Honeywell T775abm Manual
Have a look at the manual Honeywell T775abm Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 1162-0254—13 CHECKOUT Inspect all wiring connections at the controller terminals, and verify compliance with the installation wiring diagrams. WARNINGElectrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring or making wiring connections, to prevent electrical shock or equipment damage. If any wiring changes are required, first be sure to remove power from the controller before starting work. Pay particular attention to verifying the power connection (24, 120, or 240 Vac). After the controller is installed and wired, apply power. Power Loss The date and time settings are retained for 24 hours after a power outage. After a power loss of more than 24 hours, the date and time settings may need to be reentered. All other settings are stored permanently. Temperature Sensor Calibration As wire length increases, resistance increases and thus the temperature reading increases. If necessary, calibrate the sensor input by reducing the value by the amount shown in the Table 3. For example, a wire run with 18 gauge wire of 1,000 feet, requires a calibration offset of -6.0° F (-21° C). IMPORTANT If the calibration value in the table exceeds the controller’s calibration limits of +/-10° F (+/-6° C), you must use a heavier gauge wire. For example, with a wire run of 1,000 feet you must use 20 AWG wire or heavier in order to calibrate for wire loss within the limits of the controller. See “2.2.2.2. CALIBRATE (the sensor)” on page 18 for the instructions to enter the calibration value.Fig. 23 shows how sensor resistance varies with temperature for a sensor having a positive temperature coefficient (PTC) of 2.1 Ohms per degree F (3.85 Ohms per degree C) . Fig. 23. Sensor Resistance vs. Temperature. Table 3. Temperature Sensor Calibration for Resis- tance Loss Due to Wire Length. AW G Rating mΩ/ftTemperature Offset in °F (Foot) a a This is the distance from the controller to the sensor (already accounts for round trip distance).200 ft 500 ft 1,000 ft 14 2.5 0.46 1.14 2.28 16 4.0 0.72 1.82 3.64 18 6.4 1.16 2.90 5.82 20 10.2 1.86 4.64 9.28 22 16.1 2.92 7.32 14.64 AW G Rating mΩ/mTemperature Offset in °C (Meter) a 100 m 200 m 300 m 14 8.3 0.44 0.86 1.30 16 13.2 0.68 1.38 2.06 18 21.0 1.10 2.18 3.28 20 33.5 1.74 3.48 5.22 22 52.8 2.74 5.48 8.22 M24304 TEMPERATURE (DEGREES) RESISTANCE (OHMS) 1403 1317 1231 11 4 5 1059 973 20 40 60 80 100 120 140 160 180 200 220 0 10 20 30 40 50 60 70 80 90 100°F °C 0 -20 -40 120 11 0250-40 -20 -10-30 1489 887 801 1097 ± 0.08 OHMS AT 77°F (25°C) POSITIVE TEMPERATURE COEFFICIENT (PTC) OF 2.1 OHMS PER °F1 1
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1312 INTERFACE OVERVIEW The T775A/B/M controllers use an LCD panel and 6-button keypad to provide status information and permit user input of the programming, setup, and scheduling parameters. The following figure describes the display areas of the LCD and the keypad . Fig. 24. LCD Display - Home Screen And Keypad. Menu Area – On the home screen, the LCD displays the configured relays and whether they are active. In Program, Setup or Schedule mode, the LCD displays the current menu selection and its order within the menu hierarchy. Data Area – On the home screen, the LCD displays the sensors and outputs status. In Setup or Program mode, the LCD displays menu choices, parameter selections, and data values. Lock Icon – The icon indicates the MENU button is locked and prevents access to the Setup and Program menus. NOTE: Pressing and holding the HOME and MENU buttons simultaneously for five seconds locks/unlocks the MENU button. 