Home > Honeywell > Controller > Honeywell T775abm Manual

Honeywell T775abm Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell T775abm Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							INSTALLATION INSTRUCTIONS
    62-0254-13
    T775A/B/M Series 2000 
    Electronic Stand-Alone 
    Controllers
    PRODUCT DESCRIPTION
    The T775 electronic stand-alone controllers are the next 
    generation of commercial and agricultural controls 
    capable of remote sensing of temperature and providing 
    switched and/or proportional outputs to various types of 
    loads.
    Five models have analog (modulating) outputs for 
    actuator and motor control, and NEMA-4 weatherproof 
    enclosures are available for wet environments.
    IMPORTANT
    Each T775A/B/M controller is an operating 
    control, not a limit or safety control. If used in 
    applications requiring safety or limit controls, a 
    separate safety or limit control device is 
    required.
    Table 1. T775A/B/M Controller Configurations.
    Controller
    Modela
    a
    All models include a digital input for use with the disable or setback option.Description ReplacesSPDT
    Relay
    OutputsAnalog
    (Mod)
    Outputs
    b
    b
    The modulating (analog) outputs are 4-20 mA, 0-10 Vdc, 2-10 Vdc, or Series 90 selectable.Floating
    Outputs
    c
    c
    Each floating output eliminates two SPDT relays.Sensor
    InputsNbr of
    Sensors
    Included Enclosure
    T775A2009 Standard T775A1001 1 None None 1 1 NEMA 1
    T775B2016 Standard N/A 2 None 1 2 1 NEMA 4X
    T775B2024 Standard T775C1009   T775D1008 4 None 2 2 1 NEMA 4X
    T775B2032 Standard T775A1019   T775B1000 2 None 1 2 1 NEMA 1
    T775B2040 Standard T775A1027   T775A1035
    T775B1018   T775B1026
    T775B10424None2 21 NEMA 1
    T775M2006 Modulating N/A None 2 N/A 2 1 NEMA 1
    T775M2014 Modulating T775G1005   T775G1013
    T775G1021   T775G103942 N/A
    2
    d
    d
    These models can support a high/low modulating limit at Sensor B for temperature control at Sensor A.1 NEMA 4X
    T775M2022 Modulating N/A 2 2 N/A
    2
    d1 NEMA 4X
    T775M2030 Modulating T775E1114   T775F1022
    T775F1055   T775F108942 N/A
    2
    d1 NEMA 1
    T775M2048 Modulating T775E1015   T775E1023
    T775E1056   T775E1064
    T775E109822 N/A
    2
    d1 NEMA 1 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—132
    Temperature Sensorsa
    The controller accepts 1,097 Ohms PTC at 77°F (25°C):
    • 50021579-001 – Standard sensor (included with all 
    models except NEMA 4X models)
    • T775-SENS-STRAP– Strap on sensor with wiring box
    • T775-SENS-WR – Water resistant with 5 foot leads 
    (included with NEMA 4X models)
    • T775-SENS-WT – Watertight with 6 foot lead
    • T775-SENS-OAT – Outdoor air temperature sensor
    • C7031B2005 – 6 inch duct mount with wiring box
    • C7031D2003 – 5 inch immersion sensor with wiring 
    box (use immersion well; P/N 50001774-001)
    • C7031J2009 – 12 foot duct averaging sensor with 
    wiring box
    • C7046D1008 – 8 inch duct probe with mounting flange
    • C7100D1001 – 12 inch fast response, duct averaging 
    sensor with flange
    • C7130B1009 – Room mount sensor
    Accessories
    • 107324A – Bulb Holder, duct insertion
    • 107408 – Heat Conductive Compound, 4 ounce
    • 50001774-001 – Immersion Well, stainless steel 304,
    1/2 in. threading.
    Product Changes
    Below are the changes to T775A/B/M models starting with 
    Series 3 (March 2009). Series 3 can be identified by the 
    sideways 3 after the part number on the device label.
    1.Modulating high and low limit now both function in 
    either the heat or the cool mode.
    2.MIN ON added.
    3.SYNC added.
    4.Differential and throttling range increased to 300°F.
