Home > Honeywell > Alarm system > Honeywell Accenta 8 User Manual

Honeywell Accenta 8 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Honeywell Accenta 8 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 178 Honeywell manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Accenta/Optima Engineer’s Manual
    7
    Fire Zone
    Zones 7 and 8 may be programmed as fire zones. This will automatically exclude the availability of the zone
    from programs and normal security applications.
     
    	
       
    
       
      
    
    
     !#
    $
     !%&()
    
    Figure 8. Fire Zones
    The fire zone detects fires all the time and will operate whether the system is Set or Unset. A fire will cause a
    distinctive internal sounder tone. The external sounders will pulse on and off at 2 second intervals and all RKP
    indicators will flash the affected zone.
    Zones 
    						
    							Accenta/Optima Engineer’s Manual
    8
    PA Circuit
    It is recommended that no more than 10 normally closed type personal attack button may be wired in series
    and then connected to the PA circuit.
    Operational in Unset and Set, the PA circuit will cause a full alarm condition when activated. PA is
    indicated on the control panel or RKP.
    PA buttons may be fitted near the front door or in a bedroom.
    Figure 9. PA Circuit
    
    
    
    
    	
    
    
    
    
    
    
    
    
    Extension Speaker
    Extension speakers may be connected to the loudspeaker terminals to produce high volume alarm tones and
    low volume entry / exit / fault tones.
    Up to two 16 ohm extension speakers may be wired across the speaker terminals. Mounted in convenient
    positions within the installation the extension speakers will reproduce all of the alarm tones generated by the
    control panel.
    A control marked VOLUME may be used to adjust the low volume entry/exit tones to suit environmental
    conditions.Figure 10. Extension Speaker Wiring
    PA Circuit
    
    
    
    
    	
    	
    
    
    	
    
    
    
     	 
     	!	
    
    1A 
    						
    							Accenta/Optima Engineer’s Manual
    9
    External Siren (Bell Box) Output
    The external siren (bell box) is usually installed in a high position from where the siren could be seen and
    heard.
    Terminal TADB are for connection to the external siren. These terminals provide a power/hold-off supply,
    sounder trigger and tamper circuit to protect the external siren housing.
    Figure 11. External Bell-box Wiring
    The terminals are summarised as follows:
    T = Negative (-Ve) tamper return
    A = Negative (-Ve) supply (0V)
    D = Positive (+Ve) supply (12V)
    B = Negative (-Ve) Sounder trigger
    For ease of installation, the Optima/Accenta control panels and Reson8 external sirens and modules use the
    same markings.
    Where a discrete external siren is used, it should be connected to terminals D and B. Terminals T and A are
    then used for tamper protection for the housing.
    Bell Box
    
    
    
    
    
    
    
    	
    
    
    	
    
    
    
    
    
    
    
    	
    
    
    
    
    
    
    
     
    !
    
    
    #
     
    !
    
    # 
    						
    							Accenta/Optima Engineer’s Manual
    10
    Figure 12. Twin External Bell-box Wiring
    13V Supply Output
    The 13V output is to power detectors which require a voltage supply (PIR detectors etc). The supply is
    present at all times and may be used to supply a total load of 350mA.
    Set
    The output marked SET is used with latching detectors. The output becomes positive on correct Set of the
    system and is removed by entry of a valid user code.
    Bell Box (cont’d)
    
    
    
    
    
    	
    
    
    	
    
    
    
    
    
    
    
    	
    
    
    
    
    
    
    
     
    !
    
    
    #
    
    
    
    
    	
    
    
    
    
    
    
     !
    