6-Button Keypad – The keypad is used to access the menus and enter values (See “Using the LCD Panel Interface”). Using the LCD Panel Interface The 6-button keypad is used to move through the menus and enter or change parameter values. Home Button Pressing the HOME button at any time exits the current Programming or Setup display screen and returns to the home screen as shown in Fig. 24 and Fig. 25. Menu Button •Pressing the MENU button always displays the Program menu. If you are in Setup mode, you exit setup and return to the Program menu. • Pressing and holding the MENU button for five seconds leaves the current screen and displays the Setup menu. Left and Right Arrow Buttons ( and ) Use these buttons to move backward () and forward () through the Program and Setup menus. Up and Down Arrow Buttons ( and ) Use these buttons to move your selection up and down through a menu or list. • When the desired item is highlighted, you press the arrow button to display that item’s content. • When a value is displayed (e.g. 70° F), the up and down arrows increase and decrease the value. NOTE: Once you select an item from a list or enter a value, pressing the or or HOME but- ton accepts your selection or value and stores it in the controller’s memory. Home Screen In the normal run state, the LCD home screen displays the current sensed temperatures, the modulating outputs status, the active status of the output relays, and error and status codes. Active relays are indicated by the small black square („) just below the relay number. Fig. 25 shows the home screen with relays 1, 2, and 4 energized. Pressing the and buttons from the home screen cycles through each modulating output that is paired with the sensor it controls and the active output relays . Fig. 25. LCD Display - Home Screen Displaying Sensors, Active Relays, and Mod Outputs. NOTE: The modulating output home screen and the relay home screen do not dynamically update the active relay status, sensor values, and modulating output percentages. The information is a snapshot taken when you press the or button to display the screen. MOD1 40% MOD2 60% DI ON HOME RELAYS 1 2 3 4 ON SENSORSSENSOR A78SENSOR B84 MENU AREA home menuF o F o DATA AREA LOCK ICON 6 BUTTON KEYPAD M24488 MOD1 40% MOD2 60% DI ON HOME RELAYS 1 2 3 4 ON SENSORS SENSOR A 78SENSOR B84 o oF F MOD1 40% MOD2 60% DI ON HOME RELAYS 1 2 3 4 ON oF oF REL 1 ON HEAT SETPOINT 60SENSOR A62 RT 12345 HRS DI ON HOME RELAYS 1 2 3 4 ON MOD 1 40% COOL SETPOINT 74SENSOR A62 o oF F M24489 MOD1 40% MOD2 60%
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 1362-0254—13 IMPORTANT After four minutes of inactivity (no buttons pressed), the LCD display reverts to the home screen display. Accessing the Menus Menus are used for programming, scheduling, viewing the summary settings, and setup of advanced options. Programming, Scheduling, and Summary Menus To access these menus from the home screen, press the MENU button (See Fig. 26) . Fig. 26. Menus. Depending on whether scheduling is enabled or not, the LCD displays one of two menus as shown in Fig. 26. Scheduling is enabled from the Setup menu’s Output settings (See “2.3.3.1. USE SCHED” on page 25). Setup Menu To access the Setup menu, press and hold the MENU button for five seconds (Refer to Fig. 27). Fig. 27. Setup Menu. Using the Menus When you are working with the menus, use the: • Left arrow button ( ) to scroll backward through the menus •Right arrow button () to select the highlighted menu item and display its content • Up and Down arrow buttons ( and ) to scroll up and down through a list of items or to increase or decrease the value of a displayed parameter NOTE: If you press the HOME button or there is no keypad activity for four minutes, you exit Program mode and return to the home screen. If you press the MENU button, you exit and return to the menu. MENU PROGRAM EXIT homemenuORMENU DISPLAY WHEN SCHEDULING IS NOT SET MENU DISPLAY WHEN SCHEDULING IS SET MENU MOD1 40% MOD2 60% DI ON HOME RELAYS 1 2 3 4 ON F o F o SENSORS SENSOR A 78SENSOR B 84 PROGRAM SCHEDULE SUMMARY EXIT M24490 homemenu SETUP MOD1 40% MOD2 60% DI ON HOME RELAYS 1 2 3 4 ON FIVE SECONDS F o F o SENSORS SENSOR A 78SENSOR B 84 SENSORS OUTPUTS EXIT M24491