    5.Setpoint and Enable options added to the DI 
    options.
    6.HIDE option added to MOD1 and MOD2 (to hide 
    them on the home screen).
    Controller Dimensions
    Fig. 1. T775A/B/M Dimensions in inches (mm).
    aSee form 62-0265 - Temperature Sensors for the T775 
    Series 2000 Stand-alone Controller
    4 13/32 (112.1)
    1/2 (12.4)
    3 31/32 (101)
    7 23/32
    (196) 8 5/32
    (207.1) 2 15/16 (74)7/8 (22.5)1 (25.5)
    4 1/16 (103.4)
    4 1/16 (103.4)1/64 (3.8)
    2 11/16 (68.1)
    7/8 (22.5)2 13/16 (71.8)
    7/8 (22.5)
    1 (25.5) 7/8 (22.5)
    M24279
    TOP
    BOTTOM LEFTRIGHT
    FRONT VIEW 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    362-0254—13
    BEFORE INSTALLATION
    Review the “SPECIFICATIONS” on page 35 before 
    installing the controller.
    When Installing This Product
    1.Read these instructions carefully. Failure to follow 
    them could damage the product or cause a 
    hazardous condition.
    2.Check ratings given in instructions and on the 
    product to ensure the product is suitable for your 
    application.
    3.Installer must be a trained, experienced service 
    technician.
    4.After installation is complete, check out product 
    operation as provided in these instructions.
    INSTALLATION AND SETUP
    The following installation procedures are typically 
    performed in the order listed:
    1.Mounting — See “MOUNTING” below.
    2.Wiring — See “WIRING” on this page.
    3.Checkout — See page 11.
    4.Programming — See page 14.
    5.Scheduling (optional) — See page 30.
    Additional topics are:
    • Temperature sensor calibration begins on page 11.
    • Interface overview begins on page 12.
    • Setup (for advanced options) begins on page 17.
    • Summary menu begins on page 34.
    • Troubleshooting begins on page 34.
    MOUNTING
    This section describes the mounting procedures for the 
    controller and temperature sensor(s).
    Controller Mounting
    IMPORTANT
    Avoid mounting in areas where acid fumes or 
    other deteriorating vapors can attack the metal 
    parts of the controller circuit board, or in areas 
    where escaping gas or other explosive vapors 
    are present.
    IMPORTANT
    The controller must be mounted in a position that 
    allows clearance for wiring, servicing, and 
    removal.
    Use a screwdriver to pry out only the knockouts that you 
    will use. 
    If mounting on DIN rail, be sure to remove the knockouts 
    before mounting. See “Controller Wiring” on page 5 and 
    Fig. 7 on page 6 for recommended knockout usage and 
    locations. If you do not use an opened knockout be sure 
    to cover it.
    Mount the controller on any convenient interior location 
    using the four mounting holes provided on the back of the 
    enclosure using #6 or #8 screws (screws are not provided 
    and must be obtained separately). Use controller 
    dimensions in Fig. 1 on page 2 as a guide.The controller may be mounted in any orientation. 
    However, mounting in the orientation shown in Fig. 1 on 
    page 2 permits proper viewing of the LCD display and use 
    of the keypad.
    NEMA 4 Enclosure Mounting
    For models with NEMA 4 enclosures, ensure that 
    waterproof wire/conduit fittings are used at the knockouts 
    for all wiring attachments. Refer to Fig. 7 on page 6 for 
    knockout locations.
    IMPORTANT
    For NEMA 4 enclosures, be sure to cover and 
    seal all unused open knockouts.
    Temperature Sensor(s) Mounting 
    and Location
    Temperature sensors may be located up to 1,000 feet 
    (304 m) from the T775A/B/M controller. Refer to Table 3 
    on page 11 for calibration guidelines.
    The sensors may be mounted on a wall or panel for 
    sensing space temperature, strapped to a pipe or inserted 
    in an immersion well (see Fig. 2) for hot or cold water 
    sensing, or taped to a standard cap or bulb holder for duct 
    air sensing. To prevent moisture or condensation entering 
    the sensor through the lead wire holes, mount the sensor 
    with the lead wires exiting the bottom of the sensor.
