Home > Honeywell > Control panel > Honeywell Taz3 Manual

Honeywell Taz3 Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Taz3 Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    11 68-0223-2
    .
    Stages Based On Number of Zones Calling
    The thermostat controls the first stage of heat or cool. The 
    second stage of heat and cool and the third stage of heat are 
    ener
    gized by the percentage of zones calling. See Table 4. 
    Set the DIP switches as follows:
    See Table 4 to determine the number of zones re
    quired to 
    activate stages of equipment based on the number of zones in 
    the system. Staging is based on the zones available in the 
    s
    ystem, not the number of zones used for the particular 
    application. As zones satisfy, stages 2 and 3 drop out. 
    Thermostat Operation
    Conventional Thermostats
    Conventional (R,W,Y,G) heat/cool thermostats can be used 
    with the TZ-3 to control single or multi-stage gas, electric or oil 
    s
    ystems and heat pumps with auxiliary heat. The panel can 
    be configured to control second stage heat and cool and third sta
    ge heat using a 5-30 minute panel, or staging can be 
    controlled by the percentage of zones calling. The O and B 
    e
    quipment terminals are energized for changeover use with 
    heat pumps.
    Heat Pump Thermostats
    HEAT PUMP THERMOSTATS WITH SINGLE Y OUTPUT
    Heat pump thermostats can be used if thermostat control of 
    2nd stage is desired. Thermostats that have a single Y 
    terminal for first stage heat and cool can be used.  When 
    selected, all thermostats must be similar.
    If the thermostat ener
    gizes O on a call for cool, DIP switch 7 
    must be set to On and the O thermostat  wire connected to W 
    on the thermostat connections for that zone. If the thermostat 
    ener
    gizes B on a call for heat, DIP switch 6 must be set to On 
    and the B wire connected to W on the 
    panel. In either case, 
    the O is always energized to the equipment in cooling, and the 
    B is always energized to the equipment in heating.
    IMPORTANT
    Be sure DIP switches 6 and 7 are never both in the 
    On position. 
    HEAT PUMP THERMOSTATS WITH SEPARATE Y1 AND W1 
    TERMINALS
    Use heat pump thermostats with separate Y1 and W1 
    terminals for first stage heat and cool.  Keep DIP switches 6 
    and 7 in the Off position when thermostat O or B wire is not 
    used.
    Emergency Heat Control
    Emergency heat is defined as using an auxiliary heat source 
    without using the heat pump. When the Em Heat switch or a 
    thermostat puts the panel in the emergency heat mode, the 
    heat 
    pump is locked out and calls for heat are sent to the E 
    terminal.
    A heat 
    pump thermostat can also control emergency heat 
    from the thermostat system switch.  An L terminal energized 
    during the emergency heat mode is required. The 
    recommended heat 
    pump thermostats all have hot L 
    terminals. See Table 1.
    The two sta
    ge Em heat jumper connects W2 and E. Jumper 
    both pins to energize the W2 equipment on a call for 
    emergency heat. When E is a different source of heat than 
    W2, remove the 
    jumper (for example, two-stage heat pump 
    with electric heat strip auxiliary heat ). The jumper is located 
    below the equipment terminals on the lower-left corner of the 
    panel.
    Multi-Stage Thermostats
    Use multi-stage thermostats to control two stages of heat via 
    W1 and W2 thermostat terminals. Control the third stage of 
    heat through the stage timer built into the panel. Control the 
    second sta
    ge of cooling with the timer.
    Manual and Automatic Changeover Thermostats
    Automatic changeover thermostats provide automatic 
    changeover by zone. Manual changeover thermostats heat or 
    cool based on the mode of each zone thermostat. 
    DIP Switch NumberStatus
    1Off
    5On
    DIP Switch NumberStatus
    1On
    5Off
    Table 4. Staging by Percentage of Zones Calling.
    Number of 
    Zones in 
    SystemNumber of Zones Required 
    2nd Stage 
    Heat3rd Stage 
    Heat2nd Stage 
    Cool
    32 32
    42 33
    52 43
    63 54
    73 54
    83 65
    94 75
    10 4 7 6
    11 4 8 6
    12 5 9 7 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    68-0223-2 12
    Rebooting Microprocessor 
    Certain conditions can hang up the microprocessor. To reset 
    it, 
    press and release the Boot button. The system reboots and 
    enters the Purge mode. 
    Discharge Air Temperature Sensor
    The Discharge Air Temperature Sensor (not included) is a 
    su
    pply-duct-mounted temperature probe used to control 
    capacity and prevent over-heating or coil-icing. The sensor 
    attaches to the TL terminals on the panel.