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1314 1. PROGRAMMING The controller must be programmed before being placed into service. IMPORTANT During programming, the controller is live at all times. For example, the contacts may open and close when adjusting the setpoint. The Programming process uses a hierarchical menu structure that is easy to use. You press the and arrow buttons to move forward and backward through the menus. NOTES: 1. The controller interface is intuitive. You may find that you do not need the following procedure instructions to program the controller. You may want to use this procedure simply as a reference to locate the particular option or parameter of interest. 2. The menus can display only those relays that are defined in Setup (See “2.3.2. NBR OF RELAYS” on page 24). For example, if you configure only two relays, then only two relays display on the appropriate menus. 3. If you press the HOME button or there is no keypad activity for four minutes, you exit Program mode and return to the home screen. 4. If you press the MENU button, you exit Program mode and return to the menu. Setpoint and Differential The following describes the relationship between setpoint and differential for heating and cooling. These settings are programmed for each output relay. Heating Mode Setpoint and Differential In heating mode, the differential is below the setpoint. The relay de-energizes when the temperature rises to the setpoint. As the temperature drops to the setpoint minus the differential, the relay energizes. Cooling Mode Setpoint and Differential In cooling mode, the differential is above the setpoint. The relay de-energizes when the temperature falls to the setpoint. As the temperature rises to the setpoint plus the differential, the relay energizes. Setpoint High Limit You can set a single irreversible setpoint high limit maximum value, which is applied to all outputs. Adjust the setpoint (at any output) to the desired maximum setpoint. Then, simultaneously press the home, , and buttons and continue to press all three buttons for five seconds to set the setpoint high limit maximum to this value. NOTE: You must press all three buttons at exactly the same time for this action to occur. IMPORTANT 1. This action sets the maximum setpoint value of all outputs to the setpoint high limit maximum. 2. Setting the high limit setpoint maximum is irreversible. If you perform the action inadvertently gently and this setpoint adversely affects the control of your system, you must replace the controller. Programming the T775A/B/M Controller To program the controller, perform the following procedures in the order listed: 1.Enter Program mode — see “1.1. Entering Program Mode” 2.Program the Outputs — see “1.2. Program Menu for Outputs” When programming is complete, you may continue with “3. SCHEDULING” on page 30 or, for advanced options, continue with “2. SETUP (ADVANCED OPTIONS)” on page 17. Fig. 28. Program Menu. 1.1. Entering Program Mode Press the MENU button, then select PROGRAM and press the button to view the Program menu. Fig. 28 shows the Program menus for controllers with and without Modulating Outputs. NOTE: Modulating outputs are not available on the T775A and T775B controller models.ORMENU PROGRAM MENU PROGRAM M24492 RELAY 1 RELAY 2 RELAY 3 RELAY 4 EXIT MENU PROGRAM MOD 1 MOD 2 RELAY 1 RELAY 2 RELAY 3 RELAY 4 EXIT
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 1562-0254—13 Fig. 29. Program Menu Outputs. 1.2. Program Menu for Outputs Press the MENU button, select PROGRAM, then select RELAY 1 (or MOD 1) to view the parameters. Fig. 29 shows RELAY 1. NOTE: For MOD 1 and 2, THROT RNG replaces DIFFRNTL. NOTE: The Setback parameter displays only if scheduling is enabled (See Fig. 57 on page 24) or the DI Option is set to Setback. (See Fig. 60 on page 26). Continue with “1.2.1. SETPOINT”. Fig. 30. Program - Setpoint. 1.2.1. SETPOINT 1.From the menu, use the and buttons to highlight SETPOINT. 2.Press the button to display the setpoint value. 3.Use the and buttons to increase/decrease the desired setpoint temperature. Default: 70° F (21° C) Range: -40° to 248° F (-40° to 120° C) 4.Press the button to accept the setpoint temperature and display the next option. Fig. 31. Program - Differential or Throttling Range. 