    NOTES:
    1. The included sensor is not designed for very 
    wet applications. For immersion applications, 
    an immersion well is used.
    2. Heat conductive compound must be used in 
    immersion wells. 
    3. Refer to the list of temperature sensors on 
    page 2 for this type of installation
    .
    Fig. 2. Sensor Inserted in Immersion Well.
    NOTE: Multiple sensors may be parallel-series wired 
    to sense average temperatures in large 
    spaces. Refer to Fig. 3 on page 4.
    WIRING
    All wiring must comply with applicable electrical codes 
    and ordinances, or as specified on installation wiring 
    diagrams. Controller wiring is terminated to the screw 
    terminal blocks located inside the device.
    The remainder of this section describes the temperature 
    sensor wiring and the T775A/B/M controller wiring.
    SENSOR
    PLACED
    IN WELL
    IMMERSION
    WELL 1/2 NPTUSE HEAT
    CONDUCTIVE
    COMPOUND
    M24470 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—134
    Wiring Connections Access
    To access the wiring connections, remove the two screws 
    on the left side of the enclosure and gently swing open the 
    top. Be careful to not stress the ribbon cables that connect 
    the keypad and LCD display to the controller circuit board.
    Temperature Sensor Wiring
    CAUTIONElectrical Shock Hazard.
    Can short equipment circuitry.
    Make sure that metal tube of sensor does not 
    short against T terminals in wall-mounted case.
    IMPORTANT
    Poor wiring practices can cause erratic readings 
    from the sensor. Avoid the following to ensure 
    proper operation:
    • Do not route the temperature sensor wiring with 
    building power wiring.
    • Do not locate the temperature sensor wiring next 
    to control contactors.
    • Do not locate the temperature sensor wiring near 
    electrical motors.
    • Do not locate the temperature sensor wiring near 
    welding equipment.
    • Make sure good mechanical connections are 
    made to both the sensor and the controller.
    • Do not mount the sensor with the lead wire end 
    pointing up in an area where condensation can 
    occur.
    If any of the above conditions cannot be avoided, 
    use shielded cable.
    NOTE: Each T775 controller must be wired to its own 
    sensor(s). However, a benefit of the T775 
    controller’s accuracy is that there is no more 
    than a 2° F (-7° C) differential between any 
    two T775 controllers.
    Multiple Parallel Sensors
    Multiple sensors can be parallel-series wired to sense 
    average temperatures in large spaces. To maintain control 
    accuracy, the number of sensors to be parallel-series 
    wired must be of the n
    2 power (for example, 4, 9, 16, etc.). 
    Refer to Fig. 3
    .
    Fig. 3. Parallel-Series Wiring of Sensors.
    Temperature Sensor Wire Type and Size
    Temperature sensors use standard AWG 18/2 unshielded 
    wire. For cable runs greater than 25 feet or where 
    electrical interference may be a problem, shielded cable is 
    recommended (See Fig. 4).
    Refer to “Temperature Sensor Calibration” on page 11 for 
    wire size selection where cable runs are longer than 25 
    feet.
    Fig. 4. Sensor Wiring — Showing Shielded Cable Connection to Sensor A.
    TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).SENSORSM24471
    M24472
    SHIELDED
    CABLE
    SHIELDED
    CABLE
    SENSOR
    SENSOR A AND SENSOR B TERMINAL WIRING IS POLARITY INSENSITIVE.1
    NOTE: SHIELDED CABLE MUST BE 
                CONNECTED TO AN EARTH 
                GROUND. 
                HOWEVER,  DO NOT GROUND 
                SHIELDED CABLE AT SENSOR END.
    NOTE: TO MINIMIZE NOISE PICKUP, 
      MAKE SENSOR CONNECTION FROM 
      SHIELDED CABLE AS CLOSE AS 
      POSSIBLE TO SENSOR BODY.T  
    T
    T  
    T
    SENSOR A
    SENSOR B1 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    562-0254—13
    Controller Wiring
    WARNINGElectrical Shock Hazard.
    Can cause severe injury, death or property 
    damage.
