Honeywell T775abm Manual
Have a look at the manual Honeywell T775abm Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
INSTALLATION INSTRUCTIONS 62-0254-13 T775A/B/M Series 2000 Electronic Stand-Alone Controllers PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of commercial and agricultural controls capable of remote sensing of temperature and providing switched and/or proportional outputs to various types of loads. Five models have analog (modulating) outputs for actuator and motor control, and NEMA-4 weatherproof enclosures are available for wet environments. IMPORTANT Each T775A/B/M controller is an operating control, not a limit or safety control. If used in applications requiring safety or limit controls, a separate safety or limit control device is required. Table 1. T775A/B/M Controller Configurations. Controller Modela a All models include a digital input for use with the disable or setback option.Description ReplacesSPDT Relay OutputsAnalog (Mod) Outputs b b The modulating (analog) outputs are 4-20 mA, 0-10 Vdc, 2-10 Vdc, or Series 90 selectable.Floating Outputs c c Each floating output eliminates two SPDT relays.Sensor InputsNbr of Sensors Included Enclosure T775A2009 Standard T775A1001 1 None None 1 1 NEMA 1 T775B2016 Standard N/A 2 None 1 2 1 NEMA 4X T775B2024 Standard T775C1009 T775D1008 4 None 2 2 1 NEMA 4X T775B2032 Standard T775A1019 T775B1000 2 None 1 2 1 NEMA 1 T775B2040 Standard T775A1027 T775A1035 T775B1018 T775B1026 T775B10424None2 21 NEMA 1 T775M2006 Modulating N/A None 2 N/A 2 1 NEMA 1 T775M2014 Modulating T775G1005 T775G1013 T775G1021 T775G103942 N/A 2 d d These models can support a high/low modulating limit at Sensor B for temperature control at Sensor A.1 NEMA 4X T775M2022 Modulating N/A 2 2 N/A 2 d1 NEMA 4X T775M2030 Modulating T775E1114 T775F1022 T775F1055 T775F108942 N/A 2 d1 NEMA 1 T775M2048 Modulating T775E1015 T775E1023 T775E1056 T775E1064 T775E109822 N/A 2 d1 NEMA 1
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—132 Temperature Sensorsa The controller accepts 1,097 Ohms PTC at 77°F (25°C): • 50021579-001 – Standard sensor (included with all models except NEMA 4X models) • T775-SENS-STRAP– Strap on sensor with wiring box • T775-SENS-WR – Water resistant with 5 foot leads (included with NEMA 4X models) • T775-SENS-WT – Watertight with 6 foot lead • T775-SENS-OAT – Outdoor air temperature sensor • C7031B2005 – 6 inch duct mount with wiring box • C7031D2003 – 5 inch immersion sensor with wiring box (use immersion well; P/N 50001774-001) • C7031J2009 – 12 foot duct averaging sensor with wiring box • C7046D1008 – 8 inch duct probe with mounting flange • C7100D1001 – 12 inch fast response, duct averaging sensor with flange • C7130B1009 – Room mount sensor Accessories • 107324A – Bulb Holder, duct insertion • 107408 – Heat Conductive Compound, 4 ounce • 50001774-001 – Immersion Well, stainless steel 304, 1/2 in. threading. Product Changes Below are the changes to T775A/B/M models starting with Series 3 (March 2009). Series 3 can be identified by the sideways 3 after the part number on the device label. 1.Modulating high and low limit now both function in either the heat or the cool mode. 2.MIN ON added. 3.SYNC added. 4.Differential and throttling range increased to 300°F. 5.Setpoint and Enable options added to the DI options. 6.HIDE option added to MOD1 and MOD2 (to hide them on the home screen). Controller Dimensions Fig. 1. T775A/B/M Dimensions in inches (mm). aSee form 62-0265 - Temperature Sensors for the T775 Series 2000 Stand-alone Controller 4 13/32 (112.1) 1/2 (12.4) 3 31/32 (101) 7 23/32 (196) 8 5/32 (207.1) 2 15/16 (74)7/8 (22.5)1 (25.5) 4 1/16 (103.4) 4 1/16 (103.4)1/64 (3.8) 2 11/16 (68.1) 7/8 (22.5)2 13/16 (71.8) 7/8 (22.5) 1 (25.5) 7/8 (22.5) M24279 TOP BOTTOM LEFTRIGHT FRONT VIEW