1.2.2. DIFFERENTIAL or THROTTLING RANGE Differential is used for Relay outputs and Throttling Range is used for Modulating outputs. 1.From the menu, use the and buttons to highlight THROT RNG or DIFFERNTL. 2.Press the button to display the throttling range value. 3.Use the and buttons to increase/decrease the desired value. Default: 20° F (-7° C) Range: 1° to 300° F (1° to 149° C). 4.Press the button to accept the value and display the next option. In heating mode, the Differential is below the setpoint. The relay de-energizes when the temperature rises to the setpoint. As the temperature drops to the setpoint minus the Differential, the relay energizes. In cooling mode, the Differential is above the setpoint. The relay de-energizes when the temperature falls to the setpoint. As the temperature rises to the setpoint plus the Differential, the relay energizes. The Throttling Range brackets the setpoint setting, e.g., if the setpoint is 72°F (22° C) and the throttling range is 10° F (-12° C), then the effective throttling temperature range is 67° to 77° F (19° to 25° C). This applies to both modulating outputs and floating outputs. PROGRAM RELAY 1MENU PROGRAM RELAY 1 SETPOINT DIFFRNTL SENSOR HEAT/COOL SETBACK EXIT M24493 ENTER SETPOINT FOR RELAY 1 PROGRAM RELAY 1 SETPOINTMENU PROGRAM RELAY 1 SETPOINT 70F o M24494 ENTER DIFFERENTIAL FOR RELAY 1 PROGRAM RELAY 1 DIFFRNTLMENU PROGRAM RELAY 1 DIFFRNTL 20F o M24495
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1316 Fig. 32. Program - Sensor. 1.2.3. SENSOR 1.From the menu, use the and buttons to highlight SENSOR. 2.Press the button to display the sensor selec- tions. 3.Use the and buttons to select Sensor A or B. 4.Press the button to accept the highlighted sen- sor and display the next option. Fig. 33. Program - Heat/Cool. 1.2.4. HEAT/COOL 1.From the menu, use the and buttons to highlight HEAT/COOL. Default: HEAT 2.Press the button to display the heat and cool selections. 3.Use the and buttons to select Heat or Cool. 4.Press the button to accept the highlighted selection and display the next option. Fig. 34. Program - Setback. 1.2.5. SETBACK The Setback temperature option displays if scheduling is enabled (See Fig. 57 on page 24) or the DI Option is set to Setback. (See Fig. 60 on page 26). This is the desired setpoint temperature that you want to use during setback mode for this output. For example, if your setpoint is 70° F (21° C) and you want the temperature to drop 10° F during setback mode, enter 60° F (16° C) as the setpoint for this output. 1.From the menu, use the and buttons to highlight SETBACK. 2.Use the and buttons to increase/decrease the desired setpoint temperature. Default: 60° F (16° C) Range: -40° to 248° F (-40° to 120° C) 3.Press the button to accept the value and display the menu. 1.2.6. Program Next Output (Mod or Relay) For the next output (Mod or Relay), select the desired output from the Program menu (Refer to Fig. 28 on page 14). Go to “1.2.1. SETPOINT” on page 15 to program the next output. When you finish programming the outputs, continue with “1.2.7. Exiting Program Mode” on page 17. MENU PROGRAM RELAY 1 SENSOR SELECT SENSOR FOR RELAY 1 SENSOR A SENSOR B PROGRAM RELAY 1 SENSOR M24496 PROGRAM RELAY 1 HEAT/COOLMENU PROGRAM RELAY 1 HEAT/COOL SELECT HEAT/COOL FOR RELAY 1 HEAT COOL M24497 ENTER SETBACK SETPOINT FOR RELAY 1 PROGRAM RELAY 1 SETBACKMENU PROGRAM RELAY 1 SETBACK 60F o M24498
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 1762-0254—13 Fig. 35. Program - Exit. 1.2.7. Exiting Program Mode Press the HOME button to leave programming mode and return to the home screen. This completes the programming procedure. 2.SETUP (ADVANCED OPTIONS) Setup provides the ability to change the factory default settings for the temperature sensors and outputs, to enable/disable reset control, and to enable/disable scheduling. NOTE: The controller interface is intuitive. You may find that you do not need the following setup instructions for the sensors and outputs. You may want to use this procedure simply as a reference to locate the particular option or parameter of interest. NOTES: 1. If you press the HOME button or there is no keypad activity for four minutes, you exit Setup mode and return to the home screen. 