    Disconnect power supply before beginning wiring, 
    or making wiring connections, to prevent electrical 
    shock or equipment damage.
    CAUTIONDo not use 24 Vac power to power any external 
    loads if 120 Vac or 240 Vac is used to power 
    the T775A/B/M controller.
    CAUTIONA separate earth ground is required.
    Equipment damage can result if the earth ground 
    is not connected. See Fig. 5 and Table 2 on 
    page 6.
    CAUTIONEquipment Damage Hazard.
    Electrostatic discharge can short equipment 
    circuitry.
    Ensure that you are properly grounded before 
    handling the unit
    .
    Fig. 5. Earth Ground.
    IMPORTANT
    Poor wiring practices can cause erratic readings 
    from the sensor. To ensure proper operation, 
    ensure that good mechanical connections are 
    made to both the sensor and the controller.
    IMPORTANT
    When wiring the input power, only one source of 
    power can be applied to the T775A/B/M 
    controller (24 Vac or 120 Vac or 240 Vac). See Fig. 7 on page 6 for locating the appropriate power 
    input, remote sensors input, low voltage, contact closure, 
    and load output terminals. 
    Access to the terminals can be gained through standard 
    conduit knockouts (A through E in Fig. 7 on page 6) 
    located around the perimeter of the enclosure:
    • Knockouts A and B should be used only for sensor and 
    low-voltage wiring.
    • Knockouts C, D, and E can be used to gain access to 
    the load relay output terminals and 120/240 Vac power 
    wiring.
    Controller Wiring Method
    Wire the sensors and outputs, then wire the power 
    connection.
    Each terminal can accommodate the following gauges of 
    wire:
    • Single wire – from 14 AWG to 22 AWG solid or 
    stranded
    • Multiple wires – up to two 22 AWG stranded
    For 24, 120, or 240 Vac power connections:
    • Single wire – from 14 to 18 AWG solid or stranded
    Prepare wiring for the terminal blocks, as follows:
    1.Strip 1/2 in. (13 mm) insulation from the conductor.
    2.Cut a single wire to 3/16 in. (5 mm). Insert the wire 
    in the required terminal location and tighten the 
    screw.
    3.If two or more wires are being inserted into one 
    terminal location, twist the wires together a 
    minimum of three turns before inserting them to 
    ensure proper electrical contact.
    4.Cut the twisted end of the wires to 3/16 in. (5 mm) 
    before inserting them into the terminal and 
    tightening the screw.
    5.Pull on each wire in all terminals to check for good 
    mechanical connection
    .
    Fig. 6. Attaching Two or More Wires at Terminal 
    Blocks.
    C+W
    1
    2
    M24296
    NO HIGH VOLTAGE. CLASS 2 WIRING ONLY.
    EARTH GROUND TERMINAL MUST BE CONNECTED  
    TO CONDUIT CLAMP LOCALLY.1
    2
    1/2  (13) 1.  STRIP 1/2 IN. (13 MM) 
    FROM WIRES TO 
    BE ATTACHED AT 
    ONE TERMINAL.
    2. TWIST WIRES 
    TOGETHER WITH 
    PLIERS (A MINIMUM 
    OF THREE TURNS).
    3.  CUT TWISTED END OF WIRES 
    TO 3/16 IN. (5 MM) BEFORE INSERTING 
    INTO TERMINAL AND TIGHTENING SCREW. 
    THEN PULL ON EACH WIRE IN ALL 
    TERMINALS TO CHECK FOR 
    GOOD MECHANICAL CONNECTION.
    M24473 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—136
    Controller Wiring Details
    The wiring connection terminals are shown in Fig. 7 and 
    are described in Table 2.
    See Fig. 8 – 22 beginning on page 6 for typical T775A/B/
    M wiring applications.
    Fig. 7. T775A/B/M Terminal and Feature Locations.
    NOTE: Refer to Table 1 on page 1 for the specific 
    configuration of sensors and outputs 
    supported by the model you are installing.
    NOTE: For NEMA 4 enclosures, use waterproof fit-
    tings for wiring/conduit connections at 
    knockouts.
    WIRING APPLICATIONS 
    (EXAMPLES)
    Fig. 8 – 22 illustrate typical controller wiring for various 
    applications.