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 362-0254—13 BEFORE INSTALLATION Review the “SPECIFICATIONS” on page 35 before installing the controller. When Installing This Product 1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. 2.Check ratings given in instructions and on the product to ensure the product is suitable for your application. 3.Installer must be a trained, experienced service technician. 4.After installation is complete, check out product operation as provided in these instructions. INSTALLATION AND SETUP The following installation procedures are typically performed in the order listed: 1.Mounting — See “MOUNTING” below. 2.Wiring — See “WIRING” on this page. 3.Checkout — See page 11. 4.Programming — See page 14. 5.Scheduling (optional) — See page 30. Additional topics are: • Temperature sensor calibration begins on page 11. • Interface overview begins on page 12. • Setup (for advanced options) begins on page 17. • Summary menu begins on page 34. • Troubleshooting begins on page 34. MOUNTING This section describes the mounting procedures for the controller and temperature sensor(s). Controller Mounting IMPORTANT Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller circuit board, or in areas where escaping gas or other explosive vapors are present. IMPORTANT The controller must be mounted in a position that allows clearance for wiring, servicing, and removal. Use a screwdriver to pry out only the knockouts that you will use. If mounting on DIN rail, be sure to remove the knockouts before mounting. See “Controller Wiring” on page 5 and Fig. 7 on page 6 for recommended knockout usage and locations. If you do not use an opened knockout be sure to cover it. Mount the controller on any convenient interior location using the four mounting holes provided on the back of the enclosure using #6 or #8 screws (screws are not provided and must be obtained separately). Use controller dimensions in Fig. 1 on page 2 as a guide.The controller may be mounted in any orientation. However, mounting in the orientation shown in Fig. 1 on page 2 permits proper viewing of the LCD display and use of the keypad. NEMA 4 Enclosure Mounting For models with NEMA 4 enclosures, ensure that waterproof wire/conduit fittings are used at the knockouts for all wiring attachments. Refer to Fig. 7 on page 6 for knockout locations. IMPORTANT For NEMA 4 enclosures, be sure to cover and seal all unused open knockouts. Temperature Sensor(s) Mounting and Location Temperature sensors may be located up to 1,000 feet (304 m) from the T775A/B/M controller. Refer to Table 3 on page 11 for calibration guidelines. The sensors may be mounted on a wall or panel for sensing space temperature, strapped to a pipe or inserted in an immersion well (see Fig. 2) for hot or cold water sensing, or taped to a standard cap or bulb holder for duct air sensing. To prevent moisture or condensation entering the sensor through the lead wire holes, mount the sensor with the lead wires exiting the bottom of the sensor. NOTES: 1. The included sensor is not designed for very wet applications. For immersion applications, an immersion well is used. 2. Heat conductive compound must be used in immersion wells. 