TZ-3 TOTALZONE® ZONE CONTROL PANEL 11 68-0223-2 . Stages Based On Number of Zones Calling The thermostat controls the first stage of heat or cool. The second stage of heat and cool and the third stage of heat are ener gized by the percentage of zones calling. See Table 4. Set the DIP switches as follows: See Table 4 to determine the number of zones re quired to activate stages of equipment based on the number of zones in the system. Staging is based on the zones available in the s ystem, not the...
Page 12
TZ-3 TOTALZONE® ZONE CONTROL PANEL 68-0223-2 12 Rebooting Microprocessor Certain conditions can hang up the microprocessor. To reset it, press and release the Boot button. The system reboots and enters the Purge mode. Discharge Air Temperature Sensor The Discharge Air Temperature Sensor (not included) is a su pply-duct-mounted temperature probe used to control capacity and prevent over-heating or coil-icing. The sensor attaches to the TL terminals on the panel. Set the hi gh limit temperature on...
Page 13
TZ-3 TOTALZONE® ZONE CONTROL PANEL 13 68-0223-2 TROUBLESHOOTING Table 5. Troubleshooting. Symptom Possible Cause Action No LEDs are IlluminatedNo power to the board.Check for 24 Vac (±10%) across TR1 and TR2 Shorted wire.Check fuse. If hot, a short exists in thermostat, damper, or Zone-A-Lone wiring. Damper LEDs on, but no other LEDs illuminated.Insufficient voltage.Check for 24 Vac (±10%) across TR1 and TR2. Incorrect configuration.Check jumpers and DIP switches for correct configuration. Erratic...
Page 14
TZ-3 TOTALZONE® ZONE CONTROL PANEL 68-0223-2 14 Table 6. DIP Switch Settings and Functions. Table 7. LED Indicators. DIP Switch Function Off (default) On 1Staging by number of zones calling.Stages timer or thermostat controlled.Stages controlled by number of zones calling. 2ZMS low limit.40°F48°F 3Purge mode timing.Three and one-half minutes.Two mi nu t es . 4Fan control during purge.Controlled by panel.HVAC equipment controlled 5Control of W2 outpu.tTimer controlled.Controlled by W2 from...
Page 15
TZ-3 TOTALZONE® ZONE CONTROL PANEL 15 68-0223-2 See Fig. 20 for TZ-TotalZone Zone Control Panel. Fig. 20. TZ-3 TotalZone Zone Control Panel. ZoneMAX™ TERMINALSSYSTEM STATUS LED INDICATIORS TEST JUMPERS (NOT USED)ZONE DAMPER LED INDICATORS ZONE-A-LONE™ SWITCH BOOT BUTTON EMERGENCY HEAT SWITCH RESETTABLE FUSETRANSFORMER TERMINALS ZoneMAX™ TEMP SETTING ZONE, THERMOSTAT & DAMPER MOTOR TERMINALSREMOTE ZONE-A-LONE™ CONTROL TERMINALS STAGE TIMER DIP SWITCHES FOR SYSTEM CONFIGURATION 2 STAGE EM HEAT...
Page 16
68-0223-2 G.H. Rev. 9-01 www.honeywell.com/yourhome Home and Building Control Home and Building Control Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers. TZ-3 TOTALZONE® ZONE CONTROL PANEL