Honeywell Accenta 8 User Manual
Have a look at the manual Honeywell Accenta 8 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Accenta/Optima Engineer’s Manual 7 Fire Zone Zones 7 and 8 may be programmed as fire zones. This will automatically exclude the availability of the zone from programs and normal security applications. !# $ !%&() Figure 8. Fire Zones The fire zone detects fires all the time and will operate whether the system is Set or Unset. A fire will cause a distinctive internal sounder tone. The external sounders will pulse on and off at 2 second intervals and all RKP indicators will flash the affected zone. Zones
Accenta/Optima Engineer’s Manual 8 PA Circuit It is recommended that no more than 10 normally closed type personal attack button may be wired in series and then connected to the PA circuit. Operational in Unset and Set, the PA circuit will cause a full alarm condition when activated. PA is indicated on the control panel or RKP. PA buttons may be fitted near the front door or in a bedroom. Figure 9. PA Circuit Extension Speaker Extension speakers may be connected to the loudspeaker terminals to produce high volume alarm tones and low volume entry / exit / fault tones. Up to two 16 ohm extension speakers may be wired across the speaker terminals. Mounted in convenient positions within the installation the extension speakers will reproduce all of the alarm tones generated by the control panel. A control marked VOLUME may be used to adjust the low volume entry/exit tones to suit environmental conditions.Figure 10. Extension Speaker Wiring PA Circuit ! 1A
Accenta/Optima Engineer’s Manual 9 External Siren (Bell Box) Output The external siren (bell box) is usually installed in a high position from where the siren could be seen and heard. Terminal TADB are for connection to the external siren. These terminals provide a power/hold-off supply, sounder trigger and tamper circuit to protect the external siren housing. Figure 11. External Bell-box Wiring The terminals are summarised as follows: T = Negative (-Ve) tamper return A = Negative (-Ve) supply (0V) D = Positive (+Ve) supply (12V) B = Negative (-Ve) Sounder trigger For ease of installation, the Optima/Accenta control panels and Reson8 external sirens and modules use the same markings. Where a discrete external siren is used, it should be connected to terminals D and B. Terminals T and A are then used for tamper protection for the housing. Bell Box ! # ! #
Accenta/Optima Engineer’s Manual 10 Figure 12. Twin External Bell-box Wiring 13V Supply Output The 13V output is to power detectors which require a voltage supply (PIR detectors etc). The supply is present at all times and may be used to supply a total load of 350mA. Set The output marked SET is used with latching detectors. The output becomes positive on correct Set of the system and is removed by entry of a valid user code. Bell Box (cont’d) ! # ! #$ $
Accenta/Optima Engineer’s Manual 11 Remote Signalling Input and Outputs NOTE:These outputs are not applicable to the Optima compact panel. These terminals have been provided for connection to remote signalling equipment such as a digital communi- cator, or speech dialler. 13V 0V: These terminals provide a 13V supply for the communicator up to a total load of 200mA. OUTPUTS (J3): These outputs are programmed as active low output. They are held at 13V and fall to 0V when active, it can source or sink 10mA. These outputs would normally be connected directly to the input channels of wire in type communicators. Alternatively each output can be used to drive a relay (coil resistance > 1200 Ohms ) connected between the output terminal and the 13V supply terminal. The relay will energise when the output port operates. It is recommended that a back EMF protection diode is used in parallel with the relay coil. FIRE: The fire output operates when the fire zone is triggered. PA: The PA output operates when a PA alarm is triggered or a duress code is used. INT: The intruder output is operated when an intruder condition is triggered whilst the system is set. SET: The Set output operates whenever the system becomes set and is used to indicate opening and closing. ABORT: Operates if the panel is unset within 90 seconds of the alarm condition starting. It is cleared when the panel is reset by the user or engineer.Figure 13. Panel communicator Remote Signalling
Accenta/Optima Engineer’s Manual 12 Important Notes 1. Each output has been configured as active low. 2. Where the communicator is powered from an external source, not the panel and the outputs are being used without relays, the panel and external power supply will require a common negative supply rail. 3. If the communicator is not fitted inside the panel and abort is being used, care should be taken to ensure that the abort connection cannot be damaged or severed as this could cause the ARC to incorrectly filter an alarm signal. 4. It is very important that communicating systems are fully tested and that all signals are correctly received at the ARC when the system is installed and serviced. Filtering of Intruder alarms The exact method of filtering should be decided according to the security services / keyholder requirements and ARC procedures. In general, the panels offer the following methods that could be used to filter an alarm. Set/Unset A Set or Unset signal which is received by the ARC at around the same time as an intruder signal can be used to filter the alarm. Abort Output The abort output operates whenever a user code is entered to switch off an intruder alarm condition. When an abort signal is received by ARC at or around the same time as an intruder signal, the alarm can be filtered. Restore of the Intruder Output The intruder alarm output is restored to 12V whenever a user code is entered to switch off an intruder alarm condition. Where an intruder alarm is shortly followed by a restore at the ARC, this can be used to filter the alarm. Remote Signalling (cont’d)