    #$
    $ 
    
     
    						
    							Accenta/Optima Engineer’s Manual
    11
    Remote Signalling Input and Outputs
    NOTE:These outputs are not applicable to the Optima compact panel.
    These terminals have been provided for connection to remote signalling equipment such as a digital communi-
    cator, or speech dialler.
    13V 0V:  These terminals provide a 13V supply for the communicator up to a total load of 200mA.
    OUTPUTS (J3): These outputs are programmed as active low output. They are held at 13V and fall to 0V
    when active, it can source or sink 10mA.
    These outputs would normally be connected directly to the input channels of wire in type communicators.
    Alternatively each output can be used to drive a relay (coil resistance > 1200 Ohms ) connected between the
    output terminal and the 13V supply terminal. The relay will energise when the output port operates. It is
    recommended that a back EMF protection diode is used in parallel with the relay coil.
    FIRE: The fire output operates when the fire zone is triggered.
    PA: The PA output operates when a PA alarm is triggered or a duress code is used.
    INT: The intruder output is operated when an intruder condition is triggered whilst the system is set.
    SET: The Set output operates whenever the system becomes set and is used to indicate opening and closing.
    ABORT: Operates if the panel is unset within 90 seconds of the alarm condition starting. It is cleared when
    the panel is reset by the user or engineer.Figure 13. Panel communicator
    Remote Signalling
    
    
     	
    
     
     
    	
     
     
     
    
    
    
     
    	 	
     	
    	
    	 
    						
    							Accenta/Optima Engineer’s Manual
    12
    Important Notes
    1. Each output has been configured as active low.
    2. Where the communicator is powered from an external source, not the panel and the outputs are being
    used without relays, the panel and external power supply will require a common negative supply rail.
    3. If the communicator is not fitted inside the panel and abort is being used, care should be taken to ensure
    that the abort connection cannot be damaged or severed as this could cause the ARC to incorrectly
    filter an alarm signal.
    4. It is very important that communicating systems are fully tested and that all signals are correctly received
    at the ARC when the system is installed and serviced.
    Filtering of Intruder alarms
    The exact method of filtering should be decided according to the security services / keyholder requirements
    and ARC  procedures.
    In general, the panels offer the following methods that could be used to filter an alarm.
    Set/Unset A Set or Unset signal which is received by the ARC at around the same time as an intruder signal
    can be used to filter the alarm.
    Abort Output The abort output operates whenever a user code is entered to switch off an intruder alarm
    condition. When an abort signal is received by ARC at or around the same time as an intruder signal, the alarm
    can be filtered.
    Restore of the Intruder Output The intruder alarm output is restored to 12V whenever a user code is
    entered to switch off an intruder alarm condition. Where an intruder alarm is shortly followed by a restore at
    the ARC, this can be used to filter the alarm.
    Remote Signalling (cont’d) 
    						
    							Accenta/Optima Engineer’s Manual
    13
    Factory Set Condition
    User code1 0123
    User code2Not programmed
    Duress CodeNot programmed
    Engineer Code9999
    External siren Bell Duration 15 minutes
    External siren Bell Delay No delay
    Rearm Count3 Rearms
    Program 1
    Zone 1 Timed
    Zone 2 Timed inhibit
    Zone 3 - 8Immediate
    Exit time 30 seconds
    Entry time 30 seconds
    Exit mode Timed
    Program 2
    Zone 1 Timed
    Zone 2 Timed inhibit
    Zone 3 - 8Immediate
    Exit time 30 seconds
    Entry time 30 seconds
    Exit mode Disabled
    Program 3
    Zone 1 Timed
    Zone 2 Timed inhibit
    Zone 3 - 8Immediate
    Exit time 30 seconds
    Entry time 30 seconds
    Exit mode Disabled
    Zones
    Security zonesZones 1 - 8
    Standard Fire zonesNone programmed
    Double Knock zonesNone programmedOmit prevent zonesAll programmed
    Flag 1
    Silent PA N o
    RKP PA Enable Yes
    Engineer Reset N o
    User reset PA No
    User Reset Fire No
    Bell in Fire N o
    Enable Zone 7 as Fire No
    Enable Zone 8 as Fire No
    NOTE:Zone debounce period is 400 ms
    Flag 2
    Single Key setting N o
    Strobe on setting No
    Flag 3
    Accenta Optima Version X.XX
    NOTE: X.XX indicates panel version eg 1.00
    Factory Conditions
    Refer to page 17, Defaulting Panel to
    Factory Settings for the method of
    defaulting the panel. 
    						
