PRODUCT DATA 68- 0223-2® U.S. Registered Trademark Copyright © 2001 Honeywell All Rights Reserved TZ-3 TotalZone® Zone Control Panel APPLICATION The TZ-3 TotalZone Zone Control Panel controls single-stage, multi-sta ge, conventional or heat pump heat/cool equipment. It controls 2 or 3 zones, and is expandable up to 30 zones with optional TotalZone® Add-A-Zone™ Zone Control Panel. FEATURES • Up to three stages heat and two stages cooling can be controlled by thermostat or built-in timer, based on...
Page 2
TZ-3 TOTALZONE® ZONE CONTROL PANEL 68-0223-2 2 SPECIFICATIONS Electrical: 24 Vac, 60 Hz. Dimensions: See Fi g. 1. Mounting: Mounts with three screws (provided) through holes in cabinet back Wiring: 18- gauge wire for all equipment and system connections Wiring Connections: Thermostat: W2, L, G, Y, R, W Dam pers: M6 (Closed); M4 (Open); M1 (Common) ZoneMax TL, TL Zone-A-Lone: OC,OC. Transformer: TR1 (hot), TR2 (common). E quipment: Y2, Y1, O, R, G, B, W1, E, W2, W3. Thermostats (See Table...
Page 3
TZ-3 TOTALZONE® ZONE CONTROL PANEL 3 68-0223-2 Table 2. Recommended Dampers. Table 3. Required Accessories (Not Supplied With Panel). Honeywell Damper Type Round Rectangular Power-open/power-closedMARDIOBD AOBD AOBD-BM CDO-51 Spring-open/power-closedARDZDB ZDS Accessory DescriptionBypass Rating (cfm) 40 VA transformerAT140D1046 (PMT-40)— Capacity protectorZMS, DATS (C7735A1000)— Round static pressure regulator dam per 7 SPRD 8 SPRD 9 SPRD 10 SPRD 12 SPRD 14 SPRD 16 SPRD 18 SPRD300 400 600 750 1200...
Page 4
TZ-3 TOTALZONE® ZONE CONTROL PANEL 68-0223-2 4 INSTALLATION Mounting CAUTION Equipment Damage Hazard. Do not mount TZ-3 inside HVAC equipment Mount onl y on wall or on cold air return 1. Mount the thermostats in each zone of the livin g space usin g the installation instructions provided with each thermostat. 2. Mount the dam pers in the ductwork using the installa- tion instructions provided with each damper. 3. Mount the TZ-3 zone panel near the HVAC equipment; locate it on a wall or on the...
Page 5
TZ-3 TOTALZONE® ZONE CONTROL PANEL 5 68-0223-2 Fig. 4. Heat pump thermostat with separate Y1 and W1 terminals and multi-stage thermostat wiring. If the thermostat selected has a sin gle Y terminal, see Fig. 5. Select a sin gle Y thermostat for each zone. See Table 1. Set DIP switch 6 or 7 (not both) to the On position. Set switch 6 to On when B on the thermostat is wired to W on the panel. Set switch 7 to On when 0 on the thermostat is wired to W on the panel. When usin g the zone thermostat to...
Page 6
TZ-3 TOTALZONE® ZONE CONTROL PANEL 68-0223-2 6 Fig. 9. MARD and CDO-51 Damper wiring. ML6161 Motor Actuator When the ML6161 Motor Actuator is used, wire as shown in Fig. 10. Wire the R8222 relay to prevent the damper LED from constantl y lighting amber. Fig. 10. ML6161 Damper Motor Actuator wiring. Transformer Wire the transformer to the panel as shown in Fig. 11. NOTE: If the installation includes an Add-A-Zone panel, see the TotalZone Add-A-Zone Panels section. Fig. 11. Transformer wiring....
Page 7
TZ-3 TOTALZONE® ZONE CONTROL PANEL 7 68-0223-2 Multi-Stage: Wire the equipment as shown in Fig. 14 using the W2 terminal for second stage of heat and the W3 terminal for third sta ge of heat. Wire the Y2 for second stage of cooling. Fig. 14. Heating and cooling equipment. Heat Pump Equipment Wire the heat pump to the equipment terminals on the panel as shown in Fi g. 15. Refer to manufacturer’s instructions for additional wiring instructions and substitute the TZ-3 equipment terminals for the...
Page 8
TZ-3 TOTALZONE® ZONE CONTROL PANEL 68-0223-2 8 Fig. 15. Heat pump with auxiliary heat wiring. . Fig. 16. Trane XL 1800 with TAYPLUS 103 in restricted mode wiring. Water Source Heat Pumps Wire the equipment, as applicable, to the TZ-3 as shown in Fi g. 17. Turn DIP switch number 8 to On for fan on in heat. Remove the two-sta ge emergency heat jumper. W2 W3 M19075 E W1 W2E B G R 24V TRANSFORMER FAN RELAYREVERSING VALVE (COOL) EMERGENCY HEATING RELAY 2 STAGE HEATING RELAY HEAT PUMP CONTROLSTZ-3 PA N E L...
Page 9
TZ-3 TOTALZONE® ZONE CONTROL PANEL 9 68-0223-2 Waterfurnace: Wire this system to the panel as shown in Fig. 17 except use two isolation relays on compressor wires W1, Y1 and W2, Y2. Fig. 17. Water source heat pump wiring. STARTUP AND CHECKOUT After the installation is complete, verify correct operation as follows: 1. Place the Em Heat switch in the Off (down) position. 2. Place the Zone-A-Lone switch in the Occup/Remote (up) position. 3. Ver i f y that the DIP switches are set correctly. See...
Page 10
TZ-3 TOTALZONE® ZONE CONTROL PANEL 68-0223-2 10 OPERATION Sequence of Operation On a call for heating or cooling, the zone damper stays open to the calling zone, and the dampers close to the zones that are not callin g. The TZ-3 panel brings on the heating or cooling and conditioned air is delivered to the calling zone until that zone is satisfied. When the call is satisfied, the s ystem enters the Purge mode. This holds open the damper of the last zone calling and purges into that zone. The purge...