    NOTE: The electronic Series 90 output provided with 
    modulating T775 models can not drive elec-
    tro-mechanical slidewire devices like older 
    Series 3 modulating meters (prior to Series 
    6), V9055s, and S984s.
    Fig. 8. Wiring for Two-Stage Control – 24 Vac Input 
    and 24 Vac Load. Table 2. Description of Wiring
    Terminal Connections.
    Connection Terminal Label Description
    Sensors
    Sensor A T T Temperature Sensor; 
    polarity insensitive
    Sensor B
    Outputs
    Relay 1
    Relay 2
    Relay 3
    Relay 4NO
    COM
    NC120-240 Vac Relay 
    Output
    Mod 1 + - (Vdc or mA)
    W R B (Series 90)
    aModulating Output
    Mod 2
    M24474
    C NO
    NCC NO
    NC C NC
    NOC NC
    NO
    T  
    T
    T  
    T B
    R
    W
    + –
    + –
    B
    R
    W
    + –
    SENSOR A
    SENSOR B
    MOD 2 MOD 1 KNOCKOUT A
    DIGITAL
    INPUT
    POWER 
    120/240 VAC
    OUTPUT
    RELAY 2
    KNOCKOUT D POWER
    24 VAC
    OUTPUT
    RELAY 1
    KNOCKOUT C
    KNOCKOUT E
    SENSORS  A AND B USE THE TWO TT CONNECTIONS AND ARE 
    POLARITY INSENSITIVE.
    FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT, 
    USE SIGNAL (+) & COMMON (-).
    FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B.
    A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
    SOURCE (24, 120, OR 240 VAC).1
    21
    2
    OUTPUT
    RELAY 3 KNOCKOUT B
    OUTPUT
    RELAY 4
    3
    3C+
    120
    COM
    240
    Input
    DI  + - Digital Input (dry 
    contact)
    24 Vac Power
    24V +  + 24 Vac Hot
    Common  C 24 Vac Common
    Ground
    Earth Ground
    b
    120 or 240 Vac Power
    120 Vac 120 120 Vac Power
    Common COM Common
    240 Vac 240 240 Vac Power
    aFor Series 90 connections, you must insert a 340 Ohm 
    resistor across terminals R and W. Refer to Fig. 19 on 
    page 9. The resistor is included with the controller.
    bA separate earth ground is required for all installations 
    regardless of the power source (24, 120, or 240 Vac). 
    Refer to Fig. 5 on page 5.Table 2. Description of Wiring
    Terminal Connections. (Continued)
    Connection Terminal Label Description
    L1
    (HOT)
    L224 VAC
    COM
    NO COMNO
    M24475A
    LOAD 2
    LOAD 1
    SENSOR A
    C NONCC NONC
    T  
    T 
    C+ 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    762-0254—13
    Fig. 9. Wiring for Four-Stage Control – 24 Vac Input
    and 24 Vac Load.
    Fig. 10. Wiring for Two-Stage Control with 120 Vac 
    (120 Vac Input and 120 Vac Load Shown).Fig. 11. Wiring for Two-Stage Control with 240 Vac.
    Fig. 12. Wiring for Four-Stage Control with 120 Vac 
    (120 Vac Input and 120 Vac Load Shown).
    L1
    (HOT)
    L224 VAC
    M24476A
    SENSOR A
    C NONCC NONC C NC
    NOC NCNO
    T  
    T 
    COM LOAD
    4
    NO
    LOAD
    3 LOAD
    2
    LOAD
    1
    C+
    COMNO
    COM
    NO
    COM
    NO
    SENSOR A
    C NONCC NONC
    T  
    T 
    COMLOAD 2
    LOAD 1 NO COMNOCOM120V
    M33846
    C+
    120
    COM
    240POWER SUPPLYL1  ( H O T )
    L2
    SENSOR A
    C NONCC NONC
    T  
    T 
    COMLOAD 2
    LOAD 1 NO COMNOCOM 240V
    M33847
    C+
    120
    COM
    240POWER SUPPLYL1  ( H O T )
    L2
    SENSOR A
    C NONCC NONC
    C NCNOC NCNO
    T  
    T 
    COM120V
    M33848
    LOAD 1
    LOAD
    3
    LOAD
    2 COM
    NO
    LOAD 4
    C+
    120
    COM
    240
    COMNO 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—138
    Fig. 13. Wiring for Four-Stage Control with 240 Vac.