Accenta/Optima Engineer’s Manual 13 Factory Set Condition User code1 0123 User code2Not programmed Duress CodeNot programmed Engineer Code9999 External siren Bell Duration 15 minutes External siren Bell Delay No delay Rearm Count3 Rearms Program 1 Zone 1 Timed Zone 2 Timed inhibit Zone 3 - 8Immediate Exit time 30 seconds Entry time 30 seconds Exit mode Timed Program 2 Zone 1 Timed Zone 2 Timed inhibit Zone 3 - 8Immediate Exit time 30 seconds Entry time 30 seconds Exit mode Disabled Program 3 Zone 1 Timed Zone 2 Timed inhibit Zone 3 - 8Immediate Exit time 30 seconds Entry time 30 seconds Exit mode Disabled Zones Security zonesZones 1 - 8 Standard Fire zonesNone programmed Double Knock zonesNone programmedOmit prevent zonesAll programmed Flag 1 Silent PA N o RKP PA Enable Yes Engineer Reset N o User reset PA No User Reset Fire No Bell in Fire N o Enable Zone 7 as Fire No Enable Zone 8 as Fire No NOTE:Zone debounce period is 400 ms Flag 2 Single Key setting N o Strobe on setting No Flag 3 Accenta Optima Version X.XX NOTE: X.XX indicates panel version eg 1.00 Factory Conditions Refer to page 17, Defaulting Panel to Factory Settings for the method of defaulting the panel.
Accenta/Optima Engineer’s Manual 14 Mains Connection The mains power should be connected using 3-core cable of not less than 1 mm sq. from a fused spur to the mains connector inside the control panel. The 2 A fused spur must be located close to the control panel. NOTE:The mains supply must be connected by a technically competent person and according to current IEE regulations. ! # $ %&& () *& +*& * )) *& Figure 14. Mains Connection CAUTION: To avoid the risk of electrical shock you must always totally isolate the mains supply before opening the control panel cover(s). Mains Input fuse rating: 125 mA, 250 V type T (anti-surge) and of a type approved to IEC 127 part 2 sheet III. On connecting the mains supply to the panel the power indicator is lit. Power Testing the System Complete the wiring of the system and then: „Fully test the system and ensure it is fault free. „Fully program the system. „Fill in the installation log at the back of the manual and retain if for future reference. „Finally explain the operation of the system to the end user. The User Guide is attached to the centre of this manual. Detach the User Guide and leave it with the user. Mains Connection
Accenta/Optima Engineer’s Manual 15 First Power Up NOTE:For Optima compact, fit the top cover on to the base and connect the speaker wires. 1 Check that the factory fitted links are connected to terminals PA, TAMP and T-A. 2 Fit the battery wires to the battery terminals (BATT). 3 On connecting the battery, the system will go into an alarm condition with an audible alarm indication. After entry of a valid user code, there is a Tamper indication. 4 Fit the cover to hold down the tamper spring at the bottom centre of the board.Figure 15. Battery Connection ! # $ %&& Loop Tamper Loop TamperLoop Tamper Loop Tamper Loop Tamper Sunday SundaySunday Sunday Sunday 01-Jan 01-Jan01-Jan 01-Jan 01-Jan 02:36 02:36 02:36 02:36 02:36 First Power Up Day LCD INDICATIONSLED INDICATIONS 5. Enter the user code, press [0][1][2][3] factory set code. The alarm condition will cease and the system will go into day mode: 6. Immediately enter the engineer code by pressing [PROG][9][9][9][9] 7. The system is now in Engineer program mode and can be programmed. 0>Walk Test 0>Walk Test0>Walk Test 0>Walk Test 0>Walk TestAttack/PA Tamper NOTE:The LCD keypad will show SYSTEM UNSET for 30 seconds first.
Accenta/Optima Engineer’s Manual 16 Engineer Program Mode The panel may be programmed to suit a wide variety of installations. Once the Engineer program mode has been accessed, each configuration may be changed in any order. Before entering Engineer program mode the system should be in the Day mode, with the Day and Power indicators lit. Indications on LED Keypads ARC Table 1. LED Indications To exit operation RESET Quit the current function Leave program menu Return one menu level System Indications System Unset System UnsetSystem Unset System Unset System Unset System Set System SetSystem Set System Set System SetSystem Unset indication System Set indication LCD IndicationsLED Indications Engineer Program Mode LED Indications LED steady on indication LED flashing indication LED off Output to A larm Recei vi ng C entre Communicator outputs are not applicable for Optima compact panel Internal Sound. In general a flat beep is an indication of an incorrect key press External D evi ce: Strobe External D evice: Si ren