INSTALLATION INSTRUCTIONS 62-0254-13 T775A/B/M Series 2000 Electronic Stand-Alone Controllers PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of commercial and agricultural controls capable of remote sensing of temperature and providing switched and/or proportional outputs to various types of loads. Five models have analog (modulating) outputs for actuator and motor control, and NEMA-4 weatherproof enclosures are available for wet environments. IMPORTANT...
Page 2
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—132 Temperature Sensorsa The controller accepts 1,097 Ohms PTC at 77°F (25°C): • 50021579-001 – Standard sensor (included with all models except NEMA 4X models) • T775-SENS-STRAP– Strap on sensor with wiring box • T775-SENS-WR – Water resistant with 5 foot leads (included with NEMA 4X models) • T775-SENS-WT – Watertight with 6 foot lead • T775-SENS-OAT – Outdoor air temperature sensor • C7031B2005 – 6 inch duct mount with wiring box •...
Page 3
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 362-0254—13 BEFORE INSTALLATION Review the “SPECIFICATIONS” on page 35 before installing the controller. When Installing This Product 1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2.Check ratings given in instructions and on the product to ensure the product is suitable for your application. 3.Installer must be a trained, experienced service technician. 4.After...
Page 4
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—134 Wiring Connections Access To access the wiring connections, remove the two screws on the left side of the enclosure and gently swing open the top. Be careful to not stress the ribbon cables that connect the keypad and LCD display to the controller circuit board. Temperature Sensor Wiring CAUTIONElectrical Shock Hazard. Can short equipment circuitry. Make sure that metal tube of sensor does not short against T terminals in...
Page 5
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 562-0254—13 Controller Wiring WARNINGElectrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage. CAUTIONDo not use 24 Vac power to power any external loads if 120 Vac or 240 Vac is used to power the T775A/B/M controller. CAUTIONA separate earth ground is required. Equipment damage can result if the...
Page 6
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—136 Controller Wiring Details The wiring connection terminals are shown in Fig. 7 and are described in Table 2. See Fig. 8 – 22 beginning on page 6 for typical T775A/B/ M wiring applications. Fig. 7. T775A/B/M Terminal and Feature Locations. NOTE: Refer to Table 1 on page 1 for the specific configuration of sensors and outputs supported by the model you are installing. NOTE: For NEMA 4 enclosures, use waterproof fit- tings for...
Page 7
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 762-0254—13 Fig. 9. Wiring for Four-Stage Control – 24 Vac Input and 24 Vac Load. Fig. 10. Wiring for Two-Stage Control with 120 Vac (120 Vac Input and 120 Vac Load Shown).Fig. 11. Wiring for Two-Stage Control with 240 Vac. Fig. 12. Wiring for Four-Stage Control with 120 Vac (120 Vac Input and 120 Vac Load Shown). L1 (HOT) L224 VAC M24476A SENSOR A C NONCC NONC C NC NOC NCNO T T COM LOAD 4 NO LOAD 3 LOAD 2 LOAD 1 C+ COMNO COM NO COM NO SENSOR...
Page 8
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—138 Fig. 13. Wiring for Four-Stage Control with 240 Vac. Fig. 14. Wiring for Floating Output (Relay 1 and Relay 2 Pair Shown). Fig. 15. Wiring for ML7984 Valve Actuator (Using 4 to 20 mA Signal) . Fig. 16. Wiring for Digital Input (Dry Contact). Fig. 17. Wiring for Mod Motor or Direct Coupled Actuator with 4 to 20 mA Control Input SENSOR A C NONCC NONC C NCNOC NCNO T T COM 240V M33849 LOAD 1 LOAD 3 LOAD 2 COM NO LOAD 4 C+ 120 COM 240...
Page 9
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 962-0254—13 . Fig. 18. Wiring for Mod Motor or Direct Coupled Actuator with 0 to 10 Vdc Control Input Fig. 19. Wiring for Series 90 Modutrol Motor Control. Fig. 20. Wiring for Changeover Relay and Minimum Position Potentiometer Used with Series 90 Modutrol Motors. T1 T2 C R POWER USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.1 HONEYWELL MODUTROL MOTOR WITH VOLTAGE CONTROL INPUT 1 F M24483A MODULATING OUTPUT TERMINAL (MOD 1) B R W + – B R...
Page 10
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1310 Fig. 21. Wiring for Three Series 90 Modutrol Motors . Fig. 22. Wiring for Unison Control of M9184 or M9185 Modutrol IV Motor Using One Minimum Position Potentiometer for All Motors. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. USE A 1300 OHM RESISTOR FOR T WO MOTORS, 910 OHM RESISTOR FOR THREE MOTORS. THE 407EAU RESISTOR KIT, WHICH IS SHIPPED WITH THE M9184 AND M9185 MOTORS, INCLUDES BOTH RESISTORS....