T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 2162-0254—13 Fig. 46. Setup - Sensors - Sensor B - Throttling Range. 2.2.4.2. THROTTLING RANGE (Sensor B only) The throttling range for the modulating high or low limit positions the setpoint at the end of the throttling range. For example, with a high limit at Sensor B of 200°F and a throttling range of 10°F, the modulating output controlling Sensor A begins to throttle back at 190°F (88°C), and fully closes at 200°F (93°C). Conversely, the...
Page 22
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1322 Fig. 49. Setup - Outputs - Mod Out - Type. 2.3.1.1. TYPE (of output signal) 1.From the Mod menu, use the and buttons to highlight TYPE. 2.Press the button to display the Type selections. 3.Use the and buttons to highlight the desired output type. Default: 4-20 mA 4.Press the button to accept the selected type and return to the Mod menu. Fig. 50. Setup - Outputs - Mod Out - Minimum Output Percentage . 2.3.1.2. MIN OUT...
Page 23
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 2362-0254—13 Fig. 52. Setup - Outputs - Mod Out - Derivative. 2.3.1.4. DERIVATIVE The Derivative default value is factory set to zero (no derivative control). It is strongly recommended that the derivative remain at zero (0) unless you have a very good reason to adjust it. Derivative control is not needed in the vast majority of HVAC applications. 1.From the Mod menu, use the and buttons to highlight DERIVATIV. 2.Press the button to...
Page 24
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1324 Fig. 55. Setup - Outputs - Mod Out - Exit. 2.3.1.7. EXIT Press thebutton (or highlight EXIT and press the button) to exit the Mod menu and return to the Outputs menu. If you have a second modulating output to configure, go to “2.3.1. Setting up the Modulating Outputs” on page 21. If you are finished setting up the modulating outputs, continue with “2.3.2. NBR OF RELAYS”. Fig. 56. Setup - Outputs - Number of Relays. 2.3.2. NBR OF...
Page 25
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 2562-0254—13 Fig. 58. Setup - Outputs - Options - Schedule. 2.3.3.1. USE SCHED 1.Press the button to display the schedule selections. 2.Use the and buttons to highlight YES or NO. Default: NO 3.Press the button to accept the value and display the MIN OFF option. Selecting NO disables scheduling for all outputs. Selecting YES enables scheduling for all outputs. When YES is selected, all individual outputs default to follow the...
Page 26
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1326 Fig. 60. Setup - Outputs - Options - DI Options. 2.3.3.3. DI OPTIONS (digital input options) The DI Option you select applies to all outputs. This option overrides any Setpoint/Setback values entered in the Schedule. 1.Press the button to display the DI Option selections. 2.Use the and buttons to highlight DISABLE, SETBACK, or IGNORE. Default: DISABLE 3.Press the button to accept the value and display the SHOW RT...
Page 27
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 2762-0254—13 Fig. 63. Setup - Outputs - Options - Exit. 2.3.3.6. Exit Options Setup Press the button (or highlight EXIT and press the button) to exit and return to the Outputs menu. Continue with “2.3.4. Setting up the Relays” Fig. 64. Setup - Outputs - Relay Menu. 2.3.4. Setting up the Relays 1.From the Outputs menu, use the and but- tons to highlight the desired relay (1-4 depending on model). 2.Press the button to display the selected...
Page 28
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1328 Fig. 66. Setup - Outputs - Floating Relay - Menu. 2.3.4.1.1. Floating Relay Menu The Floating option is only available on the T775B2016, T775B2024, T775B2032, and T775B2040 models. When Relay 1 or Relay 3 is setup as floating, relays are paired and the Float 1 or Float 2 menu displays with the selections shown in Fig. 66. Fig. 67. Setup - Outputs - Floating Relay - Actuator. 2.3.4.1.1.1. ACTUATOR (floating relay only) The Actuator...
Page 29
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 2962-0254—13 Fig. 69. Setup - Outputs - Floating Relay - Derivative. 2.3.4.1.1.3. DERIVATIVE (modulating/floating relay only) The Derivative option displays only on the T775B2016, T775B2024, T775B2032, and T775B2040 models when the Type option = Floating. 1.From the menu, use the and buttons to highlight DERIVATIV. 2.Press the button to display the actuator value. 3.Use the and buttons to increase/decrease the desired number of...
Page 30
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1330 Fig. 72. Setup - Outputs - Relay - Exit. 2.4. EXIT Setup Mode Press the button to exit the selected relay set up and return to the Outputs menu. To setup the next relay output go to “2.3.4. Setting up the Relays” on page 27. If you are finished setting up the relay outputs, press the HOME button to exit Setup mode and return to the home screen display. This completes the Setup procedure. 3. SCHEDULING Scheduling provides the...