3. Refer to the list of temperature sensors on page 2 for this type of installation . Fig. 2. Sensor Inserted in Immersion Well. NOTE: Multiple sensors may be parallel-series wired to sense average temperatures in large spaces. Refer to Fig. 3 on page 4. WIRING All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Controller wiring is terminated to the screw terminal blocks located inside the device. The remainder of this section describes the temperature sensor wiring and the T775A/B/M controller wiring. SENSOR PLACED IN WELL IMMERSION WELL 1/2 NPTUSE HEAT CONDUCTIVE COMPOUND M24470
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—134 Wiring Connections Access To access the wiring connections, remove the two screws on the left side of the enclosure and gently swing open the top. Be careful to not stress the ribbon cables that connect the keypad and LCD display to the controller circuit board. Temperature Sensor Wiring CAUTIONElectrical Shock Hazard. Can short equipment circuitry. Make sure that metal tube of sensor does not short against T terminals in wall-mounted case. IMPORTANT Poor wiring practices can cause erratic readings from the sensor. Avoid the following to ensure proper operation: • Do not route the temperature sensor wiring with building power wiring. • Do not locate the temperature sensor wiring next to control contactors. • Do not locate the temperature sensor wiring near electrical motors. • Do not locate the temperature sensor wiring near welding equipment. • Make sure good mechanical connections are made to both the sensor and the controller. • Do not mount the sensor with the lead wire end pointing up in an area where condensation can occur. If any of the above conditions cannot be avoided, use shielded cable. NOTE: Each T775 controller must be wired to its own sensor(s). However, a benefit of the T775 controller’s accuracy is that there is no more than a 2° F (-7° C) differential between any two T775 controllers. Multiple Parallel Sensors Multiple sensors can be parallel-series wired to sense average temperatures in large spaces. To maintain control accuracy, the number of sensors to be parallel-series wired must be of the n 2 power (for example, 4, 9, 16, etc.). Refer to Fig. 3 . Fig. 3. Parallel-Series Wiring of Sensors. Temperature Sensor Wire Type and Size Temperature sensors use standard AWG 18/2 unshielded wire. For cable runs greater than 25 feet or where electrical interference may be a problem, shielded cable is recommended (See Fig. 4). Refer to “Temperature Sensor Calibration” on page 11 for wire size selection where cable runs are longer than 25 feet. Fig. 4. Sensor Wiring — Showing Shielded Cable Connection to Sensor A. TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).SENSORSM24471 M24472 SHIELDED CABLE SHIELDED CABLE SENSOR SENSOR A AND SENSOR B TERMINAL WIRING IS POLARITY INSENSITIVE.1 NOTE: SHIELDED CABLE MUST BE CONNECTED TO AN EARTH GROUND. HOWEVER, DO NOT GROUND SHIELDED CABLE AT SENSOR END. NOTE: TO MINIMIZE NOISE PICKUP, MAKE SENSOR CONNECTION FROM SHIELDED CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY.T T T T SENSOR A SENSOR B1
