygen refer to their operating instructions. 5 Check that the Touchpoint 1 display shows the correct gas units and range for the detector in use. If not follow the procedure on page 38 to change the gas units and range. 6Follow step 4 on page 35, to step 16 on page 36. 13 Press the OK button. The display shows a 10 second countdown. If the set span succeeds the display shows GOOD. If the set span fails the display shows FA I L and returns to the beginning of the set span mode. After successfully setting the span the display returns to the menu selection mode. 14 Switch off the calibration test gas and remove the flow adapter from the detector. 15 Refit any accessory to the detector. 16 Return Touchpoint 1 to normal operation. Press the Cancel button. Alternatively select a different menu option. ALARM POWER FAULT
Commissioning TP1MAN Issue 4_03-10 (MAN0630)37 3-wire 4-20 mA Source This covers connection to gas detectors such as Sensepoint Plus and Sensepoint Pro. 1 Set up the gas detector. Refer to the detector’s user manual for details describing how to set up the detector. 2 Check that all power and electrical connections to the controller, and electrical connections to the gas detector are correct. For gas detector access see its user manual. For detector to controller wiring details see page 20 and page 21. 3Follow step 2 on page 35. 4 Check for a minimum voltage of 12 Vdc at the gas detector. See the gas detector user manual. For detectors other than Sensepoint Plus and Sensepoint Pro refer to their operating instructions. 5 Check that the controller’s display shows the correct gas units and range for the detector in use. If not follow the procedure on page 38 to change the gas units and range. 6Follow step 4 on page 35, to step 16 on page 36.
User Settings TP1MAN Issue 4_03-10 (MAN0630)38 The controller is supplied pre-configured with factory defaults, see page 45. These can be used if suitable, or customized by the user to suit site requirements. This chapter explains how to: • set gas units and range, see page 38 • set zero and span, see page 40 • browse Touchpoint 1’s event record, see page 41 • set alarm levels and relay actions, see page 42 • set the real-time clock, see page 44 • set the power source, see page 45 Before performing any of the above actions refer to the procedures that explain how to use menus, see page 32. The following table provides a summary of the configuration options available. For detailed step-by-step instructions for each menu see the subsequent sections. Gas Units and Range WARNING If the range is changed, the alarm set points also change. Verify desired alarm set points. This menu is the first one displayed when the menu system is accessed. It sets the units of gas measurement and the range. 1 Press the Up and Down buttons simultaneously. This accesses the menu system and displays the menu icon, which flashes. 2 Press OK. The current units and range are displayed. 3 Press Up or Down to select a different unit of gas measurement. See the subsequent table. 4 Press OK to accept the selected unit. The display now shows the current range. 5 Press the Up or Down down buttons to select a different range. Default units and ranges are shown in this table. Caution If the range is changed, the alarm level will also be changed. Set desired alarm levels per page 42. Unitkppm ppm %LEL %v/v Range1.0 - 999.9 1.0 - 999.9 or 10 - 999910 - 100 1.0 - 100 User Settings
User Settings TP1MAN Issue 4_03-10 (MAN0630)39 %v/v / / / / / Units and Range Select kppm, ppm, %LEL or %v/v Change range value Finished. Returns to Configuration Menu CalibrationSet Zero (C0). With zero gas at detector adjust value to zero For O 2 only apply N 2 at 0.3 liter/minWait for 10s count down. If OK GOOD is displayed. If fail FA I L is displayed and return to set Zero Set Span (CS). Apply cal. gas. When stable adjust value to cal. gas concentration Wait for 10s count down. If OK GOOD is displayed. If fail FA I L is displayed and return to set span Finished. Returns to Configuration Menu HistorySelect A1, A2, F or ON/OFFSelected event shows with Year, Date, and Time. Select next record. to return to selection Alarms/ Relays A1 alarm level. Change to new value.Select r1-E (energized) or r1-d (de- energized) Select r1-L (latching) or r1-N (non-latching) Repeat for A2 alarm level, energized and latching status Repeat for Fault (energized status only) O2 only - select rising (rISE) or falling (FA L L) alarm Time/DateSelect year (2000-2099)Select month (1-12) Select day (1-31) Select hour (0-23) Select minutes (0-59) Finished. Returns to Configurati on Menu Power Source Select dC-1 (AC), dC-2 (AC&DC or dC-3 (DC) Finished. Returns to Configuration Menu / / / / / X X X
User Settings TP1MAN Issue 4_03-10 (MAN0630)40 6 When settings are complete press OK. Returns to the menu selection screen. 7 Press Cancel. Returns controller to normal operation. Zero and Span This menu is for calibrating controller measurements to the connected gas detector. 1 Access the menu system and select the menu option. Press Up or Down. The icon flashes. 2 Press OK. The top left of the display reads CO to indicate the set zero menu mode. The gas reading displays the current real zero value. Note Ensure the sensor is in clean air before carrying out the next step. For oxygen apply nitrogen to the sensor at 0.3 l/min. 3 When the gas reading is stable adjust the reading to zero. Use the Up/Down buttons. Note Honeywell Analytics recommend the use of half full-scale gas for calibration purposes (contact a distributor for the supply of calibration gas). The gas reading on the controller display shows the measured reading from the detector 7 When the gas reading is stable adjust the reading to the actual concentration of the calibration gas being applied to the detector. Use the Up/Down buttons. 4 Press OK when the reading is zero. The display now shows a 10 second countdown. When the countdown is complete the display shows GOOD if the zero has succeeded, and then changes to the span mode. If the zero fails the display shows FA I L and return to the beginning of the set zero mode. After successfully setting the zero, the display then changes to show CS in the top left to indicate the set span mode. For O 2 only — fit a flow adapter to the gas detector sensor, see step 5, and apply N 2 at 0.3 l/min. 5 Fit a flow adapter to the gas detector sensor. First remove any accessory fitted to the sensor, e.g. weather protection. 6 Apply calibration (span) gas to the detector at a flow rate of 0.3 l/min.