    Set the hi
    gh limit temperature on the maximum temperature 
    dial on the panel, located left of the stage timer. See. Fig. 19. 
    Set the tem
    perature from 110 °F to 160°F in ten-degree 
    increments. The recommended setting for fossil fuel/ electric 
    systems is 160°F (default factory setting). For heat pump 
    s
    ystems, the recommended setting is 120F. 
    The coolin
    g temperature limit can be set at 40°F or 48°F. 
    Fig. 19. Maximum temperature dial.
    IMPORTANT
    Be sure the Discharge Air Temperature Sensor wir-
    ing does not run parallel with line voltage wiring 
    unless more than 12 in. of separation exists or 
    shielded cable is used.
    Use DIP switch 2 to change cooling limit settings. 
     
    If the s
    ystem trips due to exceeding a high or low temperature 
    limit, the heating or cooling system shuts down and the fan  
    continues runnin
    g to purge the conditioned air from the plenum. 
    When the low limit is tri
    pped, the Cool LED flashes until it 
    resets. When the high limit is tripped, the Heat LED flashes 
    until it resets.
    Once the tem
    perature recovers by ten degrees, the 
    equipment run resumes.
    Zone-A-Lone Switch 
    When the Zone-A-Lone switch is in the occupied position and 
    the OC/OC terminals are not used, the s
    ystem functions as a 
    normal zone control system. When switched to the 
    unoccupied position, all dampers are opened and all requests 
    for heat, cool, or fan, exce
    pt from zone one, are not honored. 
    The zone one thermostat becomes the controlling thermostat 
    for the entire system. During long unoccupied periods, one 
    thermostat can be set back instead of ad
    justing each zone 
    thermostat in the building. 
    The T8601D2027 and T8611G2051 include two OC terminals.  
    When wired to the TZ-3 OC terminals, and with the Zone-A-
    Lone switch in the occu
    pied position, the board enters the 
    unoccu
    pied mode during the Leave and Sleep programs. This 
    feature requires two extra wires to the Zone 1 thermostat.
    Circuit Breaker Protection 
    A built-in thermal circuit breaker protects the TotalZone panel. 
    This circuit breaker 
    protects the panel against shorts in the 
    thermostat and damper wiring and the remote occupied/ 
    unoccupied switch. It does not protect against shorts in the 
    wirin
    g of the HVAC equipment into the panel.
    When the circuit breaker is tri
    pped, none of the LEDs 
    illuminate and the 
    yellow rectangular component located to 
    the left of the TR1 and TR2 terminals is hot to the touch.   
    Remove 
    power to the panel for at least ten seconds to allow 
    the circuit breaker to cool off and reset. To eliminate the short, 
    verif
    y the dampers and thermostat wiring.
    Fan On In Heat
    The system blower can be set to come on with a call for heat 
    as re
    quired for hydro-air, heat pump, or electric heat systems.  
    Set the blower using DIP switch 8.
    TotalZone Add-A-Zone Panels
    Using TotalZone Add-A-Zone Panels, the system can be 
    ex
    panded to up to 30 zones. There are three models: TAZ-1, 
    one zone; TAZ-2, two zone; and TAZ-3, three zone. Two wires 
    are re
    quired to connect the TAZ to the TZ-3.  
    IMPORTANT: 
    When multiple panels are used, it is important that 
    the transformers be in-phase. Check the phasing by 
    measuring for 24V across the TR2 transformer termi-
    nals on each panel. There should be 0 Vac. If not, 
    reverse the TR1and TR2 transformer wires on one of 
    the panels and recheck.
    See Fig. 13 and the TAZ installation instructions for more 
    information.
    Dip SwitchStatus
    Cooling 
    Temperature 
    Limit
    2Off40°F
    2On48°F
    130  F
    MAXIMUM
    TEMPERATURE
    M19079
    120  F
    110  F
    140  F
    150  F
    160  F
    DIP Switch 8Fan Control
    OffHVAC system 
    OnFan on in heat 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    13 68-0223-2
    TROUBLESHOOTING
    Table 5. Troubleshooting.
    Symptom Possible Cause Action
    No LEDs are IlluminatedNo power to the board.Check for 24 Vac (±10%) across TR1 and TR2
    Shorted wire.Check fuse.  If hot, a short exists in thermostat, damper, 
    or Zone-A-Lone wiring.
    Damper LEDs  on, but no 
    other LEDs illuminated.Insufficient voltage.Check for 24 Vac (±10%) across TR1 and TR2.
    Incorrect configuration.Check jumpers and DIP switches for correct 
    configuration.