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 562-0254—13 Controller Wiring WARNINGElectrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage. CAUTIONDo not use 24 Vac power to power any external loads if 120 Vac or 240 Vac is used to power the T775A/B/M controller. CAUTIONA separate earth ground is required. Equipment damage can result if the earth ground is not connected. See Fig. 5 and Table 2 on page 6. CAUTIONEquipment Damage Hazard. Electrostatic discharge can short equipment circuitry. Ensure that you are properly grounded before handling the unit . Fig. 5. Earth Ground. IMPORTANT Poor wiring practices can cause erratic readings from the sensor. To ensure proper operation, ensure that good mechanical connections are made to both the sensor and the controller. IMPORTANT When wiring the input power, only one source of power can be applied to the T775A/B/M controller (24 Vac or 120 Vac or 240 Vac). See Fig. 7 on page 6 for locating the appropriate power input, remote sensors input, low voltage, contact closure, and load output terminals. Access to the terminals can be gained through standard conduit knockouts (A through E in Fig. 7 on page 6) located around the perimeter of the enclosure: • Knockouts A and B should be used only for sensor and low-voltage wiring. • Knockouts C, D, and E can be used to gain access to the load relay output terminals and 120/240 Vac power wiring. Controller Wiring Method Wire the sensors and outputs, then wire the power connection. Each terminal can accommodate the following gauges of wire: • Single wire – from 14 AWG to 22 AWG solid or stranded • Multiple wires – up to two 22 AWG stranded For 24, 120, or 240 Vac power connections: • Single wire – from 14 to 18 AWG solid or stranded Prepare wiring for the terminal blocks, as follows: 1.Strip 1/2 in. (13 mm) insulation from the conductor. 2.Cut a single wire to 3/16 in. (5 mm). Insert the wire in the required terminal location and tighten the screw. 3.If two or more wires are being inserted into one terminal location, twist the wires together a minimum of three turns before inserting them to ensure proper electrical contact. 4.Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the screw. 5.Pull on each wire in all terminals to check for good mechanical connection . Fig. 6. Attaching Two or More Wires at Terminal Blocks. C+W 1 2 M24296 NO HIGH VOLTAGE. CLASS 2 WIRING ONLY. EARTH GROUND TERMINAL MUST BE CONNECTED TO CONDUIT CLAMP LOCALLY.1 2 1/2 (13) 1. STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL. 2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS). 3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION. M24473
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—136 Controller Wiring Details The wiring connection terminals are shown in Fig. 7 and are described in Table 2. See Fig. 8 – 22 beginning on page 6 for typical T775A/B/ M wiring applications. Fig. 7. T775A/B/M Terminal and Feature Locations. NOTE: Refer to Table 1 on page 1 for the specific configuration of sensors and outputs supported by the model you are installing. NOTE: For NEMA 4 enclosures, use waterproof fit- tings for wiring/conduit connections at knockouts. WIRING APPLICATIONS (EXAMPLES) Fig. 8 – 22 illustrate typical controller wiring for various applications. NOTE: The electronic Series 90 output provided with modulating T775 models can not drive elec- tro-mechanical slidewire devices like older Series 3 modulating meters (prior to Series 6), V9055s, and S984s. Fig. 8. Wiring for Two-Stage Control – 24 Vac Input and 24 Vac Load. Table 2. Description of Wiring Terminal Connections. Connection Terminal Label Description Sensors Sensor A T T Temperature Sensor; polarity insensitive