    Fig. 14. Wiring for Floating Output (Relay 1 and Relay 
    2 Pair Shown).
    Fig. 15. Wiring for ML7984 Valve Actuator 
    (Using 4 to 20 mA Signal)
    .
    Fig. 16. Wiring for Digital Input (Dry Contact).
    Fig. 17. Wiring for Mod Motor or Direct Coupled 
    Actuator with 4 to 20 mA Control Input
    SENSOR A
    C NONCC NONC
    C NCNOC NCNO
    T  
    T 
    COM 240V
    M33849
    LOAD 1
    LOAD
    3
    LOAD
    2 COM
    NO
    LOAD 4
    C+
    120
    COM
    240
    COMNO
    C NONCC NONC
    M31361
    CLOSE RELAY TO DRIVE DEVICE CLOSED. RELAY 1 SHOWN. 
    (RELAYS  1 AND  3 ARE  USED  FOR  CLOSE).
    CLOSE RELAY TO DRIVE DEVICE OPEN. RELAY 2 SHOWN. 
    (RELAYS  2 AND  4 ARE  USED  FOR  OPEN).
    THE RELAYS MUST BE WIRED IN PAIRS WITH RELAYS 1 AND 2 
    BEING THE FIRST PAIR, AND RELAYS 3 AND 4 BEING THE SECOND PAIR.
    12
    1
    2
    120/240 VAC LINE
    CLOSEDEVICE
    COM
    OPEN
    NO
    COM
    NO COMRELAY 1RELAY 2
    M27228A
    MODULATING OUTPUT
    TERMINAL (MOD 1)
    B
    R
    W
    + –
    B
    R
    W
    + –
    T1 T2 B WRC
    POWER
    ML7984 ACTUATOR
    M24482
    DIGITAL
    INPUT+ –
    USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.1M24481A
    MODULATING OUTPUT
    TERMINAL (MOD 1)
    B
    R
    W
    + –
    B
    R
    W
    + –
    POWER1
    T1 T2–+
    HONEYWELL MODUTROL MOTOR WITH 
    4-20 mA MODULATING INPUT 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    962-0254—13
    .
    Fig. 18. Wiring for Mod Motor or Direct Coupled 
    Actuator with 0 to 10 Vdc Control Input
    Fig. 19. Wiring for Series 90 Modutrol Motor Control.
    Fig. 20. Wiring for Changeover Relay and 
    Minimum Position Potentiometer Used
    with Series 90 Modutrol Motors.
    T1 T2 C R
    POWER
    USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.1 HONEYWELL MODUTROL MOTOR WITH
    VOLTAGE CONTROL INPUT
    1
    F
    M24483A
    MODULATING OUTPUT
    TERMINAL (MOD 1)
    B
    R
    W
    + –
    B
    R
    W
    + –
    M24484A
    TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN
    THE MOD 1 TERMINALS W AND R.
    - MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC
    - MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC
    USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
    INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.1
    2
    3
    MODULATING
    OUTPUT
    TERMINAL
    (MOD 1)
    B
    R
    W
    + –
    B
    R
    W
    + –
    T1 T2 B WR
    POWER
    HONEYWELL ELECTRONIC
    SERIES 90 MODUTROL MOTOR
    1
    2
    3
    M24485A
    USE SEPAR ATE TR ANSFORMER FOR T775R WHEN USING 24 VAC.
    A 250 OHM RESISTOR PROVIDES 40% AUTHORIT Y WHEN
    USING A 150 OHM MINIMUM POSITION POTENTIOMETER.
    INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.1
    2
    MODULATING OUTPUT
    TERMINAL (MOD 1)
    B
    R
    W
    + –
    B
    R
    W
    + –
    T1 T2 B WR
    POWER
    2 HONEYWELL
    ELECTRONIC SERIES 90
    MODUTROL MOTOR
    1
    WRB
    MINIMUM POSITION
    POTENTIOMETER
    (Q209)SPDT CHANGEOVER
    (H205 OR H705)
    3
    3 
    						
    							T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
    62-0254—1310
    Fig. 21. Wiring for Three Series 90 Modutrol Motors
    .
    Fig. 22. Wiring for Unison Control of M9184 or M9185 Modutrol IV Motor Using One Minimum Position 
    Potentiometer for All Motors.
    POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
    USE A 1300 OHM RESISTOR FOR T WO MOTORS, 910 OHM RESISTOR FOR THREE MOTORS. 
    THE 407EAU RESISTOR KIT, WHICH IS SHIPPED WITH THE M9184 AND M9185 MOTORS, 
    INCLUDES BOTH RESISTORS.
    INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.1
    2
    1
    2M9184 OR M9185
    MODUTROL MOTOR
    W
    R
    B
    TRTR
    W
    R
    B
    TRTR
    W
    R
    B
    TRTR
    M9184 OR M9185
    MODUTROL MOTOR
    M9184 OR M9185
    MODUTROL MOTOR
    L1
    (HOT)L2
    M24486
    MODULATING OUTPUT
    TERMINAL (MOD 1)
    B
    R
    W
    + –
    B
    R
    W
    + –
    3
    3
    POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
    UP TO SIX SIMILAR MOTORS CAN BE CONNECTED IN UNISON.
    USE RESISTOR BETWEEN R AND B ON THE MOD 1 TERMINAL: 1300 OHMS FOR TWO MOTORS; 910 OHMS FOR THREE MOTORS (4074EAU KIT).
    IF COMMON TRANSFORMER IS USED, ALL MOTORS MUST BE IN PHASE. CONNECT THE SAME TRANSFORMER LEAD TO T1 ON EACH MOTOR, 
    CONNECT THE OTHER TRANSFORMER LEAD TO T2 ON EACH MOTOR.
    USE TEMPERATURE CONTROLLER SUCH AS H205 OR H705, OR T675A FOR CHANGEOVER CONTROL.
    AUTHORITY OF MINIMUM POSITION POTENTIOMETER, IF USED, INCREASES WITH THE NUMBER OF MOTORS IN PARALLEL. WITH ONE MOTOR, 
    50% STROKE; WITH TWO MOTORS, 100% STROKE; WITH THREE MOTORS, 100% STROKE WITH 1/3 OF FULL POTENTIOMETER ROTATION.
    REVERSING THE B AND W TERMINALS ON ONE OR MORE MOTORS WILL NOT AFFECT CONTROL PERFORMANCE ON THE OTHER MOTORS. 
    THE SYSTEM CAN BE CONFIGURED TO HAVE SOME MOTORS BE REVERSE ACTING AND OTHER MOTORS BE DIRECT ACTING.
    USE SEPARATE TRANSFORMER FOR T775 WHEN POWERING FROM 24 VAC.
    THE SYSTEM IS SHOWN CONNECTED FOR COOLING. FOR HEATING, REVERSE THE W AND B LEADS OF THE MODULATING OUTPUT ON THE 
    T775 CONTROLLER.
    1
    1
    2M9184 OR M9185
    MODUTROL MOTOR
    W
    R
    B
    TRTR
    W
    R
    B
    TRTR
    W
    R
    B
    TRTR
    M9184 OR M9185
    MODUTROL MOTOR
    M9184 OR M9185
    MODUTROL MOTOR
    L1 (HOT) L2
    WRB
    MINIMUM
    POSITION
    POTENTIOMETER
    (Q209/S963)
    123W
    B R
    CHANGEOVER
    CONTROLLER
    642
    2
    2
    5
    7
    3
    9
    6
    4
    5
    7
    3
    8
    9M24487
    MODULATING OUTPUT TERMINAL (MOD 1)
    B
    R
    W
    + –
    + –
    B
    R
    W
    + –
    POWER
    24 VAC8
    C+ 
    						
    All Honeywell manuals Comments (0)

    Related Manuals for Honeywell T775abm Manual