    Erratic OperationEmergency Heat switch on.Turn off (down) Emergency Heat switch.
    Zone-A-Lone Feature on.Turn off (up) Zone-A-Lone.
    Heat pump operates 
    incorrectly or not at all.Incorrectly wired.Ver i fy that W1 and Y1 equipment terminals are jumped.
    Incorrectly configured.Ver i fy DIP switches 6 and 7 are correctly set for the type 
    of thermostat used.
    Heat LED flashing.High limit  reached.LED stops flashing with ten-degree fall.
    Cool  LED flashing.Low limit  reached.LED stops flashing with ten-degree rise.
    Idle LED flashes five  times 
    on bootup.ZMS problem or not 
    connected.Ver i fy that ZMS (if any) is connected, and wired 
    correctly.
    Idle LED flashes 
    continuousl
    y
    ZMS failure.Check for dc voltage across TL terminals:
    If 0 volt = short.
    If 1 volt = o
    pen.
    If .2 to .8 volt = normal.
    Add-A-Zone not operating.Incorrectly configured.Ver i fy DIP switch settings on the TAZ panels.
    Incorrectly wired.Check AZ1and AZ2 for correct wiring.
    Be sure that AZ1 and AZ2 are at least 12 in. from line 
    volta
    ge wiring.
     Be sure the transformers are in-phase. 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    68-0223-2 14
    Table 6. DIP Switch Settings and Functions.
    Table 7. LED Indicators. DIP Switch Function Off (default) On
    1Staging by number of zones 
    calling.Stages timer or thermostat 
    controlled.Stages controlled by number of zones 
    calling.
    2ZMS low limit.40°F48°F
    3Purge mode timing.Three and one-half minutes.Two  mi nu t es .
    4Fan control during purge.Controlled by panel.HVAC equipment controlled
    5Control of W2 outpu.tTimer controlled.Controlled by W2 from thermostat,
    6Cool changeover from 
    thermostat.Not using B on single Y 
    thermostats; or using 
    conventional thermostats.Using B on single Y thermostat.
    7Heat changeover from 
    thermostat.Not using O on single Y 
    thermostats; or using 
    conventional thermostats.Using O on single Y thermostat.
    8Fan control in heat.Fan controlled by panel in cool 
    and HVAC equipment in heat.Panel in heat and cool controlling fan.
    LED Color Illuminated Not Illuminated Flashing
    HeatRedHeat callNo heat calls.High limit reached
    CoolGreenCool callNo cool calls.Low limit reached
    PurgeAmberPurge modeNot in Purge mode.ZMS failure
    IdleRedNo callsCall for heat, cool, or fan.Initial powerup without ZMS 
    wired
    FanGreenFan only callNo fan only call.—
    EM HeatRedEmergency Heat modeNot in emergency Heat mode.—
    Zone 1,2,3Zone 
    1,2,3Green—open
    Red—closed
    Amber—movin
    g (some 
    dampers)
    —— 
    						
    							TZ-3 TOTALZONE® ZONE CONTROL PANEL
    15 68-0223-2
    See Fig. 20 for TZ-TotalZone Zone Control Panel.
    Fig. 20. TZ-3 TotalZone Zone Control Panel.
    ZoneMAX™
    TERMINALSSYSTEM STATUS 
    LED INDICATIORS TEST JUMPERS
    (NOT USED)ZONE DAMPER 
    LED INDICATORS
    ZONE-A-LONE™
    SWITCH BOOT
    BUTTON
    EMERGENCY
    HEAT SWITCH
    RESETTABLE 
    FUSETRANSFORMER
    TERMINALS ZoneMAX™
    TEMP
    SETTING
    ZONE, THERMOSTAT & DAMPER
    MOTOR TERMINALSREMOTE 
    ZONE-A-LONE™
    CONTROL 
    TERMINALS STAGE
    TIMER
    DIP SWITCHES FOR 
    SYSTEM CONFIGURATION 2 STAGE
    EM HEAT
    JUMPERHVAC
    EQUIPMENT
    TERMINALS
    ADD-A-ZONE™
    TERMINALS
    M13421 
    						
    							68-0223-2   G.H.  Rev. 9-01 www.honeywell.com/yourhome Home and Building Control Home and Building Control
    Honeywell Honeywell Limited-Honeywell Limitée
    1985 Douglas Drive North 35 Dynamic Drive
    Golden Valley, MN  55422 Scarborough, Ontario
    M1V 4Z9
    Printed in U.S.A. on recycled 
    paper containing at least 10% 
    post-consumer paper fibers.
    TZ-3 TOTALZONE® ZONE CONTROL PANEL 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell Taz3 Manual