2. If you press the MENU button, you exit Setup mode and return to the menu. Setup Procedure The Setup process uses a hierarchical menu structure that is easy to use. You press the and arrow buttons to move forward and backward through the menus. NOTE: The menus can display only those relays that are defined in Setup (see “2.3.2. NBR OF RELAYS” on page 24). For example, if you configure only two relays, then only two relays display on the appropriate menus.Once in Setup mode, you use the — • Left arrow button ( ) to scroll backward through the Setup menus • Right arrow button ( ) to select the highlighted menu item and display its content • Up and Down arrow buttons ( and ) to scroll up and down through a list of items or to increase or decrease the value of a displayed setup parameter To change the controller’s sensors and output setup parameters, perform the following procedures in the order listed: 1.Enter Setup mode — see “2.1. Entering Setup Mode” 2.Setup Sensors — see “2.2. Setting up the Sensors” 3.Setup Outputs — see “2.3. Setting up the Outputs” on page 21 4.Exit Setup Mode — see “2.4. EXIT Setup Mode” on page 30 2.1. Entering Setup Mode To enter Setup mode, press and hold the MENU button for five seconds to display the Setup menu. Refer to Fig. 27 on page 13. Fig. 36. Setup - Sensors Menu. 2.2. Setting up the Sensors 1.From the Setup menu, use the and buttons to highlight SENSORS. 2.Press the button to display the Sensors menu. MENU PROGRAM MOD 1 MOD 2 RELAY 1 RELAY 2 RELAY 3 RELAY 4 EXIT M24499 SETUP SENSORSSETUP SENSORS # SENSORS SENSOR A SENSOR B EXIT M24500
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1318 Fig. 37. Setup - Sensors - Number of Sensors. 2.2.1. Number of SENSORS The value entered here determines the number of sensors displayed on the home screen. 1.From the Sensors menu, highlight # SENSORS then press the button to display the number of sensors. 2.Use the and buttons to enter the number of sensors (1 or 2). Default: 2 3.Press the button to accept the value and display the SENSOR A selection. Fig. 38. Setup - Sensors - Sensor A Menu. 2.2.2. SENSOR A 1.From the Sensors menu, highlight SENSOR A. 2.Press the button to display the Sensor A selections. Fig. 39. Setup - Sensors - Sensor A - Units. 2.2.2.1. UNITS (° F or ° C) IMPORTANT This is a global change and affects the unit values for all temperature parameters on all displays. The UNITS screen displays only for Sensor A. 1.From the Sensor A selections, use the and buttons to highlight UNITS. 2.Press the button to display the temperature units. 3.Use the and buttons to highlight F or C. Default: F (Fahrenheit) 4.Press the button to accept the units and return to the Sensor A selections. Fig. 40. Setup - Sensors - Sensor A - Calibrate. 2.2.2.2. CALIBRATE (the sensor) Ensure that the wire size calibration value is within the limits. See “Temperature Sensor Calibration” on page 11. 1.From the Sensor A selections, use the and buttons to highlight CALIBRATE. 2.Press the button to display the calibration degree value. 3.Use the and buttons to increase/decrease the desired calibration degrees. Default: 0.0 Range: +/-10° F (+/-6° C) 4.Press the button to accept the value and return to the Sensor A selections. ENTER NUMBER OF SENSORS SETUP SENSORS # SENSORSSETUP SENSORS # SENSORS 2 M24501 SETUP SENSORS SENSOR ASETUP SENSORS SENSOR A UNITS CALIBRATE LABEL EXIT M24502 SETUP SENSORS SENSOR A UNITSSETUP SENSORS SENSOR A UNITS SELECT UNITS FOR SENSOR A DEG F DEG C M24503 SETUP SENSORS SENSOR A CALIBRATE ENTER VALUE TO CALIBRATE SENSOR A SETUP SENSORS SENSOR A CALIBRATE M24504 0.0F o