Sensor B Outputs Relay 1 Relay 2 Relay 3 Relay 4NO COM NC120-240 Vac Relay Output Mod 1 + - (Vdc or mA) W R B (Series 90) aModulating Output Mod 2 M24474 C NO NCC NO NC C NC NOC NC NO T T T T B R W + – + – B R W + – SENSOR A SENSOR B MOD 2 MOD 1 KNOCKOUT A DIGITAL INPUT POWER 120/240 VAC OUTPUT RELAY 2 KNOCKOUT D POWER 24 VAC OUTPUT RELAY 1 KNOCKOUT C KNOCKOUT E SENSORS A AND B USE THE TWO TT CONNECTIONS AND ARE POLARITY INSENSITIVE. FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT, USE SIGNAL (+) & COMMON (-). FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B. A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER SOURCE (24, 120, OR 240 VAC).1 21 2 OUTPUT RELAY 3 KNOCKOUT B OUTPUT RELAY 4 3 3C+ 120 COM 240 Input DI + - Digital Input (dry contact) 24 Vac Power 24V + + 24 Vac Hot Common C 24 Vac Common Ground Earth Ground b 120 or 240 Vac Power 120 Vac 120 120 Vac Power Common COM Common 240 Vac 240 240 Vac Power aFor Series 90 connections, you must insert a 340 Ohm resistor across terminals R and W. Refer to Fig. 19 on page 9. The resistor is included with the controller. bA separate earth ground is required for all installations regardless of the power source (24, 120, or 240 Vac). Refer to Fig. 5 on page 5.Table 2. Description of Wiring Terminal Connections. (Continued) Connection Terminal Label Description L1 (HOT) L224 VAC COM NO COMNO M24475A LOAD 2 LOAD 1 SENSOR A C NONCC NONC T T C+
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 762-0254—13 Fig. 9. Wiring for Four-Stage Control – 24 Vac Input and 24 Vac Load. Fig. 10. Wiring for Two-Stage Control with 120 Vac (120 Vac Input and 120 Vac Load Shown).Fig. 11. Wiring for Two-Stage Control with 240 Vac. Fig. 12. Wiring for Four-Stage Control with 120 Vac (120 Vac Input and 120 Vac Load Shown). L1 (HOT) L224 VAC M24476A SENSOR A C NONCC NONC C NC NOC NCNO T T COM LOAD 4 NO LOAD 3 LOAD 2 LOAD 1 C+ COMNO COM NO COM NO SENSOR A C NONCC NONC T T COMLOAD 2 LOAD 1 NO COMNOCOM120V M33846 C+ 120 COM 240POWER SUPPLYL1 ( H O T ) L2 SENSOR A C NONCC NONC T T COMLOAD 2 LOAD 1 NO COMNOCOM 240V M33847 C+ 120 COM 240POWER SUPPLYL1 ( H O T ) L2 SENSOR A C NONCC NONC C NCNOC NCNO T T COM120V M33848 LOAD 1 LOAD 3 LOAD 2 COM NO LOAD 4 C+ 120 COM 240 COMNO
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—138 Fig. 13. Wiring for Four-Stage Control with 240 Vac. Fig. 14. Wiring for Floating Output (Relay 1 and Relay 2 Pair Shown). Fig. 15. Wiring for ML7984 Valve Actuator (Using 4 to 20 mA Signal) . Fig. 16. Wiring for Digital Input (Dry Contact). Fig. 17. Wiring for Mod Motor or Direct Coupled Actuator with 4 to 20 mA Control Input SENSOR A C NONCC NONC C NCNOC NCNO T T COM 240V M33849 LOAD 1 LOAD 3 LOAD 2 COM NO LOAD 4 C+ 120 COM 240 COMNO C NONCC NONC M31361 CLOSE RELAY TO DRIVE DEVICE CLOSED. RELAY 1 SHOWN. (RELAYS 1 AND 3 ARE USED FOR CLOSE). CLOSE RELAY TO DRIVE DEVICE OPEN. RELAY 2 SHOWN. (RELAYS 2 AND 4 ARE USED FOR OPEN). THE RELAYS MUST BE WIRED IN PAIRS WITH RELAYS 1 AND 2 BEING THE FIRST PAIR, AND RELAYS 3 AND 4 BEING THE SECOND PAIR. 12 1 2 120/240 VAC LINE CLOSEDEVICE COM OPEN NO COM NO COMRELAY 1RELAY 2 M27228A MODULATING OUTPUT TERMINAL (MOD 1) B R W + – B R W + – T1 T2 B WRC POWER ML7984 ACTUATOR M24482 DIGITAL INPUT+ – USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.1M24481A MODULATING OUTPUT TERMINAL (MOD 1) B R W + – B R W + – POWER1 T1 T2–+ HONEYWELL MODUTROL MOTOR WITH 4-20 mA MODULATING INPUT