    							Accenta/Optima Engineer’s Manual
    14
    Mains Connection
    The mains power should be connected using 3-core cable of not less than 1 mm sq. from a fused spur to the
    mains connector inside the control panel. The 2 A fused spur must be located close to the control panel.
    NOTE:The mains supply must be connected by a technically competent person and according to current
    IEE regulations.
    
     
    	
    
    
     
    
    
    
    
     
    	
     !
    
    #
    
    $ %&&
    
      () *&
    +*& 
    * ))
    	
     	
     *&
    Figure 14. Mains Connection
    CAUTION: To avoid the risk of electrical shock you must always totally isolate the mains
    supply before opening the control panel cover(s).
    Mains Input fuse rating: 125 mA, 250 V type T (anti-surge) and of a type approved to IEC 127 part 2
    sheet III.
    On connecting the mains supply to the panel the power indicator is lit.
    Power
    Testing the System
    Complete the wiring of the system and then:
    „Fully test the system and ensure it is fault free.
    „Fully program the system.
    „Fill in the installation log at the back of the manual and retain if for future reference.
    „Finally explain the operation of the system to the end user. The User Guide is attached to the centre of
    this manual. Detach the User Guide and leave it with the user.
    Mains Connection 
    						
    							Accenta/Optima Engineer’s Manual
    15
    First Power Up
    NOTE:For Optima compact, fit the top cover on to the base and connect the speaker wires.
    1 Check that the factory fitted links are connected to terminals PA, TAMP and T-A.
    2 Fit the battery wires to the battery terminals (BATT).
    3 On connecting the battery, the system will go into an alarm condition with an audible alarm indication.
    After entry of a valid user code, there is a Tamper indication.
    4 Fit the cover to hold down the tamper spring at the bottom centre of the board.Figure 15. Battery Connection
    
     
    	
    
    
     
    
    
    
    
     
    	
     !
    
    #
    
    $ %&&
    Loop Tamper Loop TamperLoop Tamper Loop Tamper
    Loop Tamper
    Sunday SundaySunday Sunday
    Sunday
    01-Jan 01-Jan01-Jan 01-Jan
    01-Jan
      02:36   02:36  02:36   02:36
      02:36
    First Power Up
    Day
    LCD INDICATIONSLED INDICATIONS
    5. Enter the user code, press [0][1][2][3] factory set code. The alarm condition will cease and the
    system will go into day mode:
    6. Immediately enter the engineer code by pressing [PROG][9][9][9][9]
    7. The system is now in Engineer program mode and can be programmed.
    0>Walk Test 0>Walk Test0>Walk Test 0>Walk Test
    0>Walk TestAttack/PA Tamper
    NOTE:The LCD keypad will show SYSTEM UNSET
    for 30 seconds first. 
    						
    							Accenta/Optima Engineer’s Manual
    16
    Engineer Program Mode
    The panel may be programmed to suit a wide variety of installations.
    Once the Engineer program mode has been accessed, each configuration may be changed in any order.
    Before entering Engineer program mode the system should be in the Day mode, with the Day and Power
    indicators lit.
    Indications on LED Keypads
    ARC
    Table 1. LED Indications
    To exit operation
    RESET
    Quit the current function
    Leave program menu
    Return  one menu level
    System Indications
    System Unset System UnsetSystem Unset System Unset
    System Unset
    System Set System SetSystem Set System Set
    System SetSystem Unset indication
    System Set indication LCD IndicationsLED Indications
    Engineer Program Mode
    LED Indications
    LED steady on indication
    LED flashing indication
    LED off
    Output to A larm Recei vi ng C entre
    Communicator outputs are not applicable
    for Optima compact panel
    Internal Sound. In general a flat beep is
    an indication of an incorrect key press
    External D evi ce: Strobe
    External D evice: Si ren 
    						
    All Honeywell manuals Comments (2)

    Related Manuals for Honeywell Accenta 8 User Manual