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 1962-0254—13 Fig. 41. Setup - Sensors - Sensor A - Label. 2.2.2.3. LABEL (the sensor input) For a sensor already labeled, the display positions to and highlights that label. 1.From the Sensor A selections, use the and buttons to highlight LABEL. 2.Press the button to display the label list. 3.Use the and buttons to scroll through list and highlight the desired label. You may need to scroll up or down to view all possible labels. 4.Use the button to accept the highlighted label and exit the list. NOTE: The label names in list order are: Sensor, Boiler, Outdoor, Duct, Dischrg, Chiller, Room, Supply, Return, and Animals. Fig. 42. Setup - Sensors - Sensor A - Exit. 2.2.2.4. Exit Sensor A Setup Press thebutton to exit Sensor A selections and return to the Sensors menu. or Use the and buttons to highlight EXIT and press the button. Fig. 43. Setup - Sensors - Sensor B Menu. 2.2.3. SENSOR B For the T775M2030 and T775M2048 models only, which have a High/Low modulating temperature limit, the LIMIT item displays on the Sensor B menu. 1.From the Sensors menu, use the button to highlight SENSOR B. 2.Press the button to display the Sensor B menu. 2.2.3.1. CALIBRATE Setting the calibration value is accomplished the same way as the Sensor A. See “2.2.2.2. CALIBRATE (the sensor)” on page 18. 2.2.3.2. LABEL Setting the label is accomplished the same way as the Sensor A. See “2.2.2.3. LABEL (the sensor input)” on page 19. SETUP SENSORS SENSOR A LABELSETUP SENSORS SENSOR A LABEL SELECT LABEL FOR SENSOR A SENSOR A BOILER A OUTDOOR A DUCT A DISCHRG A CHILLER A ROOM A M24505 SETUP SENSORS SENSOR A UNITS CALIBRATE LABEL EXIT M24506 SETUP SENSORSSETUP SENSORS # SENSORS SENSOR A SENSOR B EXITSETUP SENSORS SENSOR B CALIBRATE LABEL LIMIT EXIT M24507
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS 62-0254—1320 Fig. 44. Setup - Sensors - Sensor B - Limit. 2.2.4. LIMIT (Sensor B only) For the T775M2030 and T775M2048 models only, the LIMIT item displays on the Sensor B menu. NOTE: The LIMIT option acts only on Modulating Output 1. 1.From the Sensors menu, use the button to highlight SENSOR B. 2.Press the button to display the Sensor B menu. 3.Use the and buttons to select the LIMIT item. 4.Use the button to display the Limit selections. 5.Use the and buttons to select the desired limit, (Disable, Hi Limit, or Low Limit). Default: Disable 6.Press the button to accept the value and return to the Sensor B menu. When you select Hi Limit or Low Limit, the Sensor B menu changes and adds the Hi/Low Limit and Throttling Range items. If you are setting a Hi or Low Limit, continue with “2.2.4.1. HI LIMIT or LOW LIMIT (Sensor B only)”. If you selected Disable for the Limit value, continue with “2.3. Setting up the Outputs” on page 21. Fig. 45. Setup - Sensors - Sensor B - Hi/Low Limit (showing Hi Limit). 2.2.4.1. HI LIMIT or LOW LIMIT (Sensor B only) Fig. 45 shows the High Limit, but the process is the same for setting the Low Limit. Sensor B can be assigned a high/low limit, so that as you are controlling temperature at Sensor A, the control adjusts its modulating output to prevent exceeding the user-entered limit for Sensor B. 1.From the Sensor B menu, use the button to highlight HI LIMIT or LOW LIMIT. 2.Press the button display the LIMIT value. 3.Use the and buttons to increase/decrease the desired Limit value. 4.Press the button to accept the value and return to the Limit menu. The high and low limit action will work in either the heat or the cool mode as follows: • When the low limit is used in the heat mode, the MOD1 output increases to prevent reaching the low limit at sensor B. • When the high limit is used in the heat mode, the MOD1 output decreases to prevent reaching the hi limit at sensor B. • When the low limit is used in the cool mode, the MOD1 output decreases to prevent reaching the low limit at sensor B. • When the high limit is used in the cool mode, the MOD1 output increases to prevent reaching hi limit at sensor B. SETUP SENSORS SENSOR B LIMITSETUP SENSORS SENSOR B LIMIT SELECT HI/LOW LIMIT FOR SENSOR B DISABLE HI LIMIT LOW LIMIT M24508 SETUP SENSORS SENSOR B UNITS CALIBRATE LABEL LIMIT HI LIMIT THROT RNG EXIT SETUP SENSORS SENSOR B ENTER VALUE FOR SENSOR B HI LIMITSETUP SENSORS SENSOR B HI LIM 90F o M24509