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 962-0254—13 . Fig. 18. Wiring for Mod Motor or Direct Coupled Actuator with 0 to 10 Vdc Control Input Fig. 19. Wiring for Series 90 Modutrol Motor Control. Fig. 20. Wiring for Changeover Relay and Minimum Position Potentiometer Used with Series 90 Modutrol Motors. T1 T2 C R POWER USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.1 HONEYWELL MODUTROL MOTOR WITH VOLTAGE CONTROL INPUT 1 F M24483A MODULATING OUTPUT TERMINAL (MOD 1) B R W + – B R W + – M24484A TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN THE MOD 1 TERMINALS W AND R. - MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC - MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC. INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.1 2 3 MODULATING OUTPUT TERMINAL (MOD 1) B R W + – B R W + – T1 T2 B WR POWER HONEYWELL ELECTRONIC SERIES 90 MODUTROL MOTOR 1 2 3 M24485A USE SEPAR ATE TR ANSFORMER FOR T775R WHEN USING 24 VAC. A 250 OHM RESISTOR PROVIDES 40% AUTHORIT Y WHEN USING A 150 OHM MINIMUM POSITION POTENTIOMETER. INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.1 2 MODULATING OUTPUT TERMINAL (MOD 1) B R W + – B R W + – T1 T2 B WR POWER 2 HONEYWELL ELECTRONIC SERIES 90 MODUTROL MOTOR 1 WRB MINIMUM POSITION POTENTIOMETER (Q209)SPDT CHANGEOVER (H205 OR H705) 3 3
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1310 Fig. 21. Wiring for Three Series 90 Modutrol Motors . Fig. 22. Wiring for Unison Control of M9184 or M9185 Modutrol IV Motor Using One Minimum Position Potentiometer for All Motors. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. USE A 1300 OHM RESISTOR FOR T WO MOTORS, 910 OHM RESISTOR FOR THREE MOTORS. THE 407EAU RESISTOR KIT, WHICH IS SHIPPED WITH THE M9184 AND M9185 MOTORS, INCLUDES BOTH RESISTORS. INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.1 2 1 2M9184 OR M9185 MODUTROL MOTOR W R B TRTR W R B TRTR W R B TRTR M9184 OR M9185 MODUTROL MOTOR M9184 OR M9185 MODUTROL MOTOR L1 (HOT)L2 M24486 MODULATING OUTPUT TERMINAL (MOD 1) B R W + – B R W + – 3 3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. UP TO SIX SIMILAR MOTORS CAN BE CONNECTED IN UNISON. USE RESISTOR BETWEEN R AND B ON THE MOD 1 TERMINAL: 1300 OHMS FOR TWO MOTORS; 910 OHMS FOR THREE MOTORS (4074EAU KIT). IF COMMON TRANSFORMER IS USED, ALL MOTORS MUST BE IN PHASE. CONNECT THE SAME TRANSFORMER LEAD TO T1 ON EACH MOTOR, CONNECT THE OTHER TRANSFORMER LEAD TO T2 ON EACH MOTOR. USE TEMPERATURE CONTROLLER SUCH AS H205 OR H705, OR T675A FOR CHANGEOVER CONTROL. AUTHORITY OF MINIMUM POSITION POTENTIOMETER, IF USED, INCREASES WITH THE NUMBER OF MOTORS IN PARALLEL. WITH ONE MOTOR, 50% STROKE; WITH TWO MOTORS, 100% STROKE; WITH THREE MOTORS, 100% STROKE WITH 1/3 OF FULL POTENTIOMETER ROTATION. REVERSING THE B AND W TERMINALS ON ONE OR MORE MOTORS WILL NOT AFFECT CONTROL PERFORMANCE ON THE OTHER MOTORS. THE SYSTEM CAN BE CONFIGURED TO HAVE SOME MOTORS BE REVERSE ACTING AND OTHER MOTORS BE DIRECT ACTING. USE SEPARATE TRANSFORMER FOR T775 WHEN POWERING FROM 24 VAC. THE SYSTEM IS SHOWN CONNECTED FOR COOLING. FOR HEATING, REVERSE THE W AND B LEADS OF THE MODULATING OUTPUT ON THE T775 CONTROLLER. 1 1 2M9184 OR M9185 MODUTROL MOTOR W R B TRTR W R B TRTR W R B TRTR M9184 OR M9185 MODUTROL MOTOR M9184 OR M9185 MODUTROL MOTOR L1 (HOT) L2 WRB MINIMUM POSITION POTENTIOMETER (Q209/S963) 123W B R CHANGEOVER CONTROLLER 642 2 2 5 7 3 9 6 4 5 7 3 8 9M24487 MODULATING OUTPUT TERMINAL (MOD 1) B R W + – + – B R W + – POWER 24 VAC8 C+